UNDERGROUND STORAGE TANK REMOVAL REPORT<br />

UT-<strong>44</strong><br />

1. Introduction<br />

The purpose of this Tank Removal Report is to summarize historical activities<br />

involving <strong>underground</strong> <strong>storage</strong> <strong>tank</strong> #UT-<strong>44</strong>, located near Bldg . 301 (Area I), of<br />

the Rockwell International, Rocketdyne Division, Santa Susana Field Lab .<br />

I Tank Descriplion<br />

Tank Identification - UT-<strong>44</strong><br />

Previous Tank Identification - T103<br />

Size - 4,000 gallons<br />

Structure - Steel<br />

Contents - Fuel Oil/Diesel<br />

Removal Date - August 26, 1987<br />

Abandonment Permit # - 698 (attachment A)<br />

Lead Agency - VCEH D<br />

VCEHD Inspector - Jerry Burke<br />

Photo Availabl e<br />

III. Illustrations<br />

Vicinity Map - (attachment B)<br />

Site Map - (attachment C )<br />

IV. Discussion -<br />

UT-<strong>44</strong> was removed on August 26, 1987, under permit # 698 . Following the<br />

<strong>removal</strong>, one soil sample was collected from the bottom of the excavation and<br />

analyzed by the Rocketdyne SSFL Analytical Chemistry Lab . The<br />

concentration of diesel <strong>report</strong>ed in the sample was less than the detection limit<br />

(attachment D) .<br />

Subsequent correspondences between VCEHD and Rocketdyne support clean<br />

closure of UT-<strong>44</strong>. For example, UT-<strong>44</strong> is referenced on a VCEHD UST chart for<br />

SSFL that indicates there was no contamination (see attachment J of the TRR<br />

for UT-03). Similarly, a Rocketdyne correspondence to VCEHD identifies T1.03<br />

(UT-<strong>44</strong>) as "clean" and "backfilled" (attachment E) .<br />

Conclusion/Rgg;ommendationa<br />

Based on the soil sampling results and various correspondences, no further<br />

action is--re<strong>com</strong>mended ------ ---


Attachments<br />

HDMSe00024168


ENVIRONMENTAL HtA[.I n V ~r~ . .,-.~ . _ ATTACHMENT A<br />

TO ABANDON<br />

APPLICATION FOR PERI1"<br />

i T IAI STORAGE TAN K<br />

UNDERGROUND HAZARIJOU S<br />

Joint Agency AP<br />

c Abandon Undergroernd ~fa,Tardous Materials Storage Tank<br />

rcat# rn For Permit 7'<br />

T= 000ATlO1t ,~ t . O D W02'sd CarYcn R ^ad - Burro Flats<br />

AC3 _ 7W<br />

Sa to SttSala l eld l a~<br />

Interna Ian 1<br />

'3~as+ t . Su~a~ Cinf r~W Z Codu3<br />

. Can^ Park CA. 913C Q<br />

6633 Cancoa Ave<br />

PEA;LN . A[10" ES5 tt<br />

ppgpAtb R<br />

plant<br />

m G . 3y ..-<br />

,-+ Services/ .<br />

RESS i d<strong>ut</strong>yYaw I &17NL Eh 1 end Iro Cade t<br />

ADD<br />

. CanuMa Park CA 913<br />

aAl C ~AAve<br />

0<br />

-Eft end Yi0 CO& I<br />

A<br />

73 ,,mountain View Avenue , Oxnard CA 010 3 :,<br />

w a i l fYiEN S COMPENSA 5QN4651 WO ANY 3 3 ^ O !Z<br />

Sentry - 674 Country Rd .Suite 1C~


L ENVIRONMENTAL HEALTH DEPARTMEN T<br />

APPLICATION FOR PERMIT TO ABANDON ATTACHMENT A<br />

UNDERGROUND HAZARDOUS MATERIAL STORAGE TAN K<br />

Joint Agency Application For Permit To Abandon Underground Hazardous Materials Storage Tank<br />

