05.04.2013 Views

Disconnector Cubicle - Microelettrica Scientifica

Disconnector Cubicle - Microelettrica Scientifica

Disconnector Cubicle - Microelettrica Scientifica

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

DC Switchgears<br />

Type DIACLAD - Metalclad<br />

Executions Withdrawable or Fixed<br />

Configurations Single or double poles<br />

Control Motorized or Manual<br />

Protections Reverse current relay “32”<br />

Earthing relay “64”<br />

PLC integrated device<br />

Communication protocol TCP/IP IEC80100 MODBUS<br />

Electrical Characteristics<br />

<strong>Disconnector</strong><br />

<strong>Cubicle</strong><br />

Description<br />

The <strong>Disconnector</strong> cubicle type DIACLAD is mounted between the Rectifier unit and the Feeder cubicles.<br />

It is suitable for indoor installation in DC traction substations systems such as Tramways, Metros and<br />

Trolleybuses and is designed and manufactured according to EN 50123 & IEC 61992 standards.<br />

The main feature of the incoming cubicle is to allow access to the rectifier for the inspection and<br />

maintenance while the DC section is in operation.<br />

The cubicle is composed of three separate compartments:<br />

• withdrawable or fixed <strong>Disconnector</strong> Switch compartment<br />

• low voltage compartment complete of control and measuring devices (e.g. reverse current relay “32”,<br />

earthing relay “64”, metering instruments, PLC and communication to SCADA...)<br />

• bus-bar compartment where are allocated the main incoming busbar, the connection for outgoing<br />

cables and the shunt for current measure.<br />

Nominal voltage Un [VDC] 750 1500 3000<br />

Rated voltage UNe [VDC] 900 1800 3600<br />

Rated insulation voltage UNm [VDC] 1800 2300 4800<br />

Rated impulse withstand voltage UNi [kV] 15 18 40<br />

Power frequency withstand voltage Ua [kV] 6,9 8,3 18,5<br />

Rated service current INe [kA] up to 9 up to 6 up to 4<br />

Rated current main busbar INe [kA] up to 12 up to 9 up to 6<br />

Rated voltage auxiliary circuit [VAC/DC] 24÷220 24÷220 24÷220


DC Switchgears <strong>Disconnector</strong> <strong>Cubicle</strong><br />

Typical Applications<br />

Mechanical Characteristics<br />

Nominal voltage Un [VDC]<br />

Protection degree<br />

750 1500 3000<br />

for the enclosure IP/3X IP/3X IP/3X<br />

for the remaining separations (shutters included)<br />

Dimensions<br />

IP/2X IP/2X IP/2X<br />

Width [mm] 800 800 800<br />

Depth [mm] 1800 1800 2000<br />

Height [mm] 2125 2125 2250<br />

Weight [kg]<br />

Ambient conditions<br />

~ 600 ~ 600 ~ 650<br />

operating temperature range - 5 ÷ 40°C - 5 ÷ 40°C - 5 ÷ 40°C<br />

storage temperature range - 20 ÷ 50°C - 20 ÷ 50°C - 20 ÷ 50°C<br />

relative humidity