<strong>Acoustic</strong> <strong>Laboratory</strong><br />

<strong>TROX</strong> <strong>HESCO</strong> <strong>Schweiz</strong> <strong>AG</strong>


2<br />

<strong>Acoustic</strong> <strong>Laboratory</strong><br />

We are happy to advice you.<br />

If you have any questions concerning your acoustical problems<br />

our staff will be pleased to provide you with detailed<br />

answers. Contact labor@troxhesco.ch<br />

Contents<br />

Possible applications 3<br />

Reverberation chamber 4–5<br />

Basic scheme of air handling unit and<br />

measuring equimpent 6–7


<strong>Acoustic</strong> <strong>Laboratory</strong><br />

Possible applications<br />

The Trox Hesco laboratory is mainly used for instrumentation<br />

testing and evaluation of complete air handling<br />

systems. The main focus of the laboratory is to measure<br />

and provide technical data within the product development<br />

process and for the product documentation.<br />

Totally 1700 m³ of laboratory premises are at the disposal<br />

for aero dynamical and acoustical measurements.<br />

On customer request it is also possible to provide acoustical<br />

test for any other product type.<br />

The acoustical laboratory is designed for general purposes<br />

but is primarily intended to be used for determination of<br />

sound power levels.<br />

Standard measurements<br />

Measuring one test configuration takes about 30 s. To<br />

get all relevant acoustical data of a test object it is often<br />

necessary to make dozens of measurements. Following<br />

objects are particularly suitable for sound power level<br />

measurements:<br />

• Grilles and diffusers<br />

• Volume flow control devices<br />

• Fire and smoke protection devices<br />

• Fan coil units and air terminal units<br />

• Ventilators<br />

• Pumps<br />

• Washing machines<br />

• White goods<br />

In connection with air handling pressure drops and air<br />

temperatures are recorded additionally.<br />

Other measurements<br />

The acoustic measurement infrastructure allows us to<br />

analyze other poblems like:<br />

• Measurement of sound power levels of diffusers<br />

according to SN EN ISO 5135<br />

• Measurement of sabine absorbtion coefficients � s<br />

according to SN EN ISO 354<br />

• Measurement of insertion loss De of attenuators<br />

on the basis of SN EN ISO 7235<br />

Quality management acc. to ISO 9001<br />

Since 1993 <strong>TROX</strong> <strong>HESCO</strong> <strong>Schweiz</strong> <strong>AG</strong> has been certified<br />

according to ISO 9001.<br />

All measurements are performed with periodically calibrated<br />

equipment. The calibration and verification is carried<br />

out either internally or at a certified calibration authority.<br />

Definitions and symbols<br />

f = frequency<br />

Lwr = sound power level of reference sound source<br />

Lpr = sound pressure level of reference sound source<br />

�Lr = Lwr-Lpr Note<br />

All details like e.g. device types, device manufacturers and references to standards are informative only. Trox Hesco <strong>AG</strong><br />

reserves the right to change or modify the equipment if necessary or if it is requested due to new standards.<br />