TAii% LOCAlioN<br />

Santa Susana F i eld Lati_ t D Woolsey Canyon Road - Burxo Mats<br />

CUM1A, +toKe<br />

O"ER<br />

Plockwell Internation I.<br />

MAILING ADOHESS ITtu+nher. StrM4 City and Tip Code9<br />

6633 Canoca Ave . . Canoca Park, CA 91304<br />

txONTACrrmtoN E<br />

i)PERATgR<br />

r (S1E€ 714-542 8<br />

Plant Services/ M . G . Chi, : , _z<br />

AEAik ,DtG ADDRESS dumb.'. Suait . City and Tip Codas<br />

6 3 Cafoca Ave . Cancca Park CI: 91304<br />

REMOVAL CONTRACtOR<br />

g„t n<br />

A u . Surat. Litt' and Zip Cpde i<br />

730 Mountain View Avenue, Oxna rd CA 930375<br />

WpRXMEN'S COMtpENSATtON INSURANCE COMPAN Y<br />

Sentry - 574 Country Pd .Suite 1018", Ventura, CA 93003<br />

x<br />

AREA. 1<br />

TANK<br />

NO .<br />

1<br />

/' 3<br />

/4<br />

5<br />

ATTACH A PLOT PLAN SHOWING :<br />

Location of all <strong>tank</strong>s, piping and secondary<br />

containment<br />

Leak detection system<br />

overfill protection syste m<br />

Scale<br />

North arrow<br />

SIGNATURES OF APPLICANT OR REPRE SENTATIVE<br />

PREVIOUS OWNER AND OPERATORS TANK(S )<br />

cpNtACtr~rtoN E<br />

S0 /64 -'5,r; 9<br />

PHONE<br />

805/654-177 7<br />

FOR OFFICE USE ONLY APPLICATION : Q Approved ❑ Abandon in Place El-lemoval<br />

t<br />

❑<br />

❑<br />

❑<br />

Fee See Conditions for Approval on Back of Form<br />

Check No .<br />

- - --- ~,<br />

Receipt NO . ; J L_ C7eriiet3 I:ea5ott for [3etrial :<br />

. . . . . . .<br />

File No . kt e; _ i.<br />

❑ Date "' By ~~fn a<br />

DATE<br />

RMA-7364 t2>P6 l<br />

DATE<br />

~rti' ^<br />

OWNERIOPERATO R<br />

COMPLETE THE FOLLOWING FOR EACH TANK TO BE ABANDONE D<br />

SIZE CONSTRUCTION (Steel , Fiberglass, Etc . )<br />

r _i14 L U_i<br />

ry() . a a 2<br />

SS E<br />

5 te2l<br />

C :4nrnlA C<br />

Estimated Start Date mid-1111Y 10E,<br />

#10' 1<br />

:10 ^<br />

`1v 3<br />

#107<br />

CONTENTS<br />

PRESENT AND PREVIOUSLY<br />

fuel O 1<br />

fuel Cl i<br />

fuel O i l<br />

TCE wa ste<br />

OiSTRIBUTtON: White- EH Cenary_CnntraetOt Pink-Applicant Goldenrod -Fire Dept .<br />

