24.07.2013 Views

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>UC</strong> STRATEGIC ENERGY PLAN<br />

University of California, <strong>Los</strong> <strong>Angeles</strong><br />

Prepared for<br />

University of California<br />

Office of the President<br />

December 31, 2008<br />

Prepared by:<br />

Newcomb Anderson McCormick, Inc.<br />

201 Mission Street, Suite 2010<br />

San Francisco, CA 94105<br />

Phone: (415) 896-0300<br />

Fax: (415) 896-1900<br />

2413.01


TABLE OF CONTENTS<br />

1. EXECUTIVE SUMMARY ............................................................................................. 1-1<br />

1.1 Policy on Sustainable Practices ...................................................................... 1-1<br />

1.2 <strong>Energy</strong> Use and Greenhouse Gas Reduction Targets .................................... 1-1<br />

1.3 <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects ........................................................................ 1-2<br />

2. INTROD<strong>UC</strong>TION ......................................................................................................... 2-1<br />

2.1 <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Methodology ................................................................ 2-1<br />

2.2 General Project Identification Categories and Approach ................................. 2-4<br />

2.3 <strong>Campus</strong> Overview ........................................................................................... 2-6<br />

2.4 Central <strong>Plan</strong>t .................................................................................................... 2-6<br />

2.5 <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Buildings ...................................................................... 2-6<br />

2.6 Recent <strong>Energy</strong> Project Inventory ..................................................................... 2-9<br />

3. HISTORICAL CAMPUS ENERGY USE ...................................................................... 3-1<br />

3.1 FY 99-00 and 06-07 <strong>Energy</strong> Baseline ............................................................. 3-1<br />

4. HISTORIC BUILDING ENERGY USE ......................................................................... 4-1<br />

4.1 Existing Metering Infrastructure ....................................................................... 4-1<br />

4.2 Individual Building Metering ............................................................................. 4-2<br />

4.3 Building <strong>Energy</strong> Use Targets ........................................................................... 4-3<br />

5. UTILITIES ................................................................................................................... 5-1<br />

5.1 Providers & Tariffs ........................................................................................... 5-1<br />

5.2 Procurement Options ....................................................................................... 5-1<br />

6. CAMPUS ELECTRIC INFRASTR<strong>UC</strong>TURE ................................................................ 6-1<br />

7. RENEWABLE ENERGY GENERATION ..................................................................... 7-1<br />

7.1 Technologies ................................................................................................... 7-1<br />

7.2 Existing Renewable Sources ........................................................................... 7-1<br />

8. RECOMMENDED ENERGY EFFICIENCY PROJECT DESCRIPTIONS ................... 8-1<br />

8.1 Lighting Projects .............................................................................................. 8-1<br />

8.2 HVAC Projects ................................................................................................. 8-5<br />

8.3 Monitoring Based Commissioning Projects ................................................... 8-12<br />

8.4 Capital Program Projects ............................................................................... 8-13<br />

8.5 Deferred Maintenance and Capital Renewal Projects ................................... 8-14<br />

8.6 <strong>Campus</strong> Wide Projects .................................................................................. 8-15<br />

8.7 Other Projects ................................................................................................ 8-17<br />

8.8 Custom Projects ............................................................................................ 8-18<br />

9. BUILDING OVERVIEW & PROJECTS ....................................................................... 9-1<br />

10. PROJECT SUMMARIES ........................................................................................... 10-1<br />

11. PROJECT LISTS & SUMMARY OF PROJECTS ...................................................... 11-1<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc i December 31, 2008<br />

Newcomb | Anderson | McCormick


TABLE OF CONTENTS (CONTINUED)<br />

12. ENERGY & GHG FORECAST .................................................................................. 12-1<br />

12.1 Electricity Emissions Factors ......................................................................... 12-1<br />

12.2 Gas Emissions Factors .................................................................................. 12-1<br />

12.3 Current <strong>Energy</strong> Usage and Emissions .......................................................... 12-1<br />

12.4 2014 Goals .................................................................................................... 12-1<br />

12.5 2020 Goals .................................................................................................... 12-2<br />

12.6 SEP <strong>Energy</strong> Efficiency and Renewable <strong>Energy</strong> Projects .............................. 12-2<br />

13. CONCLUSIONS ........................................................................................................ 13-1<br />

13.1 Next Steps and Recommendations ............................................................... 13-1<br />

13.2 Funding Sources ........................................................................................... 13-1<br />

APPENDICES<br />

Appendix A – Field Data Forms<br />

Appendix B – Savings Calculations<br />

Appendix C – Other Calculations and Data<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc ii December 31, 2008<br />

Newcomb | Anderson | McCormick


PREFACE<br />

This report was produced by Newcomb Anderson McCormick for the University of California,<br />

Office of the President (<strong>UC</strong>OP) and the University of California, <strong>Los</strong> <strong>Angeles</strong>. This report<br />

also includes recommendations for the medical facilities that are part of <strong>UC</strong>LA, which are<br />

technically part of the campus and therefore not referred to as a separate medical center.<br />

Valuable assistance and direction was provided for this project by George Getgen, Dirk<br />

VanUlden, Clifton Bowen, Matthew St. Clair and John Rolle of the <strong>UC</strong> Office of the<br />

President, and Dave Johnson, Robert Striff, Nick Stone, Marvin Peterson and Dan Batliwalla<br />

of <strong>UC</strong>LA.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc iii December 31, 2008<br />

Newcomb | Anderson | McCormick


1. EXECUTIVE SUMMARY<br />

1.1 Policy on Sustainable Practices<br />

The Regents of the University of California adopted a Policy on Sustainable Practices in<br />

March 2007 which states that the University will develop a <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> (SEP) for<br />

implementing energy efficiency projects in existing buildings. The initial goal for the retrofit<br />

projects is to reduce systemwide, growth adjusted energy consumption by 10% or more by<br />

2014 from the year 2000 base consumption level.<br />

In addition, the Policy directs the campuses to pursue the goal of reducing greenhouse gas<br />

(GHG) emissions to year 2000 levels by 2014 and to 1990 levels by 2020. This target is not<br />

growth adjusted. The 2020 target follows the AB32 directive on GHG emissions. Because<br />

electricity and gas purchases are expected to represent perhaps three quarters of a<br />

campus’ GHG emissions, the energy and GHG reduction goals are closely linked. It is<br />

anticipated that the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> projects will be one of the main tools the campus<br />

uses to meet its GHG targets.<br />

1.2 <strong>Energy</strong> and Greenhouse Gas Reduction Targets<br />

Table 1.1 lists past, current and projected energy purchases by <strong>UC</strong> <strong>Los</strong> <strong>Angeles</strong>, including<br />

medical facilities that are part of the campus, starting with the baseline year 2000. The<br />

energy purchases are divided by the gross building area of the campus to establish an<br />

<strong>Energy</strong> Use Index (EUI) to evaluate the growth adjusted energy use targets. Because the<br />

campus cogenerates a large portion of the electricity consumed on campus, the EUI for<br />

purchased utilities will differ from similar campuses which do not cogenerate, or from a EUI<br />

based on consumption. This cogeneration impact is a higher gas and lower electric EUI<br />

than might be otherwise anticipated.<br />

The energy purchases are also converted to GHG emissions, using emissions factors for<br />

electricity generation and natural gas use. Individual campuses are preparing plans for<br />

meeting the GHG goals, due by December 2008. Those plans will address the historical<br />

campus emissions in detail. At present the emissions factors for the different electricity<br />

providers operating in 2000 and 1990 are not available. For this <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> the<br />

GHG emissions factors are based on the statewide emissions factors for 2000. The 1990<br />

utility purchases are not currently available from university or utility records so the 2020<br />

target is undefined.<br />

The <strong>UC</strong>LA and <strong>UC</strong>LA MC energy purchases in the most recent year (FY 06-07) are also<br />

shown in Table 1.1. The cost of this energy in this year is $14,028,371 for electricity and<br />

$22,654,091 for natural gas, for a combined cost of $36,682,462. The <strong>Energy</strong> Use Index<br />

and GHG emissions for this year can be compared with the 2000 baseline to see progress<br />

to date on achieving the 2014 target.<br />

Table 1.1 also shows growth in building area and energy use projected to the year 2014<br />

without investment in new energy efficiency, based on new construction identified in the Five<br />

Year Capital Program (2007-08 to 2011-12). Actual growth could be higher. Additionally,<br />

this growth number includes the energy savings anticipated by the end of 2008 for the<br />

Partnership projects funded in the 2006-08 Program.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 1-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


1.3 <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

This <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> is intended to provide initial identification of potential for energy<br />

efficiency retrofit projects at all buildings over 50,000 square feet at University of California<br />

<strong>Los</strong> <strong>Angeles</strong>. In initial stages of the plan at the campus’ request, it was agreed that a subset<br />

of buildings would be investigated as specified by the campus and results extrapolated to<br />

other buildings. This refined list of campus approved buildings investigated in this report is<br />

summarized in Table 1.2. This includes primarily lighting, HVAC, commissioning and central<br />

plant measures. A number of other measures that apply in all sizes of buildings are<br />

identified as well. The potential for energy efficiency in new construction and renovated<br />

buildings is also addressed, based on the same Capital Program. A number of these<br />

efficiency projects were initially identified and evaluated by the campuses. A separate line<br />

item shows the potential from addition of photovoltaic power to parking roof areas on<br />

campus. This report does not represent an investment grade audit so the numbers are<br />

expected to be refined in the engineering process before the campus submits them for<br />

funding. All projects except photovoltaics were evaluated using the campus energy<br />

recharge rates.<br />

The <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> attempts to be comprehensive in its identification of potential<br />

energy projects, within the buildings agreed upon for investigation. As a result the total<br />

potential savings is significant and the payback periods for some of the measures are fairly<br />

long. During implementation the campus will select measures to implement which meet its<br />

investment and physical plant needs.<br />

The efficiency measures will be implemented through the <strong>UC</strong>/CSU Investor Owned Utility<br />

Partnership Program in the 2009-11 and 2012-14 funding cycles, and corresponding<br />

incentive programs from LADWP. Utility incentives are projected to be similar to past<br />

cycles, $0.24/kWh and $1.00/therm annual savings. <strong>Energy</strong> savings have been calculated<br />

on a project by project basis, with incentives based on the building level savings. The<br />

photovoltaic projects would be implemented using the California Solar Initiative incentives.<br />

The magnitude of project investment is many times greater than the size of past Partnership<br />

cycles, which have been constrained by the limited capital available from the campuses. A<br />

new funding mechanism will offer bond money from the Office of the President to pay<br />

upfront the University portion of the project cost, with the 15 year bond to be repaid by the<br />

campus through utility savings.<br />

The effect of these potential projects on meeting the efficiency and GHG targets is illustrated<br />

in Table 1.1. In this table the energy savings are reported as they would be measured at the<br />

utility meters, taking into account the effect of the cogeneration and TES at the central plant.<br />

The indication is that the 2014 energy goals can be met with an aggressive program of<br />

project implementation, but that more aggressive action may be required to achieve the<br />

GHG goals. The 2020 goals cannot be addressed until the 1990 baseline is established.<br />

The economics of these projects are described in Table 1.2, which lists the potential projects<br />

according to the funding source for the facility and the type of project. This table also lists<br />

the projected Partnership Program or Solar incentives and the net simple paybacks to the<br />

site, factoring in the incentives.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 1-2 December 31, 2008<br />

Newcomb | Anderson | McCormick


Table 1.1: Summary of Baseline and Projected <strong>Energy</strong> Usage, Emissions, and Goals<br />

