CHAPTER 1: <strong>GE</strong>TTING STARTED<br />

Once the signal is received the motor will be started across the line. Therefore, the<br />

following settings are left with their default values. In the S2 SYSTEM SETUP REDUCE<br />

VOLTA<strong>GE</strong> STARTING settings page:<br />

REDUCE VOLTA<strong>GE</strong> STARTING: “Off”<br />

ASSIGN CONTROL RELAYS: “Auxiliary3” (available for other use)<br />

TRANSITION ON: “Current Only”<br />

ASSIGN TRIP RELAYS: “Trip”<br />

REDUCE VOLTA<strong>GE</strong> START LEVEL: “100% FLA”<br />

REDUCE VOLTA<strong>GE</strong> START TIMER: “200 s”<br />

1.4.5 S3 <strong>Digital</strong> Inputs Settings<br />

The S3 settings page is for entering the characteristics of the digital inputs. In our example,<br />

these characteristics are specified under the Control System Requirements heading.<br />

Program the S3 settings as indicated.<br />

Some of the functions assigned to the digital inputs of the 469 Motor Management Relay<br />

are pre-defined functions, which can be selected from a list. There are four user-defined<br />

functions, called General Switch A to D, associated to the assignable inputs. Set these<br />

inputs to operate output relays, with or without delay, responding to the status change of<br />

dry contacts connected to the digital input terminals. Use the following procedure to set<br />

these functions:<br />

Change the default names to meaningful values so they can be<br />

easily identified, either via the LCD or when reviewing event reports.<br />

Identify their asserted logic.<br />

Define the functionality of the digital inputs.<br />

All the other assignable input functions are pre-defined, and when selected, they can be<br />

set to generate Trip or Alarms, as well as energize auxiliary outputs as needed.<br />

For breaker position monitoring, set the following pre-defined <strong>Digital</strong> Input called “Starter<br />

Status”. As per the information provided above, a 52b contact will be used, and must be<br />

connected between terminals D16 to D23:<br />

S3 DIGITAL INPUTS STARTER STATUS STARTER STATUS SW: “Starter Auxiliary b”<br />

To set the relay to monitor access to the station, use Assignable Input 1 as “General Switch<br />

A”, as follows. To define the digital input, enter the following data in the S3 DIGITAL INPUTS<br />

ASSIGNABLE INPUT 1 settings page.<br />

To identify the digital input:<br />

INPUT 1 FUNCTION: “General Sw. A”<br />

SWITCH NAME: “Stn. Monitor”<br />

To define the asserted logic:<br />

<strong>GE</strong>NERAL SWITCH A: “Normally Open”<br />

To define the functionality:<br />

BLOCK INPUT FROM START: “0 s”<br />

<strong>GE</strong>NERAL SWITCH A ALARM: “Latched”<br />

ASSIGN ALARM RELAYS: “Alarm”<br />

1–32 469 MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL