F. Manufacturer shall guarantee the integrity of the filter pack to 2.0” w.g.<br />
G. Performance Guarantee: Manufacturer shall provide a written performance guarantee to the<br />
owner at the time of bid and during submittal phase. <strong>Filter</strong>s not including a written performance<br />
guarantee equal to that of the Camfill-Farr 30/30 are unacceptable unless the bidder includes an<br />
allowance to the owner at time of bid to cover any additional future costs associated with the<br />
failure of the proposed product to meet these specifications. AT NO TIME WILL THE OWNER<br />
ACCEPT ADDITIONAL POST-BID COSTS FOR PRODUCTS UNABLE TO MEET THIS<br />
SPECIFICATION<br />
H. <strong>Air</strong> filters shall be medium efficiency ASHRAE pleated panels consisting of cotton and<br />
synthetic media, welded wire media support grid, and beverage board enclosing frame.<br />
I. Select filter media that is UL listed, Class I or Class II.<br />
J. Manufacturer's published performance characteristics shall be supported by approved<br />
independent laboratory test reports.<br />
K. When dust holding capacity is not published in the manufacturer's literature the submittal data<br />
shall include recent certified documentation of performance by an approved independent test<br />
laboratory.<br />
<strong>Filter</strong> Construction<br />
L. <strong>Filter</strong> media shall be a cotton and synthetic blend, lofted to a uniform depth of 0.15”, and formed<br />
into a uniform radial pleat. Polyester Media will not be accepted.<br />
M. A welded wire grid, spot-welded on one-inch centers and treated for corrosion resistance shall be<br />
bonded to the downstream side of the media to maintain radial pleats and prevent media<br />
oscillation.<br />
N. An enclosing frame of no less than 28-point high wet-strength beverage board shall provide a rigid<br />
and durable enclosure. The frame shall be bonded to the media on all sides to prevent air bypass.<br />
Integral diagonal support members on the air entering and air exiting side shall be bonded to the<br />
apex of each pleat to maintain uniform pleat spacing in varying airflows.<br />
O. <strong>Filter</strong>s shall be at least 12 pleats per liner foot for 1” deep filters, 15 pleats per linear foot for 2”<br />
deep filters, and 11 pleats per linear foot for the 4” deep filters.<br />
Performance<br />
P. The filter shall have a Minimum Efficiency Reporting Value of MERV 8 when evaluated under the<br />
guidelines of ASHRAE Standard 52.2-2007. It shall also have a MERV-A of 8 when tested per<br />
Appendix J of the same standard. The media shall maintain or increase in efficiency over the life<br />
of the filter.<br />
Q. Initial resistance to airflow shall not exceed 0.23”, 0.31” or 0.27” w.g. at an airflow of 350,<br />
500 or 492 fpm on 1”, 2” or 4” deep models respectively.<br />
R. The filter shall have an Energy Cost Index (ECI) value of five stars for High Capacity filters, and<br />
three stars for the Standard Capacity.<br />
S. The filter shall be listed by Underwriters Laboratories as UL Class 900.<br />
T. Manufacturer shall provide evidence of facility certification to ISO 9001:2008.<br />
U. Manufacturer shall guarantee the integrity of the filter pack to 2.0” w.g.<br />
V. Performance Guarantee: Manufacturer shall provide a written performance guarantee to the<br />
owner at the time of bid and during submittal phase. <strong>Filter</strong>s not including a written performance<br />
guarantee equal to that of the Camfil-Farr 30/30 are unacceptable unless the bidder includes an<br />
allowance to the owner at time of bid to cover any additional future costs associated with the<br />
failure of the proposed product to meet these specifications. AT NO TIME WILL THE OWNER<br />
ACCEPT ADDITIONAL POST-BID COSTS FOR PRODUCTS UNABLE TO MEET THIS<br />
SPECIFICATION.<br />