<strong>Energy</strong> Component<br />

of GHG Emissions<br />

vs. 2000 Baseline<br />

2014 Target: 100%<br />

<strong>Energy</strong><br />

Component of<br />

GHG Emissions<br />

(tonne CO2 eq.)<br />

Source <strong>Energy</strong><br />

Use Index vs.<br />

2000 Baseline<br />

2014 Target: 90%<br />

Source<br />

<strong>Energy</strong> Use<br />

Index<br />

(kBtu/sf-yr)<br />

<strong>Campus</strong><br />

Area<br />

(GSF)<br />

Purchased<br />

Natural Gas<br />

(th/yr)<br />

Purchased<br />

Electricity<br />

(kWh/yr)<br />

19,817,189 217 100% 213,918 100%<br />

75,539,098 35,182,004<br />

Year <strong>Energy</strong> Use Basis<br />

1990 FY 89-90 Data Not<br />

Baseline<br />

Available<br />

2000 FY 99-00 Historical<br />

Baseline Use per <strong>UC</strong>OP<br />

22,774,007 220 101% 236,651 111%<br />

159,333,888 33,682,979<br />

FY 06-07 Historical<br />

Use per <strong>UC</strong>OP<br />

Most Recent<br />

Year<br />

25,175,205 231 106% 271,086 127%<br />

212,301,682 36,525,316<br />

With Projected Growth<br />

and 2006-2008<br />

Partnership Projects<br />

Add Potential<br />

<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong><br />

Efficiency Projects<br />

Add Potential Full<br />

Roof PV<br />

2014<br />

Projected<br />

25,175,205 186 86% 229,736 107%<br />

103,363,327 36,246,018<br />

25,175,205 183 84% 227,192 106%<br />

96,413,209 36,246,018<br />

2014<br />

Projected<br />

2014<br />

Projected<br />

2020 Growth Not Projected<br />

Notes:<br />

Source <strong>Energy</strong> 10,239 Btu/kWh Electric<br />

100,000 Btu/th Gas<br />

Emissions 0.000366 tonne CO2 eq/kWh<br />

0.005295 tonne CO2 eq/th<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 1-3 December 31, 2008<br />

Newcomb | Anderson | McCormick


Table 1.2: SEP Project Savings and Economics Summary<br />

Purchased Utility Savings<br />

Net Simple<br />

Payback<br />

Period (yr)<br />

Net Project<br />

Cost ($)<br />

Anticipated<br />

Incentive ($)<br />

Monetary<br />

($/yr) Project Cost ($)<br />

Demand<br />

(kW) Gas (th/yr)<br />

1,688,231 10,618,251 3,976,161 $ 6,642,090 3.9<br />

3,004,396 27,552,281 7,904,780 $ 19,647,501 6.5<br />

1,464,872 24,427,106 3,995,107 $ 20,431,999 13.9<br />

560,089 4,586,700 1,521,237 $ 3,065,463 5.5<br />

550,316 5,982,444 1,333,220 $ 4,649,224 8.4<br />

573,605 10,395,000 1,479,558 $ 8,915,442 15.5<br />

$ 7,841,510 $ 83,561,782 $ 20,210,063 $ 63,351,719 8.1<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

1,289<br />

1,148<br />

4,645<br />

707<br />

472<br />

624<br />

8,885<br />

$ 282,316 $ 1,760,663 $ 598,718 $ 1,161,945 4.1<br />

173,703 2,999,102 457,131 $ 2,541,971 14.6<br />

$ 371,653 $ 2,943,537 $ 1,013,600 $ 1,929,937 5.2<br />

$ 1,104,523 $ 11,584,479 $ 2,616,475 $ 8,968,004 8.1<br />

$ 1,932,195 $ 19,287,781 $ 4,685,924 $ 14,601,857 7.6<br />

$ 9,773,705 $ 102,849,562 $ 24,895,987 $ 77,953,575 8.0<br />

115,570<br />

-<br />

-<br />

163,728<br />

279,298<br />

279,298<br />

192<br />

277<br />

501<br />

962<br />

1,932<br />

10,817<br />

Electricity<br />

Efficiency Projects<br />

(kWh/yr)<br />

State Funded<br />

MBCx 19,184,439<br />

HVAC Retrofits 34,140,869<br />

Lighting Retrofits 16,646,278<br />

Other Retrofits 6,364,652<br />

New Construction 6,253,593<br />

Deferred Maintenance & Capital Renewal 6,518,233<br />

Subtotals 89,108,065<br />

Non State Funded<br />

MBCx 2,328,228<br />

HVAC Retrofits 1,973,897<br />

Lighting Retrofits 4,223,324<br />

New Construction 11,304,840<br />

Subtotals 19,830,290<br />

Total Efficiency Projects 108,938,355<br />

Monetary<br />

($/yr) Note<br />

$ (27,720) Assumes Power Purchase Agreement Method of Delivery<br />

$ (222,565) Assumes Power Purchase Agreement Method of Delivery<br />

$ (250,285)<br />

Purchased Utility Savings<br />

Electricity Demand<br />

Renewable Projects<br />

(kWh/yr) (kW) Gas (th/yr)<br />

Photovoltaics, 1st MW 1,386,000 1,000 -<br />

Photovoltaics, Remaining Potential 5,564,118 4,015 -<br />

Subtotals 6,950,118 5,015 -<br />

Purchased Utility Savings<br />

Net Simple<br />

Monetary<br />

Anticipated Net Project Payback<br />

($/yr) Project Cost ($) Incentive ($) Cost ($) Period (yr)<br />

$ 7,841,510 $ 83,561,782 $ 20,210,063 $ 63,351,719 8.1<br />

$ 1,932,195 $ 19,287,781 $ 4,685,924 $ 14,601,857 7.6<br />

$ (250,285)<br />

$ 9,523,420 $ 102,849,562 $ 24,895,987 $ 77,953,575 8.2<br />

Demand<br />

(kW) Gas (th/yr)<br />

8,885 -<br />

1,932 279,298<br />

5,015 -<br />

15,832 279,298<br />

Electricity<br />

Total Projects<br />

(kWh/yr)<br />

State Funded Efficiency Projects 89,108,065<br />

Non State Funded Efficiency Projects 19,830,290<br />

Renewable Projects 6,950,118<br />

TOTAL <strong>UC</strong>LA 115,888,473


The campus has reviewed a preliminary version of the initial list of potential projects in this<br />

report and has initiated a planning process for engineering, scheduling and implementation of<br />

the projects over the next six years. It is anticipated that the list of potential projects will be<br />

continuously tuned and updated as projects are built, savings are measured, new technologies<br />

become commercially available, and campus loads change over the course of the next six<br />

years. Because the campus is served by a municipal electric utility, the campus did not actively<br />

select projects for implementation concurrent with the IOU campus deadlines, so no distinction<br />

is made between potential projects and the planned or committed projects.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 1-5 December 31, 2008<br />

Newcomb | Anderson | McCormick


2. INTROD<strong>UC</strong>TION<br />

2.1 <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Methodology<br />

The University of California Office of the President has contracted with Newcomb Anderson<br />

McCormick (NAM) to create a <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> for nine campuses and five medical<br />

centers. This <strong>Plan</strong> will identify potential energy saving projects throughout these campuses that<br />

can be implemented over the next six years, and will evaluate their contribution to helping the<br />

campuses meet the system-wide goals of reduced energy consumption and reduced<br />

greenhouse gas emissions.<br />

Newcomb Anderson McCormick assembled a team of highly respected engineering firms and<br />

experts to perform the work at the campus and assemble the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong>. The team<br />

for <strong>UC</strong> Irvine included:<br />

Team Member Role<br />

Newcomb Anderson McCormick Program Manager, SEP Aggregation<br />

P2S Engineering <strong>Campus</strong> Field Auditor, Efficiency Projects<br />

Michael Wall Engineering Renewable <strong>Energy</strong> Projects, Power Quality<br />

Cogent <strong>Energy</strong> Air Handler Simulations<br />

A kickoff meeting was held at the campus on February 28, 2008, with representation from the<br />

campus facilities staff and housing. The kickoff meeting introduced the SEP team and process,<br />

collected valuable input and provided an understanding of the campus’ priorities and needs.<br />

Additionally, the list of 50,000 square foot and larger buildings to be included in the SEP was<br />

reviewed and buildings were removed to align the effort of the SEP with campus priorities and<br />

the best opportunities for energy savings. The resulting list of buildings (referred to as SEP<br />

Building List, or SEP Buildings) became the basis for the field work and building specific project<br />

identification.<br />

Following the kickoff meeting the field investigation phase ensued. Collectively, the team<br />

performed audits and analysis of all SEP buildings and other specific opportunities to identify<br />

the list of projects included in this report. The energy efficiency projects identified by the<br />

<strong>Campus</strong> Field Auditor were focused on the SEP Buildings’ mechanical and lighting systems,<br />

with field data collected on standardized field data templates (included in Appendix A).<br />

Renewable energy potential was investigated by Michael Wall Engineering, along with a brief<br />

power quality and reliability investigation, while Newcomb Anderson McCormick’s efforts<br />

focused on historical data collection, campus wide projects, projects outside of the SEP<br />

buildings and green house gas emission impacts.<br />

During the analysis phase, the previously compiled field data was analyzed to develop projects<br />

with consistency and reasonableness in mind, using the most detailed methods of analysis<br />

possible in the time available. To this end, a standardized analysis tool was used to analyze the<br />

majority of the air hander related projects. The analysis tool provides results which incorporate<br />

factors typical of a more detailed investigation as opposed to a strategic level project analysis,<br />

including system specifics, site specific weather data, operating schedules, control strategies<br />

and typical system setpoints as determined by field investigation. Analysis of other projects was<br />

performed using project-specific engineering calculations and followed recognized engineering<br />

principles. Reasonable engineering judgment was applied to all project analyses.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


Construction costs of recommended projects are built up from contractor quotes, Means<br />

manuals, experience from past project cycles, and a variety of other sources. Project costs are<br />

the sum of the construction cost and contingency (10%), engineering and design (15%),<br />

construction management (5%) and project management (6%). While individual projects’ final<br />

costs and savings may vary from the results presented in this report, it is anticipated that the<br />

aggregate level of accuracy by campus or by utility service territory will be reasonable.<br />

A preliminary list of energy efficiency projects, delivered to <strong>UC</strong>OP on March 28, was the initial<br />

step in delivery of the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> results. This list of projects was reviewed,<br />

prioritized and scheduled by the individual campuses and returned to <strong>UC</strong>OP. The compiled<br />

results were then used to determine the level of savings commitment for the Investor Owned<br />

Utilities to use in support of their filings to the CP<strong>UC</strong> for the <strong>UC</strong>/CSU/IOU Partnership Program.<br />

The results will also assist <strong>UC</strong>OP in planning for a bond to finance the campus contributions for<br />

the construction of these projects.<br />

As of the writing of this report, the details of the Partnership Program have not been defined for<br />

the 2009-2011 cycle, and discussions are ongoing with the Municipal utilities to solicit similar<br />

participation and incentive levels for the campuses. While these crucial details are not<br />

confirmed, this <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> was in large part commissioned to determine overall<br />

potential for projects, and is a critical step in securing the incentive funding levels from both the<br />

IOU and Municipal utilities, and for <strong>UC</strong>OP funding. Consequently, this report assumes that<br />

many of the aspects of the current plan will be carried forward, including the incentive rates of<br />

$0.24/kWh and $1.00/therm of annual savings. These rates are used in the analyses of all<br />

projects in this report, including those at campuses served by Municipally Owned Utilities.<br />

Following delivery of the Preliminary List, the projects in this <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> report were<br />

aggregated and assembled. The projects from the Preliminary List are included, with some<br />

refinements following additional quality control checks. Projects have been compared to<br />

historical energy use and project costs have been refined. Other projects have been added<br />

following the development of the Preliminary List, including renewable electric generation<br />

projects (such as photovoltaics, which qualify for different utility programs), and projects which<br />

save electricity supplied by Municipally Owned Utilities whose energy efficiency programs are<br />

not regulated by the CP<strong>UC</strong> (including SMUD, LADWP and the City of Riverside). Details for<br />

these projects replace the placeholder savings previously projected.<br />

The projects included in this SEP are the result of a survey of the campus, discussions with<br />

campus personnel, and preliminary engineering of projects. This effort is not an investment<br />

grade audit. This means that the projects will require additional detailed cost estimating and<br />

refinement of savings before the campuses or the utilities can commit to specific construction<br />

budgets and energy saving calculations.<br />

This effort was designed to identify significant physical modifications required to make buildings<br />

energy efficient. It did not concentrate on operational details that might be found in an<br />

investment grade audit, such as a broken economizer, or an improper control sequence.<br />

However, the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> does recommend the monitoring-based commissioning<br />

(MBCx) of each of these buildings over the next six years (excluding buildings that have already<br />

been commissioned through the Partnership). This process will ensure that the operational<br />

problems of each building are identified and corrected, so that all measures that might be<br />

identified in an investment grade audit will ultimately be included.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-2 December 31, 2008<br />

