•<br />

Material Quality Standard: ASTM B209 (ASTM B209M).<br />

Description: Alloy, temper, and thickness recommended by manufacturer for type of<br />

use and finish indicated, but not less than 0.020 in (0.5 mm), and with strength and<br />

durability properties required to fulfill performance requirements.<br />

2. Core: Extruded polyethylene or other thermoplastic material.<br />

a. Core composed of foamed insulation is not acceptable.<br />

b. Use of glue or adhesive to laminate face sheets to core is not acceptable.<br />

B. Thickness: 0.157 in.<br />

C. Surface Texture: Smooth.<br />

D. Protective Covering: Cover panels with strippable plastic film.<br />

2.3 FASTENERS AND ANCHORS<br />

A. General: Type and size required by delegated engineering and sufficient to properly fasten or anchor<br />

specified item to substrate indicated.<br />

1.<br />

2.<br />

3.<br />

a.<br />

b.<br />

2.4 ACCESSORIES<br />

Use concealed fasteners. If concealed fasteners cannot be avoided, use countersunk Phillips<br />

head fasteners with finish matching adjacent surfaces making fastener as inconspicuous as<br />

possible.<br />

Use nuts with positive means of preventing disengagement at expansion or moving<br />

connections. Stalking of bolts, use of lock washers, or deforming threads are not allowed.<br />

Use matched bolts, washers, and nuts at friction connections.<br />

A. General: Components required for a complete assembly including gaskets, fillers, closure strips, and<br />

similar items.<br />

B. Flashing and Trim: Profiles required to seal against weather and to provide finished appearance.<br />

1. Material: Formed from 0.018 in minimum thickness, zinc-coated (galvanized) steel sheet or<br />

aluminum-zinc alloy-coated steel sheet prepainted with coil coating.<br />

2. Locations: Include, but not limited to, bases, drips, sills, jambs, corners, endwalls, framed<br />

openings, rakes, fascia, parapet caps, soffits, reveals, and fillers.<br />

3. Finish: Same as adjacent panels.<br />

C. Concealed Joinery Sealant:<br />

1. Product Quality Standard: ASTM C920, Type S, Grade NS, Class 150/50.<br />

2. Description: Single component, non-sag, neutral cure, non-staining as determined by preconstruction<br />

stain testing, and non-bleeding, silicone sealant.<br />

3. Joint Movement Capability: Plus 150 percent, minus 50 percent.<br />

4. Primers: Product provided by sealant manufacturer if required by conditions.<br />

Central Fire Station, Temple, TX August 17, 2009<br />

WHJ Architect Project No. 0818 Composite Metal Panels 07424 - 5