3


4<br />

<strong>Acoustic</strong> <strong>Laboratory</strong><br />

Reverberation chamber<br />

Possible test setup<br />

The reverberation chamber is used for the determination<br />

of the radiated acoustic power of any noise source. The<br />

room is designed to be very reverberant, so the walls are<br />

made of painted concrete. Besides the sloping ceiling<br />

and the tiled floor, the walls are non-parallel to make the<br />

room more diffuse. Additional diffusers randomly distributed<br />

in the room ensure the equal distribution of the<br />

sound energy.<br />

The whole chamber with its weight of 140 t is built on<br />

linear support elements to provide vibration isolation.<br />

Thus it is possible to reach very low background noise<br />

levels.<br />

The air handling unit is designed for flow rates up to 6000<br />

m³/h (1670 l/s) at a total pressure drop of 2000 Pa.<br />

To prevent acoustic measurements from being distorted<br />

by the noise of the supply and exhaust air handling units,<br />

the ducts are acoustically separated and fitted with highly<br />

effective attenuators.<br />

Reverberation chamber specifications<br />

• Volume: 200 m³<br />

• Surface: 209 m²<br />

• Weight: 140 tons, mounted on G+H linear support<br />

elements<br />

• Compressed air supply up to 8 bar<br />

• Water supply ND 25<br />

• Electric power supply 230 VAC / 10 A and 400 V /<br />

15 A<br />

Measuring air flow rate


<strong>Acoustic</strong> <strong>Laboratory</strong><br />

Reverberation chamber according<br />

to SN EN ISO 3741<br />

Ground plan<br />

2<br />

500<br />

100<br />

500<br />

2600<br />

Developed view<br />

6351<br />

2600 1100 2650<br />

4360<br />

2650<br />

1100<br />

6350<br />

2<br />

1100 1650<br />

6350<br />

5460<br />

7180<br />

7200<br />

4490<br />

7180<br />

7400<br />

5475<br />

5460<br />

7400<br />

260 400<br />

1<br />

850<br />

260<br />

1550<br />

3<br />

1280<br />

3<br />

1<br />

3000<br />

3600<br />

1100<br />

1580 1170 1500<br />

4900 5475<br />

1870 1100 1930<br />

2950<br />

4900 200 1580<br />

3100<br />

1100<br />

670<br />

7200<br />

1 Supply air<br />

2 Exhaust air<br />

3 Entrance<br />

Room volume V = 200 m³<br />

Surface A = 209 m²<br />

6351<br />

5


6<br />

<strong>Acoustic</strong> <strong>Laboratory</strong><br />

Basic scheme of air handling<br />

unit and measuring equipment<br />

M<br />

M<br />

5<br />

2<br />

4<br />

3<br />

A B C D<br />

Supply air unit<br />

Monoblc S-Type K6 with 4 multileaf dampers, filtration<br />

unit, heating unit (42 different levels, 40 kW) and continuously<br />

adjustable ventilator (type SD-9-071/D 35-4<br />

Fischbach).<br />

The supply air duct is fitted with splitter attenuators to<br />

ensure that the ventilator noise is lower than 20 dB(A).<br />

Furthermore the duct close to the reverberation chamber<br />

is encased with steel plates to avoid sound irradiation<br />

into the duct.<br />

The supply air inlet into the chamber is 1.1 m high by<br />

1.1 m width, which allows special measurement like e.g.<br />

attenuator measurements. For acoustic tests without air,<br />

the duct is air-tight sealed by steel plates.<br />

T<br />

5<br />

M<br />

M<br />

Exhaust air unit<br />

1<br />

M<br />

M<br />

T<br />

1a<br />

1b<br />

A Pressure -, temperature- and<br />

speed transmitters<br />

B Sending unit (noise)<br />

C Microphone positions<br />

D Regulation of air handling<br />

unit<br />

1 Supply air 1a Recirculation air 1b Outdoor air 2 Exhaust air 3 Reverberation chamber 4 AMCA-nozzels<br />

5 Attenuators<br />

The unit is subdivided into two identical parts with continuously<br />

adjustable ventilators (type SD 8-980 / D 25-4<br />

Fischbach) and automatic multileaf dampers. The exhaust<br />

air ducts are fitted with splitter attenuators to avoid perturbation<br />

of environmental noise.<br />

Other measurement equipment<br />

All measuring lines are routed through special connecting<br />

passages to the measuring unit:<br />

Air flow rate<br />

is measured with nozzles according to AMCA-standard 210-<br />

67 (range 25 … 3000 m³/h).<br />

Pressure differences<br />

are captured with Setra pressure transmitters and a<br />

Delphin data logger. Temperatures are measured with<br />

PT 100 sensors.


<strong>Acoustic</strong> <strong>Laboratory</strong><br />

<strong>Acoustic</strong>al measurement instrumentation<br />

Beside the real time analyzing system which simultaneously<br />

records the sound pressure levels of the three microphones,<br />

a reference sound source B&K type 4204, an omni<br />

directional speaker system B&K type 4241 and a microphone<br />

calibrator are at disposal.<br />

Measuring the sound power level in accordance with<br />

SN EN ISO 3741 is fully automated.<br />

The result sheets are available in different languages and<br />

contain following data:<br />

Sound power level in octave band and 1/3 octave band<br />

both linear and a-weighted, �Lr – values, background<br />

noise corrections and integration time of the measurement.<br />

Measurement equipment<br />

4<br />

3<br />

6<br />

1 Reference sound source B&K type 4204<br />

2 Omnidirectional speaker system B&K type 4241<br />

3 Condensator microphones B&K type 4179<br />

4 Microphone preamplifiers B&K type 2660<br />

5 Puls Frontend B&K type 3560C<br />

- LAN Modul B&K type 7533<br />

- In-/Output Modul B&K type 3109<br />

6 Software B&K Puls BZ 5217 / CPB Analysis 7771<br />

For measurements with air handling parts volume flow<br />

rates and pressure drops are recorded as well.<br />

On special request, an evaluation of the results in order to<br />

obtain NR or NC curves is possible.<br />

1<br />

Reverberation chamber<br />

acc. to SN EN ISO 3741<br />

5<br />

2<br />

7


Headquarters<br />

<strong>TROX</strong> <strong>HESCO</strong> <strong>Schweiz</strong> <strong>AG</strong><br />