Newcomb | Anderson | McCormick


The equivalent energy and cost savings for projects presented in the Preliminary List were been<br />

simplified to meet the financial criteria established for the <strong>UC</strong>OP funding mechanism, and to be<br />

consistent with utility incentive requirements. For HVAC projects, chilled water and hot water<br />

(or steam) savings calculated at the buildings were converted to electric (kWh) and natural gas<br />

(therm) savings using marginal central plant efficiencies, and summed with direct electric and<br />

natural gas savings, which include cooling or heating from local sources. For all other projects,<br />

the electric and gas savings were calculated directly, without involving the intricacies of the<br />

central plant. The sums of these savings for each project became the equivalent electric and<br />

gas savings, and are used for the basis of the utility incentive. The published FY06-07 recharge<br />

rates, as provided by <strong>UC</strong>OP, were applied to the equivalent electric and gas savings to estimate<br />

the energy cost savings of projects. Using the recharge rate builds in a level of conservatism for<br />

future energy savings, as no utility rate escalation is built in, and meets <strong>UC</strong>OP bond funding<br />

requirements. Operational and maintenance savings have generally been discounted in<br />

financial analysis of measures, as <strong>UC</strong>OP funding will involve only the purchased utility budgets<br />

as a repayment source.<br />

The equivalent energy savings methodology remains unchanged from the preliminary list to this<br />

SEP report. However, the central plant and any cogeneration impacts are incorporated to<br />

reflect a purchased utility cost savings and give a more true estimate of utility cost savings for<br />

the campus.<br />

The following tables show the recharge rates and marginal central plant efficiencies used in this<br />

report. The individual campuses may charge themselves different prices internally, or may<br />

calculate marginal utility costs differently, and so can use other pricing in their internal project<br />

evaluation.<br />

Table 2.1: Recharge Rates - Non-State Funded and Auxiliaries FY 06-07<br />

<strong>Campus</strong> $/kWh $/Therm<br />

<strong>Los</strong> <strong>Angeles</strong> $0.088 $0.670<br />

Table 2.2: Marginal Central <strong>Plan</strong>t Efficiencies<br />

<strong>Plan</strong>t kWh/ <strong>Plan</strong>t Therm <strong>Plan</strong>t Therm/<br />

<strong>Campus</strong><br />

Bldg ton-hr /Bldg ton-hr Bldg MMBTU<br />

<strong>Los</strong> <strong>Angeles</strong> 0.8 0 12.5<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-3 December 31, 2008<br />

Newcomb | Anderson | McCormick


<strong>Campus</strong><br />

<strong>Los</strong> <strong>Angeles</strong><br />

Santa Monica<br />

Hospital<br />

<strong>Los</strong> <strong>Angeles</strong>,<br />

Westwood<br />

Med Facilities<br />

Table 2.3: Central <strong>Plan</strong>t & Cogeneration Impacts on Purchased Utilities<br />

Building<br />

<strong>Energy</strong> Saved<br />

Steam<br />

Chilled Water<br />

Electricity<br />

Purchased Utility<br />

Savings Notes<br />

Steam not required for space heating is used in<br />

the low pressure end of the steam turbine to<br />

62.4 kWh/MBtu increase electrical output.<br />

High pressure steam diverted from the chillers<br />

to the steam turbine will increase electrical<br />

0.72 kWh/tonh output.<br />

1 kWh/kWh<br />

Combined Cycle Cogen: Reduction in electricity<br />

use lowers purchases from utility.<br />

Steam 12.5 th gas/MBtu Steam is delivered by natural gas fired boilers.<br />

Chilled Water 0.8 kWh/tonh<br />

Electricity 1 kWh/kWh No cogenerated electricity<br />

Steam 62.4 kWh/MBtu Steam comes from <strong>UC</strong> <strong>Los</strong> <strong>Angeles</strong>.<br />

Chilled Water 0.72 kWh/tonh From <strong>UC</strong> <strong>Los</strong> <strong>Angeles</strong><br />

Electricity 1 kWh/kWh Combined Cycle Cogen: Buy from <strong>UC</strong>LA.<br />

2.2 General Project Identification Categories and Approach<br />

The following is a general description of the projects that were identified by the <strong>Strategic</strong> <strong>Energy</strong><br />

<strong>Plan</strong>. More detailed scope and savings information is included in the Project Descriptions<br />

section of the report.<br />

In general, projects were selected for this report that will bring campus systems up to the state<br />

of the art technology. This is intended to identify all of the possible energy savings available<br />

through retrofit projects. This results in some projects with longer paybacks where the existing<br />

system may be moderately efficient, but not necessarily state of the art. However, it defines a<br />

maximum savings target for the buildings evaluated. The campuses can decide on the<br />

appropriate level of investment based on their individual needs and their performance in<br />

meeting energy savings and green house gas emissions goals.<br />

2.2.1 Lighting Projects<br />

The report identifies the potential to convert existing 32W T8 fluorescent fixtures to 28W T8<br />

lamps with premium efficiency ballasts with low ballast factor, at 42 W per two lamp fixture.<br />

Several campuses have alternative standards, including <strong>UC</strong> Santa Barbara, which is<br />

emphasizing dimming ballasts. Also recommended are increased penetration of occupancy<br />

sensor controls, daylight harvesting, new stairwell fixtures, and replacement of interior HID<br />

fixtures with fluorescent. Fluorescent conversion is also generally recommended for parking<br />

structures.<br />

2.2.2 HVAC Projects<br />

A variety of HVAC projects are recommended for implementation at campus buildings. The<br />

general intention of these retrofits is to make all air handlers of 10 hp and above meet basic<br />

efficiency standards: variable air volume with economizers, operating only the hours necessary,<br />

with direct digital controls, demand control ventilation where warranted, and static pressure<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-4 December 31, 2008<br />

Newcomb | Anderson | McCormick


eset. Laboratory air handlers would also be converted to variable air volume, with variable flow<br />

fume hoods and minimum ventilation controls set at 6 air changes per hour. In some cases<br />

further savings will be achieved through air quality monitoring and automatic sash closers.<br />

Kitchen hoods are recommended for conversion to variable air volume as well. A variety of<br />

other chiller and boiler projects are recommended for other buildings that are not served by a<br />

central plant.<br />

2.2.3 Monitoring Based Commissioning Projects<br />

This report includes a monitoring-based commissioning project at every <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong><br />

building. This is an integral element of the retrofit projects that are recommended at most<br />

buildings. The combination of retrofits and commissioning will capture the majority of the<br />

energy saving potential of the HVAC systems. Monitoring based commissioning is also<br />

recommended for all main central plants where it has not yet been implemented.<br />

2.2.4 New Construction and Renovation from Capital Program<br />

This report includes a number of planned construction and renovation projects at each campus.<br />

It is assumed that a Savings By Design process will be in place to generate a design which<br />

outperforms Title 24 by at least 30%. The campus contribution to the resulting construction<br />

costs are assumed to come from <strong>UC</strong>OP bond funding. This removes the capital constraint from<br />

the construction budget and allows more efficient buildings to be designed and built.<br />

2.2.5 Deferred Maintenance and Capital Renewal Projects<br />

The campuses each spend up to $10 million per year on deferred maintenance and capital<br />

renewal projects. This report estimates that about 12% of these projects have an energy<br />

savings component. It is recommended that utility incentives be employed to make these<br />

measures marginally more efficient. It is also recommended that <strong>UC</strong>OP bond funds be used<br />

where possible to supplement project funding to allow construction of energy saving projects<br />

that otherwise might not be funded.<br />

2.2.6 <strong>Campus</strong> Wide Projects<br />

<strong>Campus</strong> wide projects include the replacement of pre-2001 refrigerators with <strong>Energy</strong> Star units,<br />

replacement of lab freezers with more efficient units, and the installation of occupancy sensor<br />

controls on vending machines. The campus wide use of power management software is<br />

recommended to reduce the energy consumption of network computers when they are not in<br />

use. The replacement of CRT monitors with LCD monitors is recommended as well. Finally, an<br />

estimate of the potential energy savings from computer server virtualization was included.<br />

2.2.7 Other Projects<br />

Several other miscellaneous projects were evaluated, including swimming pool projects. Pool<br />

covers with powered take up spools were recommended where they are not currently used.<br />

Variable speed drives are recommended for pool filter pumps during off hours operation. Solar<br />

collectors are also recommended for pools where adjacent roof space is available. In addition,<br />

boiler replacement was evaluated for swimming pool and other boilers for thermal loads not<br />

served by the central plant.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-5 December 31, 2008<br />

Newcomb | Anderson | McCormick


2.3 <strong>Campus</strong> Overview<br />

University of California, <strong>Los</strong> <strong>Angeles</strong> was founded in 1919 and opened its medical center in<br />

1955. The campus currently has approximately 27,000 undergraduate and 11,500 graduate<br />

students, and over 4,000 faculty members. <strong>UC</strong>LA is one of the most prestigious campuses in<br />

the University of California system with 174 buildings spread across 419 acres.<br />

The majority of the buildings audited for at <strong>UC</strong>LA are old and historic. Chilled water and heating<br />

hot water is supplied from campus central plant except for few buildings which have localized<br />

chillers and hydronic boilers. Buildings audited included residential, educational, athletic,<br />

medical and research facilities. Residential buildings use water source heat pumps and split air<br />

conditioning units. A majority of the laboratory buildings have constant volume fume hoods and<br />

dual duct mixing boxes for zone control. Molecular Science Building, a laboratory building has<br />

variable air volume fume hoods with VAV box for zone control. Animal research facilities also<br />

have constant volume terminal boxes with higher air change rate (ACH @ 15). Buildings employ<br />

either direct digital controls (DDC) or pneumatic controls to control and monitor major<br />

mechanical equipment and for zone control. Air handling units serving buildings vary from and<br />

include constant volume dual duct air handlers, variable air volume air handlers, and multi zone<br />

units. Some of VAV AHU’s have inlet guides vanes to control supply air flow. All major<br />

mechanical equipment in building is controlled and scheduled through campus energy<br />

management system (Siemens Apogee).<br />

2.4 Central <strong>Plan</strong>t<br />

The central plant at <strong>UC</strong>LA serves the main campus in Westwood. It is based on a cogeneration<br />

system which includes two GE LM 1600 gas turbines, each with a rating of 14.5 MW, two high<br />

pressure (600 psig) heat recovery steam generators with duct burners, and an<br />

induction/extraction condensing steam turbine, for a total generation capacity of about 40 MW.<br />

Power is generated in parallel with LADWP, providing most of the campus electric load, which<br />

peaks at about 50 MW. The facility also houses two backpressure steam turbine centrifugal<br />

chillers rated at 5,300 tons, four single stage absorption chillers, and an electric centrifugal<br />

chiller rated at 5,300 tons. Steam is provided to the campus at 100 psig. A portion of the gas<br />

used to operate this plant is recovered from the Mountain Gate Landfill.<br />

2.5 <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Buildings<br />

The following 41 buildings were investigated as part of this SEP effort, and were selected using<br />

the criteria described above. The total gross area of the SEP buildings represents<br />

approximately 6 million square feet, or 29% of the campus gross area (exclusive of parking). An<br />

additional 18 buildings were identified as appropriate to extrapolate findings to directly,<br />

incorporating approximately 8.7 million square feet (or 42%) of total building area into this<br />

report.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-6 December 31, 2008<br />

