– VT primary and secondary ratings<br />

– System frequency<br />

– System phase sequence<br />

CHAPTER 1: <strong>GE</strong>TTING STARTED<br />

• Define the protection elements that will be enabled. Prepare a list of protection<br />

functions including the following information. By default, all the protection functions<br />

must be assumed “Disabled”:<br />

– Pickup parameter<br />

– Operating curve, if applicable<br />

– Time dial or multiplier<br />

– Any additional intentional time delay<br />

– Directionality, if applicable<br />

• Define how many output contacts will be energized in response to a given protection<br />

function. Note that the 469 relay can be programmed to Trip or Alarm and, at the<br />

same time, to energize one, a combination, or all the 2 auxiliary relays during the<br />

process.<br />

• Define if the output relays will be set as failsafe type.<br />

• Define if the 469 relay will be used to start the motor. If so, gather information on the<br />

required conditions to execute the command.<br />

• Define if the 469 will be involved in the motor starting process, particularly on reduced<br />

voltage start applications.<br />

• Define if the 469 will be applied a multi speed applications.<br />

• Define if the relay will be used to monitor the status of the starter or breaker. It is<br />

strongly recommended that the 469 be always programmed to monitor the status of<br />

the disconnecting device, by means of a dry contact connected to one of the digital<br />

inputs of the relay. Use an auxiliary contact from the breaker or starter either a<br />

normally open contact, 52a, which is normally in open position when the<br />

disconnecting device is open, or a normally closed contact, 52b, which is in close<br />

position when the breaker or starter is open.<br />

• If the 469 will be used to respond to digital inputs, record the following information:<br />

– <strong>Digital</strong> Input name<br />

– Condition by which the digital input would be considered asserted<br />

– Function that the digital input will initiate within the 469<br />

• If the 469 will be used to perform monitoring functions and act upon certain<br />

conditions, record information such as:<br />

– minimum and maximum values<br />

– alarm and trip values<br />

– time delays<br />

• It is important to familiarize yourself with the relay protection and control functions<br />

before setting up the relay.<br />

1–18 469 MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL