25.04.2013 Views

Alternate Power Source System Codes - UL.com

Alternate Power Source System Codes - UL.com

Alternate Power Source System Codes - UL.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Alternate</strong> <strong>Power</strong> <strong>Source</strong><br />

<strong>System</strong> <strong>Codes</strong><br />

Emergency, standby, legally required systems and a fire pump too…<br />

The application requirements for today’s alternate<br />

power sources are still largely dependent<br />

upon engine driven generator systems.<br />

Installations can be single or multiple installed<br />

in a parallel configuration determined by load<br />

requirements and critical system needs.<br />

These are problems designers face and<br />

choices to make when developing an<br />

alternate power source system for a structure.<br />

Proper generator selection is not as simple<br />

as selecting the low bid price. In fact, it can<br />

involve the application of numerous codes<br />

and standards. As an example, Section<br />

2701 of the 2009 International Building Code<br />

(IBC) states that required emergency and<br />

standby power systems are to be installed in<br />

accordance with the NFPA 110 and NFPA 111<br />

standards. In addition, Section 2702.1.1 of<br />

the IBC requires that emergency and standby<br />

stationary generators be listed in accordance<br />

with <strong>UL</strong> 2200, the Standard for Safety of<br />

Stationary Engine Generator Assemblies. <strong>UL</strong><br />

White Book category FTSR covers Stationary<br />

Generators Listed to <strong>UL</strong> 2200. These generators<br />

are rated 600 V or less and are intended<br />

for installation and use in accordance with:<br />

• NFPA 70 “National Electrical Code”<br />

• NFPA 37 “Standard for the Installation<br />

and Use of Stationary Combustion<br />

Engines and Gas Turbines”<br />

• NFPA 99 “Standard for Health<br />

Care Facilities”<br />

• NFPA 110 “Standard for Emergency<br />

and Standby <strong>Power</strong> <strong>System</strong>s”<br />

The need for any <strong>UL</strong> 2200 Listed generator<br />

serving as an alternate power source begins<br />

with the simple decision of which systems need<br />

power when a utility <strong>com</strong>pany goes off line.<br />

This is determined using Article 220 of<br />

the 2008 National Electrical Code (NEC)<br />

and a precise load calculation to establish<br />

the actual building load the generator<br />

must supply as required by NEC Sections<br />

695.3(B)(1), 700.5, 701.6 and 702.5. Again,<br />

numerous codes and standards must be<br />

applied to an installation, based on building<br />

occupancy, use, and content loading. States<br />

and municipalities typically adopt the numerous<br />

codes and standards that must be considered<br />

for proper installation such as:<br />

• Building Code<br />

• Life Safety Code<br />

June 2010<br />

For regulatory authorities in the electrical inspection <strong>com</strong>munity.<br />

• Health Care Standard (for Medical Facilities)<br />

(continued)


Electrical Connections<br />

a supplement of The Code Authority ®<br />

<strong>Alternate</strong> <strong>Power</strong> <strong>Source</strong> <strong>System</strong> <strong>Codes</strong> (continued)<br />