Newcomb | Anderson | McCormick


Table 2.4: SEP Buildings<br />

Building Key Building Name<br />

Basic Gross Area -<br />

Non-assignable Parking Area<br />

04C4202 PERLOFF HALL 65,909<br />

04C4203 YOUNG LIBRY 305,919<br />

04C4228A GEOLOGY 182,149<br />

04C4228C MOLECULR SCI 178,666<br />

04C4235 WOODEN/PS4 207,721<br />

04C4256A ENGR BLDG 4 294,124<br />

04C4260 FACMGMT BLDG 189,197<br />

04C4265 TIVERTON HSE 57,224<br />

04C4270 WILSHIRE CTR 315,208<br />

04C4302A CANYON POINT 107,419<br />

04C4302D COVEL COMMON 144,067<br />

04C4310 KERCKHOFF 70,820<br />

04C4315 GONDA CENTER 125,202<br />

04C4317 LAW 275,439<br />

04C4318A POWELL LIB 166,846<br />

04C4320 LIFE SCIENCE 214,613<br />

04C4325 DORIS STEIN 94,309<br />

04C4331 PUBLIC HLTH 140,563<br />

04C4332E M DAVIES CC 70,228<br />

04C4333 JULES STEIN 87,905<br />

04C4343 BOELTER HALL 373,904<br />

04C4344 MORTON MED 366,834<br />

04C4345 MED PLZA 200/300 101,095<br />

04C4348 MACDONALDLAB 144,611<br />

04C4352 SYCAMORE CT 98,951<br />

04C4360 SAC 113,383<br />

04C4374 FOWLER MUSM 101,995<br />

04C4375 ROYCE HALL 184,673<br />

04C4415 UNEX 95,065<br />

SOUTHERN REGIONAL<br />

04C4562 LIBRARY FACILITY 228,306<br />

04C4580 BUNCHE HALL 229,248<br />

04C510B SMH EMERGCY** 18,059<br />

04C510D SMH PAVILION** 194,181<br />

04C510F SMH WST TOWR** 202,568<br />

04C510H SMH CENT PLT** 21,427<br />

04C515A COLLINS CTR 31,311<br />

04C515B GOLD HALL 55,344<br />

04C515C ENTREP HALL 72,591<br />

04C515D CORNELL HALL 71,737<br />

04C515E ROSNFLD LIBR 51,046<br />

04C515F MULLIN CMNS 33,957<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-7 December 31, 2008<br />

Newcomb | Anderson | McCormick


Table 2.4: SEP Buildings (Continued)<br />

Building Key Building Name<br />

Basic Gross Area -<br />

Non-assignable Parking Area<br />

Buildings with Extrapolated Results<br />

04C4332D MED SCHOOL N/A – only part of building<br />

04C4200 MURPHY HALL 220,188<br />

04C4227 SLICHTER 62,557<br />

04C4228B YOUNG HALL 297,589<br />

04C4319 FRANZ HALL 238,054<br />

04C4329 REED RESRCH 69,176<br />

04C4332B BRAIN RSCH 86,578<br />

04C4334 DENTISTRY 204,369<br />

04C4335 SCHOENBERG 122,552<br />

04C4336 FACTOR 199,857<br />

04C4359 MATH SCIENCE 224,078<br />

04C4363 KNUDSEN HALL 164,702<br />

04C4403 BOYER HALL 133,042<br />

04C4577A MELNITZ HALL 61,827<br />

04C4578 MACGOWAN 129,542<br />

04C4579 PUBLIC AFFAIRS 201,667<br />

04C4581 WARREN HALL 102,205<br />

04C4594 REHAB CENTER 142,566<br />

** Buildings removed from scope at request of campus during course of investigation due to<br />

availability of Med <strong>Center</strong> personnel and prioritization of activities related to the opening of the<br />

new hospital.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-8 December 31, 2008<br />

Newcomb | Anderson | McCormick


2.6 Recent <strong>Energy</strong> Project Inventory<br />

The campus has participated in the <strong>UC</strong>/CSU/IOU Partnership Programs. The projects in Table<br />

2.5 were implemented during the 2004-05 Partnership cycle. Since they were implemented no<br />

later than calendar year 2005, the associated energy savings are considered to be reflected in<br />

the historical energy use data gathered for 2006-07. Therefore, no adjustment has been made<br />

to the campus’ baseline energy use.<br />

Table 2.5: 2004-05 <strong>UC</strong>/CSU/IOU Project History<br />

Electric Gas<br />

Savings Savings<br />

Building Project Description<br />

(kWh/yr) (th/yr)<br />

3 Pools Pool covers - 3 pools (19,320 sqft) 0 90,070<br />

Pool Pool cover - 1 pool (6000 sqft) 0 23,470<br />

Pool Pool cover - 1 pool (3,750 sqft) 0 17,910<br />

Pool Pool cover - 1 pool (525 sqft) 0 2,610<br />

Factor Building MBCx 337,510 83,365<br />

The projects in Table 2.6 are planned, or may have begun during the current 2006-08<br />

<strong>UC</strong>/CSU/IOU Partnership, but were not substantially complete prior to the FY06-07 historical<br />

energy use baseline. Since they are scheduled for implementation, the SEP has considered<br />

these projects in a couple of ways. First, the projects recommended in this report have not<br />

included these projects, thereby avoiding duplication of measures. Second, the 2006-07<br />

baseline energy use has been adjusted by the anticipated energy savings for baseline energy<br />

use to compare the proposed projects to, and for the comparison of, building benchmarks.<br />

Details of savings for each project in SEP buildings and the associated adjustment in baseline<br />

energy are reflected on the building summary sheets later in this report.<br />

Table 2.6: 2006-08 <strong>UC</strong>/CSU/IOU Project History<br />

Electric<br />

Savings<br />

Building<br />

SEP Buildings<br />

Project Description<br />

(kWh/yr)<br />

MSB<br />

MSB<br />

Upgrade vent and controls and install ZP sensors on 194<br />

fume hoods<br />

Upgrade vent and controls and install ZP sensors on 26<br />

fume hoods<br />

37 Buildings Occupancy Sensor Project (not part of Partnership)<br />

Gas<br />

Savings<br />

(th/yr)<br />

Not<br />

Reported 167,232<br />

Not<br />

Reported 22,410<br />

Not<br />

Reported 0<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 2-9 December 31, 2008<br />

Newcomb | Anderson | McCormick


3. HISTORICAL CAMPUS ENERGY USE<br />

3.1 FY 99-00 and 06-07 <strong>Energy</strong> Baseline<br />

Purchased electricity and natural gas consumption for the <strong>UC</strong>LA and <strong>UC</strong>LA MC are provided in<br />

the graphs below. The University of California Office of the President has provided information<br />

on purchases for fiscal years 1999-2000, 2005-2006, and 2006-2007 1 . Reliable information is<br />

not currently available for the fiscal year 1989-1990. The information is divided between statefunded<br />

buildings (shown in blue) and non state-funded buildings (shown in red). Savings from<br />

energy efficiency projects will use the fiscal year 2006-2007 as the baseline for comparison.<br />

1 <strong>Campus</strong> PU Costs & Usage State & NonSt.xls<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 3-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


4. HISTORIC BUILDING ENERGY USE<br />

4.1 Existing Metering Infrastructure<br />

Three types of metered historical energy use data were requested from <strong>UC</strong>LA energy<br />

management personnel – total annual, total monthly, and interval data for one summer and one<br />

winter week. An effort was made to obtain this data for each of the four utilities present on the<br />

<strong>UC</strong>LA campuses – electric, gas, chilled water, and steam. However, building-level meter data<br />

was not available for any of the utilities. The campus reports that there are existing building<br />

meters, but that they are not networked and are manually read. The campus indicated that any<br />

readings available would not be easy to obtain, nor valuable and requested averages be used<br />

for the purposes of this report.<br />

The percentage of SEP buildings on the <strong>UC</strong>LA campuses for which metered electricity and gas<br />

consumption was available is shown in Table 4.1. This table also shows estimates of the<br />

percentage of non-metered buildings, applying the assumption that if data was not provided it<br />

was because the building lacked a functioning meter. This is very likely to overstate the number<br />

of buildings without meters, as other causes for missing data were occasionally reported by<br />

energy management personnel throughout the <strong>UC</strong> system.<br />

Metered<br />

Table 4.1: Building Electric and Gas Meters<br />

SEP Buildings<br />

No Metered Data<br />

Available<br />

Electric Gas Electric Gas<br />

SEP<br />

Bldgs<br />

W/Local<br />

Gas<br />

Total<br />

SEP<br />

Bldgs<br />

Total<br />

Bldgs<br />

0 0% 0 0% 41 100% 41 100% - 41 372<br />

The number of SEP buildings for which chilled water and steam consumption was available is<br />

show in Table 4.2. Again, it is assumed that the SEP buildings with no metered data lacked a<br />

functioning meter.<br />

Table 4.2: Building BTU Meters<br />

SEP Buildings<br />

Metered<br />

No Metered Data<br />

Available<br />

SEP<br />

Bldgs<br />

W/Distr.<br />

Total<br />

SEP Total<br />

Heating Cooling Heating Cooling Heat Bldgs Bldgs<br />

0 0% 0 0% 41 100% 41 100% - 41 372<br />

We recommend that all SEP buildings that currently lack metered data be outfitted with a meter<br />

for each utility. The Monitoring Based Commissioning (MBCx) measures that we have outlined<br />

in Section 8.3 should provide meters for all of the SEP buildings. However, additional meters<br />

are appropriate for buildings that are below the 50,000 SF threshold that are large energy<br />

consumers.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 4-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


4.2 Individual Building Metering<br />

Building-level meter data was not available for this study. Estimates of baseline building energy<br />

consumption were therefore made using campus average values. This campus average was<br />

estimated based on total campus energy purchase data, with adjustments to account for gas<br />

consumption and electricity production by the cogen facility. The sources of building energy<br />

estimate data for <strong>UC</strong>LA are summarized in Table 4.3.<br />

Table 4.3: Sources of Data Used for Baseline Building <strong>Energy</strong> Estimates<br />

PREFERRED METHOD<br />

Use actual metered consumption<br />

ALTERNATE METHOD<br />

Extrapolate use using average values from the following sources<br />

Basic Buildings Complex Buildings<br />

Electricity derived from total derived from total<br />

campus electricity campus electricity<br />

purchase, plus cogen purchase, plus cogen<br />

plant’s production plant’s production<br />

Gas derived from total derived from total<br />

campus gas<br />

campus gas<br />

purchase, less cogen purchase, less cogen<br />

plant’s consumption plant’s consumption<br />

[1a]<br />

[1b]<br />

Steam<br />

same as gas use same as gas use<br />

(SEP buildings only) [2a]<br />

[2b]<br />

Chilled Water<br />

(SEP buildings only)<br />

median value from<br />

other campuses<br />

median value from<br />

other campuses<br />

Using the various sources described in Table 4.3, factors with units of energy use – kWh, therm,<br />

or MMBtu – per gross square foot were developed for each of the energy use categories in the<br />

left column of the table. A procedure was required to apply the appropriate factors to each<br />

building. For SEP buildings, this procedure relied on the building classification – “basic” or<br />

“complex”. A sample of the decision structure applied to each building to determine the<br />

appropriate energy use factors for steam and gas is shown in Figure 4.1. Similar structures<br />

were used to apply appropriate factors for electricity and chilled water.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 4-2 December 31, 2008<br />

Newcomb | Anderson | McCormick


Figure 4.1: Decision Structure for Estimating Building Steam and Gas Consumption*<br />

Extrapolate Using<br />

[2a]<br />

Basic<br />

<strong>Campus</strong> provided<br />

building<br />

consumption data<br />

No<br />

Is it an SEP<br />

building?<br />

Yes<br />

Is heating provided<br />

by the central<br />

plant?<br />

Yes<br />

Building Type is<br />

Complex/Simple<br />

No<br />

Complex<br />

Yes<br />

Extrapolate Using<br />

[2b]<br />

[1a] – [2b] refer to the factors described in Table 4.3<br />

Report actual<br />

usage<br />

Report<br />

heating as gas<br />

Extrapolate Using<br />

[1a]<br />

Complex<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 4-3 December 31, 2008<br />

Newcomb | Anderson | McCormick<br />

Basic<br />

Building Type is<br />

Complex/Simple<br />

Extrapolate Using<br />

[1b]<br />

The building energy consumption estimated by applying campus averages to building area<br />

provides a rough measure of the baseline building energy use for buildings that lacked metered<br />

data. The overall accuracy of this method is dependent upon the accuracy of the reported<br />

campus energy purchase on which it is based. The summed estimates of building energy<br />

consumption exactly equal the reported energy purchase. Building-level estimates developed<br />

by this method are useful as a baseline against which savings estimates can be measured.<br />

However, for any individual building the actual baseline energy use may differ significantly from<br />

the estimate due to the variation among buildings.<br />

4.3 Building <strong>Energy</strong> Use Targets<br />

The absence of metered annual energy use for buildings on the <strong>UC</strong>LA campuses precluded the<br />

development of building energy use targets based on local data. Instead, the building-level<br />

energy consumption from the <strong>UC</strong> San Diego SEP buildings is presented as indicative of the<br />

building energy consumption that can be achieved by buildings with similar use. Electricity use<br />