Walderstrasse 125<br />

Postfach 455<br />

CH - 8630 Rüti ZH<br />

Telefon +41 (0)55 250 71 11<br />

Telefax +41 (0)55 250 73 10<br />

www.troxhesco.ch<br />

info@troxhesco.ch<br />

Head office Deutschland<br />

<strong>TROX</strong> GmbH Telefon +49(0)2845/202-0<br />

Heinrich-Trox-Platz Telefax+49(0)2845/202-265<br />

E-Mail trox@trox.de<br />

D-47504 Neukirchen-Vluyn www.trox.de<br />

Subsidiaries<br />

Argentinien<br />

<strong>TROX</strong> Argentina S.A.<br />

Australien<br />

<strong>TROX</strong> Australia Pty Ltd<br />

Belgien<br />

S.A. <strong>TROX</strong> Belgium N.V.<br />

Brasilien<br />

<strong>TROX</strong> do Brasil Ltda.<br />

Bulgarien<br />

<strong>TROX</strong> Austria GmbH<br />

China<br />

<strong>TROX</strong> Air Conditioning<br />

Components(Suzhou) Co., Ltd.<br />

Dänemark<br />

<strong>TROX</strong> Danmark A/S<br />

Deutschland<br />

FSL GmbH & Co. KG<strong>TROX</strong> Deutschland<br />

GmbH<br />

Frankreich<br />

<strong>TROX</strong> France Sarl<br />

Foreign representations<br />

Abu Dhabi<br />

Ägypten<br />

Bosnien-Herzegowina<br />

Chile<br />

Finnland<br />

Griechenland<br />

Indonesien<br />

Iran<br />

Irland<br />

Island<br />

Israel<br />

Jordanien<br />

Korea<br />

Lettland<br />

Libanon<br />

Litauen<br />

Marokko<br />

Neuseeland<br />

Branch office / Romandy<br />

<strong>TROX</strong> <strong>HESCO</strong> <strong>Schweiz</strong> <strong>AG</strong><br />

Route des Arsenaux 37<br />

Case postale 257<br />

CH - 1705 Fribourg<br />

Telefon +41 (0)26 425 59 00<br />

Telefax +41 (0)26 425 59 01<br />

www.troxhesco.ch<br />

info@troxhesco.ch<br />

Großbritannien<br />

<strong>TROX</strong> UK Ltd.<br />

<strong>TROX</strong> AITCS Ltd.<br />

Hongkong<br />

<strong>TROX</strong> Hong Kong Ltd.<br />

<strong>TROX</strong> AITCS Ltd.<br />

Indien<br />

<strong>TROX</strong> INDIA PRIVATE LIMITED<br />

Italien<br />

<strong>TROX</strong> Italia S.p.A.<br />

Kroatien<br />

<strong>TROX</strong> Austria GmbH<br />

Malaysia<br />

<strong>TROX</strong> Malaysia Sdn. Bhd.<br />

Norwegen<br />

<strong>TROX</strong> Auranor Norge AS<br />

Österreich<br />

<strong>TROX</strong> Austria GmbH<br />

Polen<br />

<strong>TROX</strong> Austria GmbH<br />

Rumänien<br />

<strong>TROX</strong> Austria GmbH<br />

Niederlande<br />

Oman<br />

Pakistan<br />

Philippinen<br />

Portugal<br />

Saudi Arabien<br />

Schweden<br />

Simbabwe<br />

Slowakische Republik<br />

Representation / Italian-speaking<br />

Switzerland<br />

Bärtschi SA<br />

Centro Ingegneria Impiantistic<br />

Via Baragge 13 c<br />

CH - 6512 Giubiasco<br />

Telefon +41 (0)91 857 73 27<br />

Telefax +41 (0) 91 857 63 78<br />

www.troxhesco.ch<br />

info@troxhesco.ch<br />

Russland<br />

OOO <strong>TROX</strong> RUS<br />

Schweden<br />

<strong>TROX</strong> Sverige AB<br />

<strong>Schweiz</strong><br />

<strong>TROX</strong> <strong>HESCO</strong> <strong>Schweiz</strong> <strong>AG</strong><br />

Serbien<br />

<strong>TROX</strong> Austria GmbH<br />

Spanien<br />

<strong>TROX</strong> España, S.A.<br />

Südafrika<br />

<strong>TROX</strong> South Africa (Pty) Ltd<br />

Tschechische Republik<br />

<strong>TROX</strong> Austria GmbH<br />

Ungarn<br />

<strong>TROX</strong> Austria GmbH<br />

USA<br />

<strong>TROX</strong> USA, Inc.<br />

<strong>TROX</strong> AITCS Ltd.<br />

Vereinigte Arabische Emirate<br />

<strong>TROX</strong> Middle East (LLC)<br />

Slowenien<br />

Taiwan<br />

Thailand<br />

Türkei<br />

Ukraine<br />

Uruguay<br />

Venezuela<br />

Vietnam<br />

Zypern

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!