Zone 2 Fluorescent<br />
A linear twin lamp fluorescent<br />
luminaire suitable for areas<br />
where concentration of<br />
flammable gases or combustible<br />
dust are present<br />
Ordering Guide Lamps to be ordered separately.<br />
www.thornlighting.com.au<br />
• Electronic Ballast provides<br />
high luminous efficiency, lower<br />
energy consumption and<br />
longer service life of the lamps<br />
• Emergency operation can be<br />
set for 2 hour duration<br />
• Central locking system<br />
operated by standard SW13<br />
hex socket key enables fixture<br />
to be opened from one point<br />
of housing<br />
• Diffuser hinges from either side<br />
and is also designed to act<br />
as a convenient lamp support<br />
when open to simplify lamp<br />
replacement<br />
• IIC gas group<br />
• Exn compliant<br />
Description ILCOS Code Socket Wt (kg) Temp Class SAP Code<br />
ZONE 2 FLUORESCENT 2X18W HF FD G13 4.0 T4 96064663<br />
ZONE 2 FLUORESCENT 2X18W HF E2M FD G13 6.0 T4 96064664<br />
ZONE 2 FLUORESCENT 2X36W HF FD G13 6.0 T4 96061948<br />
ZONE 2 FLUORESCENT 2X36W HF E2M<br />
Accessory<br />
FD G13 8.0 T4 96064665<br />
ZONE 1/2 FLUORESCENT CEILING BRA KIT<br />
HF - High frequency, E2M - 2 hour maintained emergency<br />
96064666<br />
1632<br />
1660<br />
T26 (FD) G13 18-36W<br />
AS/NZS60598<br />
IP66<br />
Class I Electrical<br />
Materials/Finish<br />
Body: fibreglass reinforced<br />
polyester (GRP), grey.<br />
Diffuser: moulded<br />
polycarbonate, clear.<br />
Gasket: polyurethane foam.<br />
Cable entry: brass.<br />
Installation/Mounting<br />
Surface mounted with through<br />
wiring terminal block at each<br />
end of the fixture internally wired<br />
(4mm²) to facilitate ease of<br />
connection. 4 x M20 threaded<br />
metal entries. Ceiling mount<br />
bracket accessory available for<br />
increased support.<br />
Specification<br />
To specify state:<br />
Twin lamps linear fluorescent<br />
luminaire suitable for Zone 2,<br />
Zone 21 & 22 T4 hazardous<br />
applications.<br />
As Thorn Zone 2 Fluorescent.<br />
Compliances<br />
Australian Standard 2238<br />
Electrical Equipment for<br />
Explosive Atmosphere.<br />
Certificate of Compliance Aus<br />
Ex 3723. Australian Standard<br />
1939 Degrees of Protection of<br />
Electrical Equipment IP66.<br />
120°<br />
188<br />
46<br />
150°<br />
Cd/1000lm<br />
200 150°<br />
65<br />
130<br />
50<br />
90° 90°<br />
60°<br />
30°<br />
Zone 2 Fluorescent<br />
Lamp: 2x18W T26<br />
150<br />
100<br />
0°<br />
30°<br />
120°<br />
60°<br />
<strong>Lighting</strong> people and places<br />
177<br />
INDUSTRIAL<br />
HAZARDOUS AREA LUMINAIRES