*


of <strong>UC</strong>SD buildings is shown in Figure 4.2, grouped according to whether the building is<br />

identified as Basic or Complex.<br />

Note that there is a broad range in electricity use intensities. In addition, some of the Basic<br />

buildings use more electricity per square foot than some of the Complex buildings. Although<br />

there are significant differences from one building to another, the performance of some buildings<br />

at a relatively low electricity use per square foot suggests a performance target for buildings on<br />

the <strong>UC</strong>LA campuses. The San Diego climate, on average, requires more cooling than the <strong>Los</strong><br />

<strong>Angeles</strong> climate. Therefore, performance targets based on the <strong>UC</strong> San Diego building-level<br />

data should represent a conservative estimate of the improvements that can be achieved in<br />

buildings on the <strong>UC</strong>LA campus.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 4-4 December 31, 2008<br />

Newcomb | Anderson | McCormick


Figure 4.2: Electricity Use Index for <strong>UC</strong> Santa Diego & MC Buildings with Meter Data<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

Electricity Consumption (kWh/GSF-yr)<br />

10<br />

0<br />

RITTER REPL<br />

NIEREN ANNEX<br />

GYMNASIUM<br />

SCI ENG RSCH<br />

PRICE CTR<br />

WAR LEC HALL<br />

NIERENBERG<br />

COG SCI BLDG<br />

CENTER HALL<br />

GALBRTH HALL<br />

GEISEL LIB<br />

TOR PINE NOR<br />

TOR PIN CTR<br />

H SS BLDG<br />

MULTIPURPOSE<br />

PEPCYNHALL<br />

SOC SCI BLDG<br />

RCRH ARGO<br />

UH BACH CYN<br />

TENAYA HALL<br />

TIOGA HALL<br />

GOLDBERG<br />

BLACK<br />

BRENNAN<br />

DOUGLAS<br />

7835 TRADE<br />

UH OUTPT CTR<br />

U HOSPITAL<br />

UH SOUTH WNG<br />

CLIN SCI BLD<br />

CMM EAST<br />

SVERDRUP<br />

PACIFIC HALL<br />

CMM WEST<br />

YORK HALL<br />

CENT MOL GEN<br />

PERLMAN HOSP<br />

THORNTON HSP<br />

BONNER HALL<br />

MTF<br />

BIOLOGY BLDG<br />

MCGILL/MANDLER<br />

BAS SCI BLDG<br />

CHEM RES BLD<br />

CALITIT<br />

UREY HALL<br />

MAYER HALL<br />

ENG UNIT 2<br />

ENG UNIT 1<br />

AP M BLDG<br />

EBU 3B<br />

RIMAC<br />

CTF (Hillcrest)<br />

MANDEVILLE<br />

HUBBS HALL<br />

CMRR<br />

Basic Complex<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 4-5 December 31, 2008<br />

Newcomb | Anderson | McCormick


5. UTILITIES<br />

5.1 Providers & Tariffs<br />

In the baseline 2006-07 Fiscal Year, electricity at <strong>UC</strong>LA main campus was provided <strong>Los</strong><br />

<strong>Angeles</strong> Department of Water and Power, and by the cogeneration plant. The Santa Monica<br />

hospital is served by Southern California Edison (SCE), for both commodity and transmission<br />

and distribution.<br />

The campus purchases natural gas with the majority of the commodity for the cogeneration from<br />

the Department of General Services, and Southern California Gas (SCG) provides the<br />

transportation service. Approximately 8% of its natural gas is landfill gas provided by nearby<br />

Mountain Gate Landfill. SCG provides the natural gas for the remaining campus use, other than<br />

cogeneration.<br />

5.2 Procurement Options<br />

There are limited procurement options for the campus, but the campus is taking advantage of<br />

opportunities and should continue to explore other avenues if and when available.<br />

For electricity, current regulations do not allow for direct access, so electricity in excess of the<br />

campus’ self generating capacity is likely to remain with LADWP for the foreseeable future. For<br />

natural gas, the campus is already exercising its option to purchase gas commodity on the DGS<br />

rate schedule.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 5-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


6. CAMPUS ELECTRIC INFRASTR<strong>UC</strong>TURE<br />

Although the term “power quality” can be used to describe a variety of electrical generation and<br />

distribution system attributes, for the purposes of this study, issues that could result in additional<br />

energy charges from the utility were the focus. Primarily, these are conditions that cause a<br />

differential between campus and/or facility kW and kVA usage. When this differential is large<br />

enough, the utility will apply an additional charge, commonly referred to as a VAR charge. A<br />

review of the <strong>UC</strong>LA campus utility charges and discussion with facilities personnel confirms that<br />

there are no power quality issues of this type on campus.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 6-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


7. RENEWABLE ENERGY GENERATION<br />

7.1 Technologies<br />

Sustainable energy sources are available in many types and forms, including photovoltaics, fuel<br />

cells, and wind power. The use of direct solar heating as an alternative energy source is<br />

discussed under Section 8 of this report.<br />

Fuel cell infrastructure and operational requirements typically give this type of generation project<br />

an unacceptably long payback, unless the cell was designed to be installed as part of curriculum<br />

or research requirements. As such, fuel cell use was discounted. Additionally, wind patterns in<br />

and around the buildings at the campus were not conducive to a reliable pattern that could<br />

sustain sufficient power generation to make a wind power project viable.<br />

Photovoltaic sources were identified as the most cost-effective and readily available means of<br />

sustainable energy. The remaining evaluation of sustainable energy on campus is focused on<br />

this technology. The most efficient, least intrusive form of this technology is a relatively flat, nonpenetrating<br />

array mounted on a rooftop or parking structure canopy. This resource is available<br />

from several sources around the globe, and is not considered proprietary. Available square<br />

footage for power production assumes maximum exposure at a low angle of incidence, along<br />

with regular access and maintenance of the equipment. Due to the potential for substantial<br />

variance in the availability of incentives and funding for installation due to existing public utility<br />

agreements, third-party power contracts, and the potential for existing renewable resources<br />

already in use at the campus, no incentives are included to offset construction costs.<br />

7.2 Existing Renewable Sources<br />

<strong>UC</strong> <strong>Los</strong> <strong>Angeles</strong> currently procures approximately 8% of its natural gas consumed by the<br />

cogeneration plant from a landfill source. No other major renewable energy sources are on<br />

campus.<br />

7.2.1 Potential Projects<br />

The University’s cost of Power Purchase Agreement photovoltaic power used in this report is<br />

assumed to be $0.02/kWh above available retail power for the first 1 MW of photovoltaic power,<br />

assuming the third party receives the utility incentives, tax credits and so on. The University’s<br />

cost of PPA PV power for all capacity beyond the first 1 MW is assumed to be $0.04/kWh above<br />

available retail power for IOU customers. It is assumed that the campus will have access to the<br />

Renewable <strong>Energy</strong> Credits associated with this power, at least in time for the 2014 and 2020<br />

target dates.<br />

The study identified a total photovoltaic potential of 5 MW of system capacity at an estimated<br />

construction cost of $47.3M. System locations and details are listed in the table below. Based<br />

on the California <strong>Energy</strong> Commission’s Clean Power Estimator tool, the annual output of the<br />

system is estimated at 6,950,118 kWh.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 7-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


Table 7.1: Photovoltaic Project Potential<br />

Estimated Annual<br />

Building<br />

Available Roof<br />

PV System<br />

Estimated PV System<br />

Building Name<br />

Power Output (kW-<br />

Number<br />

Area (sf)<br />

Capacity (kW)<br />

Construction Cost***<br />

h)**<br />

PARKG STR 9 04C4208 67,800 47,460 8.5 403 559,126 $3,832,395<br />

PV Power<br />

Density<br />

(W/sf)*<br />

Gross<br />

Roof Area<br />

(sf)<br />

PARKG STR 8 04C4209 206,400 109,480 8.5 931 1,289,784 $8,840,510<br />

PARKG STR 2 04C4210 99,000 69,300 8.5 589 816,423 $5,595,975<br />

PARKG ST CHS 04C4211 122,500 73,500 8.5 625 865,904 $5,935,125<br />

PARKG STR 32 04C4263 63,000 44,100 8.5 375 519,542 $3,561,075<br />

PARKG STR 1 04C4342 108,300 75,810 8.5 644 893,118 $6,121,658<br />

PARKG STR 5 04C4587 40,000 23,250 8.5 198 273,908 $1,877,438<br />

PARKG STR 3 112,250 72,963 8.5 620 859,577 $5,891,762<br />

MED PLZA 100 04C4006 17,500 6,860 8.5 58 80,818 $524,790<br />

DENTISTRY 04C4334 30,000 18,000 8.5 153 212,058 $1,377,000<br />

MORTON MED 04C4344 47,500 17,500 8.5 149 206,168 $1,338,750<br />

MED PLZA 300 04C4345 30,400 16,720 8.5 142 196,978 $1,279,080<br />

SMH WST TOWR 04C510F 27,280 15,000 8.5 128 176,715 $1,147,500<br />

<strong>UC</strong>LA <strong>Campus</strong> Total 589,943 5,015 6,950,118 $47,323,057<br />

* Based upon CEC typical PV module rating.<br />

** Based upon 1370 equivalent full load sun-hours per year, calculated using Clean Power Estimator (http://www.consumerenergycenter.org/renewables/estimator/index.html) for a Simple<br />

Commercial PV System, 5 degree tilt, south facing system in zip code 90095.<br />

*** Based upon $9.00 per watt for roof installation, or $9.50 per watt for parking structure installation, exclusive of tax credits, rebates, or incentives.<br />

2413.01/Reports/<strong>UC</strong> SEP Draft Report – <strong>UC</strong>LA.doc 7-2 December 31, 2008<br />

Newcomb | Anderson | McCormick


8. RECOMMENDED ENERGY EFFICIENCY PROJECT DESCRIPTIONS<br />

The projects identified in this SEP are described below, and the project titles are referenced for<br />

each applicable project on the individual Project Summary pages later in this report. While<br />

there are often alternative technologies or approaches to projects that can be considered for a<br />

given retrofit, this report’s recommendations focus on projects that can be implemented cost<br />

effectively with available technologies and methods. Where appropriate, alternate approaches<br />

and considerations are discussed for projects considered but not included as a recommendation<br />

of this SEP.<br />

For ease of reference, all SEP projects have been assigned an SEP ID Number. The SEP ID<br />

number consists of one letter followed by four digits, and is a unique number that will help easily<br />

locate projects. The SEP ID number has been included on the Building Overview pages later in<br />

this report, and the Project Summary section of this report is organized by SEP ID number to<br />

allow easy location of a project.<br />

8.1 Lighting Projects<br />

The <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> includes a projection of the magnitude of lighting energy efficiency<br />

projects on the campus. The plan addresses interior fluorescent building lighting and interior<br />

HID lighting, as well as parking garage lighting and some outdoor lighting.<br />

8.1.1 Lighting Project 1. Interior Linear Fluorescent Lighting<br />

The standard project for fluorescent light fixtures is to use a state of the art lamp and ballast<br />

combination to limit each pair of fluorescent lamps and ballast to approximately 42 watts. This<br />

can be achieved through different combinations of lamps and ballasts according to each<br />

individual campus’s preference.<br />

Unless a campus expressed a specific preference, the default retrofit used for the analysis was<br />

to replace existing 32W T8 lamps and any remaining T12 lamps and their associated ballasts<br />

with 28W T8 lamps and premium efficiency ballasts with low ballast factors. The resulting<br />

fixtures typically operate at slightly lower light levels relative to the existing levels, but their<br />

improved color rendition has been shown to increase or maintain the perceived light level.<br />

<strong>Campus</strong>es can factor in color temperature, lamp life, lamp standardization, ballast<br />

standardization and a number of issues into their design.<br />

<strong>UC</strong> Santa Barbara, has chosen to install dimming ballasts in many applications instead of basic<br />

ballasts. This involves extra expense and operating complexity, but the potential for greater<br />

energy savings as well. The higher cost and savings are documented in the analysis.<br />

8.1.2 Lighting Project 2. Interior Lighting Controls<br />

Another standard lighting project is to install occupancy control in rooms that do not currently<br />

have occupancy control. The analysis accounts for the fact that most campuses already have<br />

occupancy sensors in some buildings, primarily in offices and classrooms. Some campuses<br />

have early generation occupancy sensors in classrooms, many of which have been disabled at<br />

the request of faculty and staff. Newer “dual technology” occupancy sensors, which detect both<br />

motion and heat, are much more reliable than the older technology, which was prone to turning<br />

off lights when occupants were not moving.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


