ENERCON<br />
Proposal for IEC 61400-25<br />
LN Wind Power Plant Control and Monitoring System<br />
Werner Bohlen Frank Fischer<br />
• Control of Wind Power Plants<br />
• Introduction of LN WCMS<br />
• Modification of LN WTUR<br />
Energy for the World<br />
AG-Präsentation
ENERCON<br />
Control of Wind Power Plants<br />
Energy for the World<br />
AG-Präsentation
ENERCON<br />
Control of Wind Power Plants<br />
• WPP Active Power Management (installed rated power of the WTGS of a<br />
WPP extends grid capacity)<br />
• WPP Active Power Management (control of active power initiated by the<br />
utility due to grid status, e.g. e.on Erzeugungsmanagement)<br />
• WPP Reactive Power Management (control of reactive power initiated by<br />
the utility due to grid status, e.g. e.on exten<strong>de</strong>d grid connection rules)<br />
• WPP Reactive Power Management (voltage control)<br />
• WPP Controlling Power Range Management<br />
Energy for the World<br />
AG-Präsentation
WCMS Feature:<br />
ENERCON<br />
Control of Wind Power Plants<br />
• Controller using setpoint values (<strong>from</strong> utility) and actual values (<strong>from</strong><br />
measurement unit).<br />
Energy for the World<br />
AG-Präsentation
WCMS Feature:<br />
ENERCON<br />
Control of Wind Power Plants<br />
• Process Data Interface (to the utility) collecting data <strong>from</strong> the WTGs of the<br />
WPP (resp. <strong>from</strong> subordinate WPPs) to generate values for available active<br />
and reactive power of the WPP for controlling power range management.<br />
Energy for the World<br />
AG-Präsentation
WCMS Feature:<br />
ENERCON<br />
Control of Wind Power Plants<br />
• Process Data Interface (to the utility) for active power gradients.<br />
Energy for the World<br />
AG-Präsentation
Measured Values / Processed Values<br />
Available active power of WPP at PCC<br />
ENERCON<br />
Introduction of LN WCMS<br />
Available reactive power generating of WPP at PCC<br />
Available reactive power absorbing of WPP at PCC<br />
Available power factor generating of WPP at PCC<br />
Available power factor absorbing of WPP at PCC<br />
Controls<br />
Start command to the WPP<br />
Stop command to the WPP<br />
Settings<br />
Demand value of active power generation of WPP at PCC<br />
Demand value of reactive power generation of WPP at PCC<br />
Demand value of power factor at PCC<br />
Maximum allowable active power gradient after start of WPP<br />
Minimum allowable active power gradient after change of <strong>de</strong>mand value of active power generation of<br />
WPP<br />
Energy for the World<br />
AG-Präsentation
ENERCON<br />
Modification of LN WTUR<br />
• Generating values for available active and reactive power of the WTGS<br />
(controlling power range management of the WPP).<br />
• Two data sets containing setpoint data for P, Q, cos j<br />
(1) Default values for WTGS operation when the communication is<br />
interrupted resp. the WTGS is part of the WPP, but not subjected to WPP<br />
control<br />
(2) Demand values for WTGS operation when the WTGS is subjected to<br />
WPP control<br />
Energy for the World<br />
AG-Präsentation
ENERCON<br />
Modification of LN WTUR<br />
Measured Values / Processed Values<br />
TotPwrAt<br />
TotPwrRt<br />
Available active power of WTGS* NEW<br />
Available reactive power generating of WTGS* NEW<br />
Available reactive power absorbing of WTGS* NEW<br />
Available power factor generating of WTGS* NEW<br />
Available power factor absorbing of WTGS* NEW<br />
* computed value <strong>de</strong>pending on wind conditions etc.<br />
Energy for the World<br />
AG-Präsentation
Controls<br />
...<br />
WCMS activated NEW<br />
Settings<br />
ENERCON<br />
Modification of LN WTUR<br />
DmdPwrAt Demand value of active power generation of WTGS – Default value<br />
DmdPwrRt Demand value of reactive power generation of WTGS – Default value<br />
DmdPF Demand value of power factor of WTGS – Default value<br />
MaxGdPwrAt Maximum allowable active power gradient after start of WTGS – Default value<br />
Minimum allowable active power gradient after change of maximum value of active power generation of<br />
WTGS – Default value NEW<br />
Demand value of active power generation of WTGS – WCMS value NEW<br />
Demand value of reactive power generation of WTGS – WCMS value NEW<br />
Demand value of power factor of WTGS – WCMS value NEW<br />
Maximum allowable active power gradient after start of WTGS – WCMS value NEW<br />
Minimum allowable active power gradient after change of maximum value of active power generation of<br />
WTGS – WCMS value NEW<br />
Energy for the World<br />
AG-Präsentation