page 16<br />

When embedding <strong>MC</strong> cable in concrete, inform other trades about the installation, so they can<br />

take appropriate care to protect the cable from damage. One way to inform other trades, when<br />

using reusable concrete forms, is to spray paint the inside of the form along the path of the <strong>MC</strong><br />

cable. When the form is removed, the paint should adhere to the concrete, marking the location<br />

of the <strong>MC</strong> cable in the concrete.<br />

• design options FoR FutuRe eleCtRiCal needs<br />

What happens with <strong>MC</strong> cable when system changes are required? What if a new cable run is needed, or<br />

a circuit needs to be upsized after the job is complete? What if <strong>MC</strong> cable is buried in concrete or direct<br />

buried? Good application design can allow for <strong>MC</strong> feeder upgrades that are cost-effective and minimally<br />

intrusive. When possible, during the design stage consider one or more of the following options:<br />

• Run an extra circuit where future expansion is anticipated.<br />

• Run one or two empty conduits to install conductors if additional circuits are needed.<br />

This is especially useful when <strong>MC</strong> cable is in concrete or direct buried.<br />

• Use a basket support system for overhead installations<br />

• Install a trench in concrete for under floor applications<br />

• Install raceways under the floor and flush with the floor for future installation and<br />

removal of <strong>MC</strong> cables.<br />

NOTE: NEC ® Article 390 for under floor raceways also covers Trench-Type<br />

Raceways Flush with Concrete.<br />

• gRounding ConsideRations<br />

NEC ® Section 330.108 requires that Type <strong>MC</strong> cable provide an adequate path for equipment grounding.<br />

The method used to achieve adequate grounding<br />

depends on the construction of the cable.<br />

Standard interlocked armor construction requires<br />

an equipment grounding conductor in the cable.<br />

The conductor may be bare or green insulated.<br />

neC ® 330.108 - Where Type <strong>MC</strong> cable is used<br />

for equipment grounding; it shall comply with<br />

250.118(10) and 250.122<br />

NOTE: Corrugated-sheath constructions of<br />

type <strong>MC</strong> cable – such as <strong>Southwire</strong>’s ARMOR-X ®<br />

and <strong>Southwire</strong>’s <strong>MC</strong>AP <strong>MC</strong> AP <strong>MC</strong> cable allow the use of the armor as the equipment ground, or may<br />

require a combination of the armor and equipment grounding conductor, depending on the<br />

cable construction or application.<br />

The equipment grounding conductor of <strong>Southwire</strong> Type <strong>MC</strong> cable can be configured either as a<br />

single conductor or as multiple equal-sized conductors whose sum is equal to or larger than the<br />

required size. In either case, the grounding capacity is sized in accordance with NEC ® requirements<br />

(NEC ® 250.122).<br />

Other available <strong>MC</strong> constructions may also provide additional equipment grounding conductors that<br />

may be used for isolated or redundant grounding.<br />

equipment grounding conductors for cables in parallel circuits—NEC ® Section 250.122 requires<br />

that parallel conductors have an equipment grounding conductor sized according to the rating or<br />

setting of the overcurrent device.<br />