Occupancy sensors are recommended in this report for all classrooms, offices, meeting rooms,<br />

restrooms, lecture halls, auditoriums, storage areas, some library spaces, and a portion of<br />

residential areas. They are not recommended in this report for laboratories, animal quarters,<br />

greenhouses, food service areas, museums, or medical service areas. On average, occupancy<br />

sensors are assumed to reduce lighting energy use by 25%, per utility incentive standards.<br />

Daylight harvesting has also been recommended at many campuses. Daylight harvesting<br />

should be applied to fixtures near skylights or windows, in areas that are overlit when sunlight is<br />

entering the building. Daylighting controls are assumed to apply to 10% of the fluorescent<br />

fixtures in classrooms, lecture halls, libraries, athletic areas, and common spaces, and 5% of<br />

fixtures in offices. For those fixtures, the daylighting controls are assumed to reduce energy use<br />

by 75% after occupancy sensor control.<br />

8.1.3 Lighting Project 3. Stairwell Lighting<br />

There is a significant energy savings potential from the lighting in stairwells. The standard<br />

project for these fixtures is to replace them with bi-level fluorescent fixtures. Bi-level fixtures are<br />

controlled by occupancy sensors that reduce lighting levels to a low standby mode when the<br />

space is unoccupied. The fixtures are specifically designed to meet fire code requirements for<br />

stairwells.<br />

It is recommended that <strong>UC</strong> replace every stairwell fixture in the system with this technology.<br />

<strong>UC</strong>LA has bi-level stairwell lighting in two buildings and intends to install more.<br />

8.1.4 Lighting Project 4. Interior High Bay Lighting<br />

Interior high intensity discharge (HID) fixtures are identified for conversion to fluorescent<br />

sources, generally T8 or T5 lamps, with occupancy sensor control. These are typically located<br />

in gymnasiums, sports facilities, swimming pools, and other high ceiling areas. Fluorescent has<br />

become the standard design for efficient lighting in high bay applications because of the<br />

relatively efficient output of the fluorescent sources, the higher output capacity of the T5 lamps,<br />

better color rendition, and the instant-on capability that permits occupancy control.<br />

8.1.5 Lighting Project 5. Parking Garage and Outdoor Pole Lighting<br />

Fluorescent lighting is a common conversion for parking garage lighting as well. A number of<br />

garages are lit with high pressure sodium (HPS) fluorescent fixtures, so the conversion to two or<br />

three lamp T8 fluorescent fixtures provides a significant energy savings and much improved<br />

color rendition. The lumen level is not necessarily maintained in these conversions, but<br />

occupant satisfaction is maintained. Some campuses are experimenting with bi-level garage<br />

lighting, controlled by occupancy sensors. This can be applied to HID as well as fluorescent<br />

light sources. Others have chosen to replace HID lighting with induction lighting, which is a<br />

more expensive technology that has much longer lamp life than any other technology.<br />

<strong>Campus</strong>es also have a significant amount of outdoor pole lighting, along sidewalks, in parking<br />

lots, and on the roofs of parking garages. Pole lighting is commonly LPS, HPS, or HID<br />

technology. LPS and HPS fixtures can be retrofitted with fluorescent technology, and metal<br />

halide fixtures with pulse start metal halide or fluorescent technology.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-2 December 31, 2008<br />

Newcomb | Anderson | McCormick


One campus, <strong>UC</strong> Santa Barbara, has chosen to replace existing HPS pole street lights with new<br />

LED technology. LED technology is currently quite expensive, but has great potential for energy<br />

savings.<br />

8.1.6 <strong>Campus</strong> Specific Lighting Survey Details<br />

<strong>UC</strong>LA campus buildings currently have 32W T8 lamps and standard electronic ballasts in nearly<br />

all linear fluorescent fixtures. The campus recently began using 28W T8 lamps as a standard<br />

replacement lamp. This report includes an analysis of retrofitting all 32W T8 fixtures in campus<br />

buildings with 28W T8 lamps and premium efficiency ballasts with low ballast factors. The<br />

analysis is based on the campus’s estimate that there are 600,000 T8 lamps on the campus. Of<br />

these, it is estimated that 10% have already been replaced with 28W T8 lamps.<br />

An alternative to replacing both the lamps and ballasts is to replace only the lamps. This will<br />

achieve a higher light level than the recommended project, but fewer energy savings. A savings<br />

and cost analysis of replacing only the lamps is included in the appendix.<br />

<strong>UC</strong>LA has installed bi-level stairwell fixtures in two buildings, and plans to replace 600 fixtures<br />

with the bi-level technology. A savings and cost analysis of this project is included.<br />

<strong>UC</strong>LA has occupancy control in most offices, classrooms, and restrooms on campus. It is<br />

recommended that additional occupancy sensors be installed to cover all offices, classrooms,<br />

and restrooms, in addition to meeting rooms, auditoriums, storage areas, and some library<br />

spaces. Based on a small sampling of campus buildings, it is estimated that 25% of <strong>UC</strong>LA<br />

buildings do not yet have occupancy sensors. The analysis assumes that occupancy control is<br />

installed on the remaining 25% of the lighting.<br />

According to the <strong>UC</strong>LA Housing staff, approximately 95% of lighting fixtures in Housing<br />

buildings have 32W T8 fluorescent lamps and standard electronic ballasts. In renovations,<br />

occupancy sensor controls are included in offices, but not in residential rooms. Renovations<br />

also include bi-level stairwell fixtures. Because the campus did not request an analysis, a<br />

lighting retrofit was not analyzed for Housing areas.<br />

There are a few interior areas on campus that are lit with HID fixtures, such as the Wooden<br />

<strong>Center</strong> and SAC/Men’s Gym, Pauley Pavilion, and the Ackerman Bookstore. Alternatives have<br />

been analyzed and recommended.<br />

All of the parking structures are lit with high pressure sodium (HPS) fixtures, with the exception<br />

of one floor of the Parking Structure 5, which has induction lighting. At the request of the<br />

campus, induction lighting was analyzed as a retrofit for the parking structures.<br />

At the direction of the campus, the lighting analysis of the medical facilities was not included.<br />

8.1.7 Other Projects & Technologies to Consider<br />

Potential Lighting Alternate 1. Integrated Classroom Lighting System<br />

The Integrated Classroom Lighting System (ICLS) has been developed and promoted by the<br />

California <strong>Energy</strong> Commission’s PIER Program. ICLS combines direct-indirect fluorescent<br />

fixtures with occupancy and daylight sensors, and plug-and-play interconnection cables, to<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-3 December 31, 2008<br />

Newcomb | Anderson | McCormick


provide a highly energy-efficient system that offers teachers more control and flexibility than<br />

conventional systems. ICLS has been demonstrated to demand an average of 0.6 to 0.85 watts<br />

per square foot, compared to more conventional systems, which typically draw between 0.8 and<br />

1.4 watts per square foot.<br />

PIER has found that the cost of installing ICLS in new construction projects is often equal to or<br />

lower than for conventional systems, because the system is available as an integrated<br />

package. New construction or renovation costs have been in the range of $3,000 to $4,000 per<br />

classroom. Installing ICLS as a retrofit is less cost-effective at current prices. <strong>UC</strong> Berkeley<br />

installed a few ICLS systems with an added dimming feature, at a cost of approximately $9,000<br />

per classroom. Although the cost of ICLS can be high relative to conventional systems, it is<br />

expected to drop to competitive levels within the next six years.<br />

Potential Lighting Alternate 2. LED Exterior and Interior Lights<br />

LED lighting is a technology with significant energy-saving potential. Although the current cost<br />

of LEDs is significantly higher than more conventional systems, costs are expected to drop<br />

significantly within the next few years. With their anticipated drop in cost and extremely high<br />

efficiency, LEDs should be seriously considered for applications at the <strong>UC</strong> campuses within the<br />

next six years.<br />

Historically, LEDs have been used for specialized lighting applications that required bright point<br />

sources of light, but products are quickly emerging to address more standard commercial and<br />

residential lighting needs. Every <strong>UC</strong> campus is now using LED exit signs in their buildings, and<br />

LED stop lights have also become standard. <strong>UC</strong> Santa Barbara is currently planning to replace<br />

nearly 400 high pressure sodium (HPS) pole fixtures with LED pole fixtures, a project that will<br />

save an estimated 40% of the lights’ energy use. <strong>UC</strong> Davis has installed bathroom vanity lights<br />

in two residence halls that use LED technology. The vanity light combines a one watt LED<br />

nightlight with an occupancy sensor controlling the overhead light.<br />

Other emerging LED technologies applicable to the <strong>UC</strong> system include exterior pathway lights,<br />

exterior wall packs, office and classroom task lighting, and cabinet undermount fixtures.<br />

Potential Lighting Alternate 3. Wireless Lighting Controls<br />

A promising technology for lighting control is the wireless mesh network fixture controller being<br />

developed by Adura Technologies of San Francisco. This is a technology which was developed<br />

at the <strong>UC</strong> Berkeley <strong>Center</strong> for the Built Environment. Several test sites have been installed in<br />

<strong>UC</strong> Berkeley buildings.<br />

The controller under development is a device to be installed in every light fixture in a ceiling grid.<br />

It can turn one or two ballasts in a fixture on or off. The controller measures power use by the<br />

fixture so it can report back on actual operations. Wireless sensors are installed in the building<br />

in appropriate locations to measure occupancy, ambient light, and so on.<br />

The wireless mesh network allows the controllers and sensors to communicate with each other.<br />

An internet portal in the building gives access to web based software which is used to configure<br />

the system. A variety of logic applications can be used to control fixtures individually or in<br />

groups. One set of ambient light sensors might be used to turn off or reduce output from all<br />

fixtures on a west face. Occupancy sensors can be programmed to control any set of fixtures.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-4 December 31, 2008<br />

Newcomb | Anderson | McCormick


The controllers themselves are programmed to respond to certain sensors as well as time<br />

control settings. Once programmed the mesh network can operate itself optimally with no<br />

external input. Or it can be used to control fixtures according to a web based signal, such as a<br />

demand response incident.<br />

Wireless mesh network lighting controllers promise extensive lighting control (time scheduling,<br />

occupancy sensor, daylight harvesting, and demand response) with power measurement and a<br />

relatively low first price. No wiring outside of the fixture is required, saving time and complexity.<br />

One feature not likely to be offered is dimming control, but with relatively low power fixtures, as<br />

well as individual ballast switching, this offers diminishing returns. This product is expected to<br />

be commercially available in one to two years.<br />

8.2 HVAC Projects<br />

8.2.1 Air Handler Project 1. Convert Constant Volume Air Handlers and Terminal Boxes to<br />

Variable Air Volume<br />

This project converts constant volume air handlers with terminal boxes to variable air volume.<br />

This project concentrates on larger air handlers which may be dual duct, multizone, reheat, or<br />

other constant volume configuration. These air handlers serve the zones through terminal<br />

boxes which may be mixing boxes or reheat boxes, often including pressure independent<br />

devices and sound attenuators.<br />

The project involves installing VFDs on the supply and return fans to allow the air flow to vary<br />

according to the load. In addition, a retrofit kit (damper, actuator, flow measuring station) is<br />

installed on each of the terminal boxes to convert it into a pressure independent variable volume<br />

device. This kit includes direct digital controls, which increases the cost but greatly increases<br />

the functionality. A large multizone air handler could fit in this category as well, with a retrofit kit<br />

installed in each zone duct and a two position actuator applied to the existing mixing dampers.<br />

The retrofit allows the zone temperatures to be properly controlled with less simultaneous<br />

heating and cooling energy use. In addition, reduced air flow requirements and lower operating<br />

static pressures will result in fan energy savings.<br />

In some cases, the air handlers have existing variable volume devices such as variable inlet<br />

vanes (VIV) or varicone flow devices, which are generally less efficient than modern VFDs, and<br />

may not be working optimally. In these cases, the project would replace the existing flow control<br />

device with a variable frequency drive, and the existing flow control is reflected in the project<br />

costs and savings.<br />

The savings are calculated for this project through a bin simulation adjusted for local weather,<br />

operating hours, building load characteristics, air handler flows and configuration, and<br />

temperature control strategies.<br />

The cost for implementing this project includes variable frequency drives for the supply and<br />

return fans, retrofit kits with DDC for each zone terminal box, and a control strategy to optimize<br />

the air flow and static pressure from the supply fan.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-5 December 31, 2008<br />

