<strong>TTC</strong> Best Performance By Reducing Infiltrated Air<br />
Design of side sealing off walls and fall ducts<br />
18<br />
1 2 2 Correct 1<br />
Installation<br />
600…800 mm<br />
18.1<br />
The cooling unit has been correctly installed,<br />
no reduction in performance.<br />
(1) Side sealing off walls<br />
(2) Fall duct walls correctly arranged<br />
Infiltrated Air Infiltrated Air<br />
1 2 2<br />
1<br />
600…800 mm<br />
Incorrect<br />
Installation<br />
Correct<br />
Installation<br />
100<br />
(150)*<br />
18.7<br />
The calculated performance will be<br />
achieved with this installation.<br />
Air infiltration will not be possible.<br />
1<br />
Infiltrated Air<br />
600…800 mm<br />
2 2 Incorrect<br />
Installation<br />
1<br />
18.2<br />
The <strong>Cooling</strong> unit is too big. The calculated<br />
performance will not be achieved.<br />
(1) Side sealing off walls<br />
(2) Fall duct walls<br />
Air<br />
Air<br />
Turbulence<br />
turbulence<br />
1 2 2<br />
1<br />
600…800 mm<br />
Incorrect<br />
Installation<br />
18.4 18.5 18.6<br />
The cooling unit is too small. The calculated<br />
performance will not be achieved.<br />
(1) Side sealing off walls<br />
(2) Fall duct walls<br />
Installation in front of ducts<br />
Issued 02/2005. We reserve the right to make technical changes.<br />
The cooling unit is too small. The calculated<br />
performance will not be achieved.<br />
(1) Side sealing off walls<br />
(2) Fall duct walls<br />
Incorrect<br />
Installation<br />
100<br />
(150)*<br />
18.8<br />
The calculated performance will not be<br />
achieved with this installation (air<br />
turbulences).<br />
Infiltrated Air Infiltrated Air<br />
1 2 2 Incorrect 1<br />
600…800 mm Installation<br />
18.3<br />
The cooling unit is too big. The calculated<br />
performance will not be achieved.<br />
(1) Side sealing off walls<br />
(2) Fall duct walls<br />
1 Unstable air flow Incorrect 1<br />
due to lack of fall Installation<br />
duct walls<br />
Fall ducts have not been installed. The<br />
calculated performance will not be<br />
achieved with this installation.<br />
(1) Side sealing off walls<br />
Incorrect<br />
Installation<br />
100<br />
(150)*<br />
18.9<br />
The calculated performance will not be<br />
achieved with this installation (problems<br />
with infiltrated air).