• Fire Code<br />

• Sprinkler Code<br />

• Fire Pump Code<br />

• National Electrical Code<br />

What is unique about installing emergency<br />

and standby power systems is that often<br />

codes applicable to an installation, will<br />

reference and require the use of a second,<br />

third, or even a fourth code or standard.<br />

The <strong>com</strong>bination of codes and standards<br />

determines the entire set of requirements for<br />

a proper installation of a specific generator<br />

system and its unique <strong>com</strong>ponents and<br />

features. These codes and standards may<br />

have separate requirements, but they are all<br />

intended to work in harmony and impact the<br />

overall decision to make a code <strong>com</strong>pliant<br />

installation. Here is a basic example:<br />

A building under design is required by Section<br />

903 of the IBC to have a sprinkler protection<br />

system installed in accordance with NFPA<br />

13, the Standard for Sprinkler <strong>System</strong>s.<br />

The municipal water system supplying the<br />

building has inadequate pressure to make the<br />

sprinkler system design feasible. A fire pump<br />

is designed into the system as an acceptable<br />

water supply source to increase water<br />

pressure for the sprinklers. The designer<br />

specifies a fire pump that <strong>com</strong>plies with NFPA<br />

20, the Standard for Fire Pumps and required<br />

by NFPA 13 and Section 913 of the IBC. The<br />

fire pump now be<strong>com</strong>es part of the design<br />

requirement for the required sprinkler system.<br />

This <strong>UL</strong> 2200 Listed generator will<br />

supply three individual <strong>UL</strong> Listed<br />

transfer switches evaluated to<br />

<strong>UL</strong> 1008, Standard for Safety of<br />

Published by the Regulatory Services<br />

Department of Underwriters Laboratories Inc.<br />

© 2010. All rights reserved.<br />

Transfer Switch Equipment, to provide backup<br />

power to critical circuits. Additional information<br />

on transfer switches may be located in the <strong>UL</strong><br />

White Book under categories:<br />

• WPTZ — Transfer Switches<br />

• WPWR — Automatic Transfer Switches<br />

for use in Emergency <strong>System</strong>s<br />

• XNVE — Transfer Switches for use in<br />

Fire Pump Motor Circuits<br />

The fire pump disconnect must be a<br />

supervised connection as required by Section<br />

695.4 of the NEC and clearly marked in<br />

at least one inch letters — as “Fire Pump<br />

Disconnecting Means,” with overcurrent<br />

protection that can carry locked rotor current<br />

indefinitely, and located some distance away<br />

to assure adequate physical separation<br />

from the other disconnects in accordance<br />

with NEC Sections 695.4(B)(1), (2), (3), (5),<br />

695.6(C) and NFPA 20. From this supervised<br />

switch, feeder conductors are sized to 125<br />

percent of the full load current of a fire pump<br />

motor, pressure maintenance pump plus 100<br />

percent of any other associated equipment if<br />

supplied by this feeder per the requirements<br />

of NEC Section 695.6(C)(1). This application<br />

<strong>com</strong>plies with both NEC Articles 695 and<br />

700. The use of a vertical switchboard with<br />

separate sections is not permitted in a single<br />

generator installation due to the requirements<br />

of the NEC Sections 695.4(A) and (B)(2).<br />

Generator selection and sizing is only one of<br />

the many factors that designer’s face. NFPA<br />

20 and NEC Section 695.7 include<br />

requirements that the voltage at<br />

controller line terminals shall not<br />

drop more than 15 percent below<br />

normal (controller-rated voltage)<br />

under motor-starting conditions, and<br />

the voltage at the motor terminals<br />

shall not drop more than 5 percent<br />

below the voltage rating of the<br />

motor when it is operating at<br />

115 percent of the full-load<br />

current rating of the motor. This<br />

requires careful load calculation<br />

and generator sizing to<br />

ac<strong>com</strong>modate all loads that must<br />

Managing Editor: Jeffrey A. Fecteau<br />

+1.651.408.8562<br />

Jeffrey.Fecteau@us.ul.<strong>com</strong><br />

www.ul.<strong>com</strong>/tcaec<br />

<strong>UL</strong><br />

June 2010<br />

be served, and the fire pump started with no<br />

dip in voltage. If this proves problematic, load<br />

shedding on start up to eliminate voltage drop<br />

at the controller terminals be<strong>com</strong>es mandatory.<br />

Emergency and legally required standby<br />

generator systems must have a witness<br />

and load test prior to issuing a certificate<br />

of occupancy for a building as required by<br />

NEC Sections 700.4(A), (E) and 701.5(A), (E).<br />

The witness and load test are required to<br />

ensure that a generator listed to <strong>UL</strong> 2200<br />

is properly sized and installed to carry all<br />

required loads. In addition to the previously<br />

mentioned requirements, NEC Section 695.10<br />

requires fire pump equipment must be listed;<br />

additional information is located in the <strong>UL</strong><br />

White Book under categories:<br />

• QXZF — Fire Pump Motors<br />

• QYZS — Fire Pump Controllers<br />

• QVUT — Pumping Equipment for<br />

Fire Service<br />

As the example illustrates, designers often face<br />

<strong>com</strong>plex issues when designing power supply<br />

systems for fire pumps. Often what seems<br />

like a <strong>com</strong>mon sense approach may not be<br />

truly code <strong>com</strong>pliant. Careful consideration of<br />

the above-mentioned codes and standards is<br />

essential to a code <strong>com</strong>pliant design and to<br />

receive the approval of the code authorities<br />

from all the interested disciplines.<br />

For more information about <strong>UL</strong> Listed<br />

generators or <strong>UL</strong> Listed transfer switches,<br />

please contact Donnie Shields at<br />

+1.847.224.2760 or Donald.Shields@us.ul.<strong>com</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!