Newcomb | Anderson | McCormick


This project does not apply to air handlers that serve patient areas in the medical centers, as<br />

they are required by OSHPD to operate at constant volume all of the time. It does not apply to<br />

laboratory air handlers, where more elaborate air flow control devices are needed.<br />

8.2.2 Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume<br />

This project converts constant volume air handlers that do not use terminal boxes to variable air<br />

volume. This project concentrates on medium size air handlers which may be single zone, dual<br />

duct, multizone, reheat or other constant volume configuration. These air handlers do not serve<br />

zones through terminal boxes but through simpler reheat coils or mixing devices that do not<br />

have pressure independent controls. Large single zone air handlers without specific zone<br />

temperature control will fall into this category as well.<br />

The project involves installing VFDs on the supply and return fans to allow the air flow to vary<br />

according to the load. A retrofit kit is not installed at each zone temperature controller because<br />

there are not standardized boxes, the zones tend to be smaller and more numerous. Older<br />

construction tends to include plaster ceilings and other access constraints.<br />

In the case of a single zone air handler the VFD controls will be integrated into the current<br />

temperature controls to reduce the air flow to a minimum flow rate when the thermostat is not<br />

calling for full heating or cooling. For the other air handlers with zone temperature controls the<br />

retrofit includes DART wireless supply air temperature sensors or equivalent. This wireless<br />

control system allows the fan speed to be slowed to a minimum flow rate whenever the zone<br />

temperatures are satisfied.<br />

The retrofit allows the zone temperatures to be properly controlled with less simultaneous<br />

heating and cooling energy use. In addition, reduced air flow requirements and lower operating<br />

static pressures will result in fan energy savings.<br />

In some cases, the air handlers have existing variable volume devices such as variable inlet<br />

vanes (VIV) or varicone flow devices, which are generally less efficient than modern VFDs, and<br />

may not be working optimally. In these cases, the project would replace the existing flow control<br />

device with a variable frequency drive, and the existing flow control is reflected in the project<br />

costs and savings.<br />

The savings are calculated for this project through a bin simulation adjusted for local weather,<br />

operating hours, building load characteristics, air handler flows and configuration, and<br />

temperature control strategies.<br />

The cost for implementing this project includes variable frequency drives for the supply and<br />

return fans, wireless remote supply air temperature sensors for representative zone supply<br />

registers and a control strategy to optimize the air flow and static pressure from the supply fan.<br />

This project does not apply to air handlers that serve patient areas in the medical centers, as<br />

they are required by OSHPD to operate at constant volume all of the time. It does not apply to<br />

laboratory air handlers, where more elaborate air flow control devices are needed.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-6 December 31, 2008<br />

Newcomb | Anderson | McCormick


8.2.3 Air Handler Project 3. Demand Control Ventilation<br />

This project adds a carbon dioxide sensor to air handlers that serve areas with highly variable<br />

occupancies, such as lecture halls, theaters, gymnasiums. Measurement of the carbon dioxide<br />

level is used to reset the minimum outside air flow function of the outside air economizer<br />

according to occupancy requirements. The project includes a carbon dioxide sensor which is<br />

usually located inside the lecture hall or building space. This will result in the heating and<br />

cooling of less outside air when it is not needed for ventilation.<br />

The minimum flow of outside air into the air handler has typically been designed according to full<br />

occupancy of the space. For example, if there are 200 seats in a lecture hall the minimum<br />

outside air flow may have been determined by multiplying 15 cfm per person (or seat) times 200<br />

seats, or 3,000 cfm. The outside air economizer would be adjusted never to drop below this<br />

level.<br />

In the modified case the minimum outside air flow will be allowed to drop to lower levels as long<br />

as adequate ventilation is maintained for the number of people in the room, as indicated by the<br />

carbon dioxide levels. This is a standard control sequence required by Title 24 for new<br />

construction in high density spaces. Title 24 requires a minimum outside air flow rate of at least<br />

0.15 cfm/sf, regardless of occupancy. This level of ventilation removes contaminants not<br />

related to human occupants. This level of outside air supply is typically found in office areas, so<br />

carbon dioxide sensors do not offer significant energy savings potential for offices and other<br />

areas that are never densely occupied.<br />

The savings are calculated for this project through a bin simulation adjusted for local weather,<br />

operating hours, building load characteristics, air handler flows and configuration, and<br />

temperature control strategies.<br />

The cost for implementing this project includes a carbon dioxide sensor, which can be factory<br />

calibrated with no need for additional calibration during its service life, and integration into the<br />

economizer control sequence. The campus can choose to monitor and log the carbon dioxide<br />

levels.<br />

This project does not apply to air handlers serving office areas or other relatively low density<br />

areas. It does not apply to patient handling or laboratory air handlers where other outside air<br />

requirements exist.<br />

8.2.4 Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers<br />

This project adds a static pressure reset capability to existing VAV air handlers that do not have<br />

direct digital zone controls. The current design static pressure setpoint may be the appropriate<br />

pressure to operate at during hours of high air conditioning load, but it is not necessarily needed<br />

during other hours of operation. This project automatically resets the static pressure to a level<br />

that maintains comfort conditions but is typically lower than the original setpoint.<br />

There are two technologies commonly used to apply this control strategy. If the VAV system<br />

has direct digital controls at the room thermostats it is possible to use information from these<br />

thermostats to automatically reset the supply static pressure. It can be continuously reset so<br />

that a small portion of the VAV boxes are calling for full cooling. This would be an indicator that<br />

the pressure is operating at as low a point possible. For air handlers with DDC at the zones,<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-7 December 31, 2008<br />

Newcomb | Anderson | McCormick


this is a control sequence change which could be addressed in the commissioning project. The<br />

cost for reprogramming is relatively minor and so is not included in this section as a project.<br />

Other VAV air handlers do not have DDC at the zone level, and so do not provide this type of<br />

feedback. An alternative control strategy will be used to address this situation, SAV with InCITe<br />

offered by Federspiel Controls. This system uses air flow measurement at the air handler to<br />

quantify the building load and resets the supply air pressure accordingly. This control sequence<br />

has been installed in several <strong>UC</strong> buildings over the last several years. The cost and savings for<br />

applying SAV with InCITe to air handlers without DDC zone controls are included in this project.<br />

This approach to resetting supply pressure setpoints reduces fan energy use during part load<br />

conditions, while continuously meeting comfort requirements. The savings are calculated<br />

through a bin simulation adjusted for local weather, operating hours, building load<br />

characteristics, air handler flows and configurations and temperature control strategies.<br />

The cost of implementing this control involves either reprogramming the DDC system or<br />

installing the SAV with InCITe system. Either process requires fine tuning for optimal<br />

performance.<br />

This measure should apply to all existing VAV air handlers except in laboratories or other areas<br />

where static pressure control of the spaces is critical. It also applies to air handlers<br />

8.2.5 Air Handler Project 5. Reduce Air Handler Operating Hours<br />

This project shuts down air handlers during nights and weekends, when the areas they serve<br />

are not in use. This applies to classroom buildings, offices, lounges, gyms and libraries. These<br />

air handlers may operate continuously now in order to cool a server or telecom closet. Or they<br />

may operate to condition the building in case someone comes in to work during non-business<br />

hours.<br />

The building needs can typically be met by means other than running the air handlers<br />

continuously. In the case of the cooling needs of servers, the first choice would be to locate<br />

these servers in data centers where they receive cooling as needed, conditioned power, UPS<br />

backup, and continuous staffing. If there are servers or telecom equipment which cannot be<br />

relocated outside the building, they should be conditioned during nights and weekends by either<br />

split heat pumps, or dedicated chilled water coils where chilled water is continuously available.<br />

In the case where the comfort of faculty, staff or students is critical during non-standard hours,<br />

these requirements can be met in several ways with existing control systems. For example, the<br />

space temperature of the buildings can be monitored during the nights and weekends so when it<br />

drifts outside a given comfort zone (perhaps 65° to 80°F) the air handler can operate as long as<br />

necessary to reestablish temperature control. The air handler would then shut off again until the<br />

building drifts outside of the setback temperature control points again. Some faculty or staff<br />

could also be given phone in access to the building control system to allow them to request air<br />

handler operation for several hours at a time when they find the temperature unacceptable.<br />

The intention of this project is to provide a similar level of service to the University occupants<br />

that they currently enjoy, but at a lower energy use. The cost of this modification will be based<br />

on the number of spot cooling devices which may be necessary to serve specific building hot<br />

spots. The programming portion for the DDC system is not particularly expensive, as this is a<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-8 December 31, 2008<br />

Newcomb | Anderson | McCormick


standard control sequence. Temperature monitoring may be needed in older air handlers<br />

without direct digital control. Specific application notes are listed below.<br />

8.2.6 Air Handler Project 6. Convert Air Handlers to Direct Digital Control<br />

This measure involves replacing pneumatic controls on larger air handlers with direct digital<br />

controls. The intention is that no air handlers with supply fans of 10 hp or larger be left<br />

operating with pneumatic controls. The continued use of pneumatic controls creates problems<br />

in terms of calibration and drift, inadequate control sequences, inability to monitor and verify<br />

proper operation, incompatibility with demand response and inability to commission with lasting<br />

effect.<br />

8.2.7 Air Handler Project 7. Outside Air Ventilation Heat Recovery<br />

An energy recovery system is recommended in some facilities to capture heat or cooling from<br />

exhaust air and reuse some of it to precondition the make-up air before supplying it to the<br />

building. The type of heat exchangers or HVAC coils used to transfer this energy from the<br />

exhaust flow to the supply air can vary according to building design. Installation of a heat<br />

exchanger can result in significant energy savings in buildings that require a supply of 100%<br />

outside air. This was recommended for specific buildings in locations that experience significant<br />

variances in outdoor air temperature over the course of a year.<br />

8.2.8 Air Handler Project 8. Kitchen Hood VFD<br />

Demand ventilation controls are recommended for the university’s larger dining facilities’<br />

commercial kitchen hood exhaust fans (typically 3 hp and up). Standard exhaust hoods<br />

consume a significant amount of energy because they constantly run at maximum flow and<br />

require make-up air that must be heated or cooled. By installing VAV hoods controlled by<br />

infrared smoke sensors and temperature sensors, supply and exhaust fan speeds can be<br />

adjusted to match actual cooking activity under the hood, reducing the excess energy<br />

consumed in between meal preparation times. These controls have already been installed in<br />

several <strong>UC</strong> campus dining facilities with positive results that have led to further installation<br />

requests.<br />

8.2.9 Air Handler Project 9. Add Air Side Economizer<br />

This project adds air side economizer on air handlers. This project concentrates on larger air<br />

handlers which use minimum fresh air for ventilation and do not take advantages of outside air<br />

conditions for cooling (or for heating). During cooling mode, in the absence of an economizer<br />

return air that is generally warm is mixed with the minimum outside air and then cooled with the<br />

help of mechanical cooling to meet the supply air temperature requirements. The amount of<br />

fresh or outside air brought into space through air handlers is fixed and not varied.<br />

In the economizer mode, whenever outside conditions favor, outside air cooler than return air is<br />

brought into the space and, instead of being supplied back to the space, return air is exhausted.<br />

This is also known as free cooling, and significantly reduces cooling energy cost and system<br />

load. The same applies to heating mode where outside air warmer than return air is brought<br />

into the space to meet heating demand.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-9 December 31, 2008<br />