DATE<br />

2t~c)<br />

~2 14<br />

[11 Property lines<br />

I] Nearest intersection or road<br />

❑ Equipment summary<br />

© Existing equipment and equipment to be<br />

removed<br />

HDMSe00024170


4<br />

0 403<br />

APPROXIMATE LOCATION<br />

OP FORMER UST# UT-47<br />

71 3<br />

APPROXIMATE LOCATION<br />

OF FORMER UST# UT--<strong>44</strong><br />

0<br />

APPROXIMATE LOCATION,<br />

OF FORMER UST# UT-45<br />

! l/<br />

APPROXIMATE LOCATION<br />

OF FORMER UST# UT.43<br />

38 6<br />

0<br />

91<br />

3 0<br />

322 3<br />

30 2<br />

5 266<br />

0<br />

0<br />

i<br />

30 5<br />

X98 4<br />

408<br />

h-l<br />

SSFL AREA I<br />

UNDERGROUND FUEL OIL TANK<br />

WE L


isE89it6<br />

AEA II<br />

FIE LABORA RY<br />

.828 827 8 4<br />

!<br />

eu._o<br />

Big,<br />

~ ._. i . .~ . 980<br />

43 9<br />

4 1<br />

924<br />

z2s4✓~..<br />

K<br />

TI2 ,,<br />

38<br />

799 (X[174<br />

347<br />

Q:3<br />

.31 " ~~99~~ 9170/<br />

LEGEND<br />

BUILDINGS (l oo,200 , 300 a400 SERIES)<br />

STRUCTURES<br />

WATER TANKS (8o0 SERIES)<br />

AREAS i500 SERIES )<br />

(700 a 900 SERIES)<br />

0 ACTIVE WELLS OR WATER TANK S<br />

0 INACTIVE WELLS<br />

A I l Al.;rlMCt'r 1 4<br />

II/!2164 II%8<br />

I<br />

0<br />

SCALE IN FEET<br />

400 Soo 1200 0<br />

DSK 1439 6<br />

05 5 . F -C . S S FL .MAP-MASTE R<br />

L<br />

HDMSe00024172


TO : Ron Jensen & J . Matsushita<br />

FROM : SSFL ANALYTICAL CHEMISTRY<br />

CHEMICAL ANALYSIS<br />

REPORT<br />

REFERENCE : LOGBOOK : 87 PAGE - 14 0<br />

NOTEBOOK : 588 PAGE - 27<br />

Lori No . Sampl e<br />

Identification<br />

LOC NUMBER :<br />

87 08 .27 0<br />

ATTACHM T<br />

DEPT/GROUP : 831/5812<br />

PHONE : 5<strong>44</strong> :7<br />

DATE : September 2 . 198 7<br />

Result s<br />

8708 .270 Soil sample fo r<br />

diesel fuel<br />

Diesel Fuel i n<br />

analysis . Soil as received = TR t 5 pp m<br />

I .D . 826S7PB301 by weigh t<br />

Soil from botto m<br />

of pit at Building<br />

301 . Moisture in Soil = 6 by weigh t<br />

Sampled b :<br />

R . Blanchar d<br />

on 8--26-196 7<br />

1525hrs .<br />

Sample received :<br />

on 8-26-108 7<br />

[la 1530hrs .<br />

Comments : The date, are for internal use ran y .<br />

APPROVED :<br />

Manager<br />

HDMSe00024173


Racketdyne Division<br />

Rockwell international Corporation<br />

6633 Canoga Avenue<br />

Canoga Park. California 9130 3<br />

Telex : 698478<br />

ROCKETOYN CNPK<br />

Rockwell<br />

CERTIFIED - RETURN RECEIPT REQUESTE D<br />

29 November 1989 In reply refer to 89RC1453 8<br />

Resource Management Agency .<br />

County of Ventura<br />

Environmental Health Department<br />

800 So<strong>ut</strong>h Victoria Avenue<br />

Ventura, CA 9300 9<br />

Attention : Mr . Kevin Tinsle y<br />

Subject : Santa Susana Field Laboratory Underground Tank Status<br />

Gentlemen :<br />

Pursuant to your request in your letter dated 1 November 1989, Rockwell<br />

international Corporation, Rocketdyne Division (Rocketdyne) submits the<br />

following o<strong>ut</strong>line of additional information on Santa Susana Fiel d<br />

Laboratory <strong>underground</strong> <strong>tank</strong>s :<br />

1<br />

. A total of five'<strong>underground</strong> <strong>tank</strong>s have been removed from Building<br />

