CONSTRUCTION NOISE & VIBRATION Page 15 42.6590.R1:CFCD5<br />
QUALITATIVE ASSESSMENT Rev04<br />
330kV ELECTRICITY CABLE<br />
HOLROYD <strong>to</strong> ROOKWOOD ROAD January 2012<br />
Table 8: Predicted Noise Levels from Micro Tunnelling<br />
L10 dB(A) re: 20 x 10 -6 Pa<br />
Distance from<br />
Sound Pressure Level<br />
Construction<br />
dB(A)<br />
Activity<br />
(m)<br />
Site<br />
Establishment<br />
Drilling Cable Laying<br />
15 85 87 79<br />
40 76 78 70<br />
80 70 72 64<br />
100 68 70 62<br />
150 65 67 59<br />
300 59 61 53<br />
4.5.2(a) Assessment<br />
The predicted noise levels for the micro tunnelling activities exceed a noise<br />
management goal of LA90 +10dB (50-60dB(A)) for activities three (3) weeks or<br />
longer at residential properties within 150 metres of the construction activities.<br />
Depending on the final selection of the drilling rig some engineering noise<br />
controls may be feasible. Where feasible and practical, engineering noise controls<br />
and work practices will be considered <strong>to</strong> minimise noise impacts (Section 5).<br />
Directional drilling activities will be restricted <strong>to</strong> the daytime hours of 7.00am <strong>to</strong><br />
6.00pm Monday <strong>to</strong> Friday, and 7.00am <strong>to</strong> 1.00pm Saturday. It is not envisaged<br />
that micro tunnelling will be undertaken outside normal daytime hours, however<br />
if it is required, notification will be provided <strong>to</strong> residents, Council and DECCW<br />
prior <strong>to</strong> commencing the works.<br />
Where directional drilling or micro tunnelling is required, construction activities<br />
are not expected <strong>to</strong> exceed three (3) weeks at any one location, this noise impact<br />
would likely be acceptable. Albeit night time work may be required when located<br />
within close proximity <strong>to</strong> main roads or railways.<br />
PERRAM & PARTNERS ATKINS ACOUSTICS