OPTIONS cONTINUEd<br />
PROgRAmmINg KIT<br />
For Type 3, Type 4 or Type 7<br />
Provides software and cable connection to a notebook<br />
computer for programming or retrieving fault interrupter<br />
control information. The cable connects the USB port of<br />
the computer to the control box (Type 3 or 4) or mechanism<br />
housing (Type 7).<br />
Catalog Number for Type 3, Type 4, Type 7: LPK7-VICSS<br />
p Programming Kit<br />
OThER cOmPATIblE RElAyS FOR OvERcURRENT<br />
PROTEcTION<br />
Various other relays can be provided <strong>with</strong> Trident switchgear<br />
including Schweitzer’s model SEL Falcon, SEL-351R,<br />
SEL-651R, SEL-501, SEL-551, SEL-351S and SEL-751A.<br />
JUNcTION bOx<br />
For auxiliary contacts and remote power/remote trip connections.<br />
Includes NEMA 4X (IP56) enclosure <strong>with</strong> terminal strip<br />
connections.<br />
p Junction Box<br />
G&W ELECTRIC PAGE 4<br />
gROUNd lUgS<br />
Bronze, eyebolt style ground lugs are available for 4/0<br />
maximum conductor cable.<br />
p Ground lug<br />
FRAmES<br />
Bolted, galvanized mounting frames are available for<br />
vertical mounting of vault style switches providing a 24”<br />
distance from the ground to the center of the bottom bushing.<br />
Other size frames are available.<br />
Consult your G&W representative for availability.<br />
bUShINgS<br />
Bushings shall be tested to IEEE 386. The switch is available<br />
<strong>with</strong> either 600A apparatus bushings or 200A deep<br />
well bushings. 600A apparatus bushings are suitable for<br />
use <strong>with</strong> T-body elbows. 200A deep well bushings can be<br />
used <strong>with</strong> 200A load break inserts and elbows.<br />
AUxIlIARy cONTAcTS<br />
Auxiliary contacts are mounted <strong>with</strong>in the mechanism<br />
housing to provide remote indication of the vacuum<br />
interrupter contact position. One normally open and one<br />
normally closed Form C contact is provided.