055 . On 21 February 1986 a 1,000 gallon diesel fuel <strong>tank</strong> was<br />

removed under a Ventura County Environmental Health Department<br />

(VCEHO) permit . Upon <strong>removal</strong> it was observed that there were hole s<br />

in the <strong>tank</strong> and an uncontrolled release had'occurred . Initial<br />

samples indicated contamination of 1 .1 to 1 .3 percent diesel fuel by<br />

weight . After remedial-work was performed samples collected<br />

indicated results ranging from 0 .001 to 0 .006 percent diesel fuel by<br />

weight . Approximately 45 yards of contaminated soil was transported<br />

to Casmalia for landfill on 21 May 1986 .<br />

The additional four <strong>underground</strong> <strong>tank</strong>s were radioactive waste holdup<br />

<strong>tank</strong>s of 1 :85, 230 and two 1,000 gallons in size . These <strong>tank</strong>s were<br />

removed with the de<strong>com</strong>missioning of the interim status Nuclear<br />

Material Development Facility (NMDF) . With the concurrence of the<br />

U .S . Nuclear Regulatory Commission the license for the facility was<br />

terminated and the area released for unrestricted use . No<br />

additional <strong>tank</strong>s have been found to exist at Building 055 . (See<br />

Enclosure 1 )<br />

2 . On 2 October 1986 a 500 gallon diesel fuel <strong>tank</strong> was removed under<br />

VCEHD permit #424 at Building 020 . Initial samples indicated<br />

contamination of 0 .3 percent diesel fuel by weight . Remedial work<br />

. . . . . . . . . . . . . . .was. . .performed .. . . . .A . .c.1 .ean_closure . .was. ..determined . . . . . . . The . . . . . . . . . County . . . . . was<br />

present during the <strong>tank</strong> abandonment . On 20 and 29 October 1986, .4 . . .<br />

cubic yards of'soil contaminated with diesel fuel was transported to<br />

Casmalia for landfill . (See Enclosure 2)<br />

ATTACHMENT E<br />

HDMSe00024174


89RC1453 8<br />

29 November 198 9<br />

Page 2<br />

3 . The following is an o<strong>ut</strong>line for the abandoiument of 14 <strong>tank</strong>s unde r<br />

VCEHO permit #698/#986 :<br />

Tank Bldg Date Removed Photos Analysis Results Statu s<br />

201 204 7 Nov 88 yes yes Contaminated Ongoing 4<br />

202 204 1 Jul 88 yes no3 Clean Backfil l<br />

203 204 29 Sep 88 yes yes Contaminated Ongoing "<br />

204 207 1 Jul 88 yes no3 Clean Backfil l<br />

205 207 no<br />

X101 300 26 Aug 87 yes yes Clean Backfil l<br />

102L1 324 26 Aug 87 yes yes Contaminated Backfill s<br />

103 301 26 Aug B, 7 yes yes Clean Backfil l<br />

-104 301 31 Aug 87 yes yes Clean Backfil l<br />

207 206 31 Aug 87 yes no3 Clean Backfi l l-.<br />

401 009 31 Aug 87 yes yes Contaminated Remediated /<br />

Backf i l l '<br />

403 005" 31 Aug 87 yes yes Contaminated Backfi11 6<br />

301 CTL-III 31 Aug 87 yes no' Clean Backf il l<br />

302 CTL- III<br />

2<br />

n o<br />

FOOTNOTES -<br />

Tank 204 at B/207 was found to be a septic <strong>tank</strong> and not removed as<br />

an <strong>underground</strong> fuel <strong>tank</strong> .<br />

2 Permit #698 was filed in respect to facility design maps,<br />

therefore due to incorrect drawings the total <strong>tank</strong> count at the<br />

CTL-III facility was misrepresented and only one <strong>tank</strong> was removed .<br />

a Analysis for <strong>tank</strong>s 202, 204, 207, and 301 were not required per<br />

Ventura County Environmental Health Department inspector at the<br />

time of <strong>removal</strong>. -<br />

4 The remedial work for <strong>tank</strong>s 201 and 203 is currently in progres s<br />

_ . . . . . .. . . . . .in- accordance with" the- Ventura- County -LUFT .program. . . . . Any.questi .ons. . . . . . . . ..<br />

regarding the work performed should be referred to files C8817 1<br />

and C88115 .<br />