Newcomb | Anderson | McCormick


The project involves installing DDC dampers on outside air intake, return air and exhaust air to<br />

control percentage of outside air and return air in supply air to vary according to the load and<br />

outside conditions. In addition, a retrofit kit (damper actuator, flow measuring station, outside air<br />

temperature and humidity monitoring station, mixed air temperature sensor) is installed on each<br />

of the air handler. This kit includes direct digital controls, which increases the cost but greatly<br />

increases the functionality. Enthalpy changeover control strategy will be adapted to use outside<br />

air in the most economical way without use of energy required to dehumidify additional outside<br />

air. Enthalpy is a measure of the total heat in the air, which is calculated by measuring both the<br />

dry bulb temperature and the relative humidity. Outside air will be used for cooling when the<br />

enthalpy of outside air is lower than the enthalpy of return air. Outside air and return air<br />

dampers are modulated to admit enough outside air to minimize cooling energy use. When<br />

outside air enthalpy is greater than the return air enthalpy, minimum outside air required for<br />

ventilation is brought into the space.<br />

8.2.10 Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to<br />

Variable Air Volume<br />

The intention of this project is to convert laboratories to variable air volume systems and reduce<br />

the large outside air heating, cooling and fan power loads. Many existing labs are constant<br />

volume reheat systems, with a fixed air flow coming from the air handlers being reheated at the<br />

laboratory and exhausted through the constant volume hoods or room general exhaust. Most<br />

new laboratories utilize VAV air handlers and fume hoods. The intention of this project is to<br />

update the configuration of the existing labs so that they can operate as efficiently as the new<br />

labs. The <strong>UC</strong> EH&S Laboratory Safety Design Guide Second Edition September 2007 states<br />

“All laboratories should contain a fully integrated laboratory variable air volume (VAV)<br />

airflow/pressure control system to control room temperature, ventilation rate and room<br />

pressurization.”<br />

This project starts with a review of the air balance requirements of the facility. The air flow<br />

needs of each room are determined according to the function of the room, the number of hoods<br />

and the internal and external heat loads. This air balance may be significantly reduced from the<br />

existing design because of better understanding of actual loads or better design parameters.<br />

The minimum air changes typically needed in a laboratory are 6 air changes per hour for a room<br />

with a 10 foot ceiling, per the EH&S Design Guide. A given lab may need higher minimums,<br />

depending upon the density of hoods.<br />

The mechanical work includes converting the air handlers to VAV with the addition of VFDs to<br />

the supply fans. This may be appropriate for the exhaust fans as well, depending upon how<br />

they are ducted together. The hoods are converted to variable flow through the addition of an<br />

exhaust flow control valve and the sealing off of the sash bypass. If there are a small number of<br />

hoods in a larger room, these do not need to be converted to VAV, where the general exhaust<br />

requirements for the room are great enough that it makes no difference whether the air leaves<br />

through the hood or the general exhaust duct. The room supply air and general exhaust<br />

typically require new flow control valves or dampers as well to allow pressure control of each<br />

room. The exhaust fans may need stepping control and/or VFDs to maintain proper exhaust<br />

pressure in the duct and proper discharge velocity on the roof. The control systems should<br />

include supply temperature reset, utilizing either a DDC sequence or a controller such as DART,<br />

described above.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-10 December 31, 2008<br />

Newcomb | Anderson | McCormick


8.2.11 Laboratory Air Handler Project 2. Rebalance Variable Air Volume Laboratory (or<br />

Vivarium) Air Handlers<br />

A number of newer laboratories at the campuses were designed and built with VAV fume hoods<br />

and air handlers. Some of these have presented opportunity for efficiency improvement through<br />

rebalance of their systems to provide desired minimum air change rates (6 ACH). The current<br />

air change rate may be higher if the labs were designed for standard heat loads that did not end<br />

up being installed in most places. In some buildings air changes were provided for future hoods<br />

that were not installed.<br />

This project will readjust the air balance in the existing labs to meet the air flow requirements as<br />

the buildings are currently operating. Should the operations of a given laboratory change in the<br />

future, the air change rate can be adjusted just for that room through a similar process.<br />

The work involved in implementing this project is the recalculation of air change minimum air<br />

flows for each lab, based on the current building loads and 6 ACH minimum. Where the<br />

building has a DDC system, the new minimum air flows are set for the boxes and the operation<br />

is observed for stability and temperature control. Where there is no DDC system a more<br />

involved air balance will be necessary, probably manually setting the minimum flows on the<br />

zone supply boxes. The existing static pressure controllers should provide the reduced air flow<br />

and fan savings when the minimum air flows occur. The control systems should include supply<br />

temperature reset, utilizing either a DDC sequence or a controller such as DART, described<br />

above.<br />

8.2.12 Laboratory Air Handler Project 3. Reduce Minimum Air Change Requirements through<br />

Continuous Monitoring<br />

The first two Laboratory Air Handler Projects will reduce air change rates according to the needs<br />

of the individual rooms, with minimum flows set for 6 air changes per hour. This project will<br />

further reduce the minimum air flow setpoints in laboratory areas, with monitoring provided to<br />

raise the air change rate should a chemical spill be detected. The plan from the <strong>UC</strong> Irvine<br />

campus is to drop minimum air flow setpoints to 4 ACH during hours when the laboratories are<br />

normally occupied and to 2 ACH during other hours. This will further reduce the use of<br />

electricity to circulate the air, as well as heating and cooling requirements for the 100% outside<br />

air flow.<br />

The approach at <strong>UC</strong> Irvine is comprised of a chemical monitoring system that monitors the<br />

concentration of a number of common gases. The currently proposed system is an Aircuity<br />

system which uses a central monitoring station physically connected by sampling tubing to<br />

perhaps 20 rooms. The air quality in each laboratory is sampled periodically, typically once<br />

every 15 minutes. Detection of high gas concentrations caused by a spill would automatically<br />

increase the air change rate in the affected lab. A push button in each lab could be manually<br />

activated to do the same.<br />

Implementation of this measure requires approval of the campus Environmental and Health<br />

Safety department, which exists at <strong>UC</strong> Irvine. An interest in this project was expressed by<br />

<strong>UC</strong>LA.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-11 December 31, 2008<br />

Newcomb | Anderson | McCormick


8.2.13 <strong>Medical</strong> <strong>Center</strong> Air Handler Project 1. Optimization of Constant Volume Air Handlers<br />

In patient handling areas of medical centers, OSHPD typically requires constant volume air<br />

handlers to allow a precise air balance and maintenance of static pressure differences between<br />

rooms and hallways. This does not permit the use of VAV systems and their associated<br />

savings. Many of these systems are required to be 100% outside air as well. The most that can<br />

be done in a constant volume air handler is to ensure that the supply air temperature is set as<br />

high as possible while maintaining comfort, and ensuring that, if there is an outside air<br />

economizer, it is controlled according to the supply air temperature.<br />

This is a relatively easy programming effort in a DDC system. If a DDC system is not present<br />

some other optimizing approach is required. This could be a reset schedule based on outside<br />

air or other load indicator. It could also be done through a sampling of the supply air<br />

temperature in typical zones through a wireless mesh network of temperature sensors, as<br />

recommended in Air Handler Project 2, using the DART technology. It is not clear in which<br />

parts of a medical center this wireless technology could be employed.<br />

8.3 Monitoring Based Commissioning Projects<br />

8.3.1 Monitoring Based Commission for All SEP Buildings<br />

Monitoring Based Commissioning (MBCx) is recommended for all campus buildings of 50,000 sf<br />

and greater over the course of the next two utility funding cycles (six years). This process<br />

includes installing networked whole building meters on the buildings to automatically track<br />

electricity, steam, hot water, chilled water and/or natural gas use. It also includes a<br />

commissioning effort to review building operations, the functionality of controls, the<br />

appropriateness of sequences of operations, time scheduling, and numerous other building<br />

operation parameters. The process of identifying the SEP projects was a building survey, as<br />

opposed to an investment grade energy audit. The operational changes which would normally<br />

be identified in a detailed audit should be identified and resolved through the commissioning<br />

process.<br />

Where capital projects have been identified for buildings, for example, convert to variable air<br />

volume or install variable flow fume hoods, it is recommended that the commissioning process<br />

be integrated with the retrofit process, even though it is included separately in the project list.<br />

This is a hybrid MBCx process which will result in the most expedient change in building<br />

operations. In the case where no retrofit projects have been identified the commissioning<br />

process can be implemented at any time. It is possible that the commissioning process will<br />

result in the identification of additional retrofit measures which can be funded and installed in a<br />

later process.<br />

No commissioning project is recommended for buildings which received monitoring based<br />

commissioning in the 2004-2005 or 2006-2008 <strong>UC</strong> CSU IOU Partnership Program.<br />

The budgets for the MBCx projects were projected based on the 20060-2008 Partnership<br />

Program applications. The average cost for MBCx in Basic buildings was $0.61 per square foot.<br />

For Complex buildings the average cost is $1.22 per square foot.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-12 December 31, 2008<br />

Newcomb | Anderson | McCormick


The projected MBCx energy savings for the SEP buildings are determined relative to the 2006-<br />

2008 Partnership Program applications. There is a 70% multiplier applied to all savings<br />

projections because the buildings already in the MBCx program were selected specifically for<br />

their potential, while the proposed SEP buildings are only selected based on size.<br />

Basic building applications average electricity savings of 10% or 1.1 kWh/sf-yr, and gas savings<br />

of 15% or 0.15 th/sf-yr. <strong>Energy</strong> savings are projected to SEP buildings according to historical<br />

energy use of the building, if it is known. If historical energy use is not known, savings are<br />

projected on the basis of the building area. In both cases a 70% savings scaling factor is<br />

applied.<br />

Complex building applications average electricity savings of 9% or 2.7 kWh/sf-yr, and gas<br />

savings of 21% or 0.29 th/sf-yr. <strong>Energy</strong> savings are projected to SEP buildings according to<br />

historical energy use of the building, if it is known. If historical energy use is not known, savings<br />

are projected on the basis of the building area. In both cases a 70% savings scaling factor is<br />

applied.<br />

In addition, MBCx was recommended for all central plants which have not previously been<br />

commissioned through the Partnership program.<br />

8.4 Capital Program Projects<br />

8.4.1 New Construction and Renovation from Capital Program<br />

There is a significant opportunity to integrate energy efficiency with new construction and<br />

renovation of campus facilities. This is currently implemented through the Savings By Design<br />

process administered by the statewide investor owned utilities, as well as SMUD. It is<br />

anticipated that this program will be continued in the 2009-2014 utility portfolio. It is hoped that<br />

it can be integrated with the <strong>UC</strong> CSU IOU Partnership Program to become more effective.<br />

The anticipated program modifications include the following: encourage energy savings of<br />

greater than 25% relative to Title 24 to earn the maximum incentive levels of $0.25 per kWh and<br />

$1.00 per therm; use the Partnership minimum required campus contribution of 20% rather than<br />

the Savings By Design requirement of 50%; remove the $150,000 or $450,000 cap per project;<br />

consider some up front engineering funding.<br />

On the <strong>UC</strong> side the current process is hampered by severe competition for construction funds to<br />

implement the efficiency measures. Even when funds are set aside in the design budgets to<br />

meet the current <strong>UC</strong> goal of 20% below Title 24, efficiency measures are sometimes lost in<br />

“value engineering” during the construction process. There are typically not enough funds<br />

available to allow construction of buildings with the energy efficiency measures justified by life<br />

cycle costing.<br />

The opportunity to use the energy efficiency bond money in new construction and renovation<br />

projects would create significantly more opportunities for the installation of energy efficiency in<br />

these projects. The potential cost and savings is projected for this analysis, assuming each<br />

project could reduce energy use by approximately 30% below Title 24 and assuming that the<br />

total investment to achieve this performance would result in a simple payback period of 7 years.<br />

It is possible that this performance level can be achieved with a shorter payback, or that higher<br />

percentage savings can be achieved with this payback period.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-13 December 31, 2008<br />

Newcomb | Anderson | McCormick


The potential cost and savings for this measure is based on the planned construction for the<br />

campuses, as detailed in the 2007-08 to 2011-12 Capital Program document from the <strong>UC</strong>OP<br />

website. This includes construction and renovation projects on all campuses, independent of<br />

building funding source. The total project cost and savings were projected for individual<br />

projects, based on average performance numbers from existing <strong>UC</strong> buildings. A projected 30%<br />

savings in Basic buildings is 3.3 kWh/sf-yr and 0.3 th/sf-yr. A projected 30% savings in<br />

Complex buildings is 8.9 kWh/sf-yr and 0.4 th/sf-yr.<br />

These savings were projected to the building areas identified in the Capital Program document.<br />

Where building area was not directly identified, it was estimated from the project budget based<br />

on a projected construction cost of $611 per gross square foot. This is based on the average<br />

construction cost of the projects where stated ($917 per assignable square foot) and the<br />

observed ratio of gross square feet to assignable square feet from the <strong>UC</strong>OP comprehensive<br />

building list (1.5).<br />

The 2007-08 to 2011-12 Capital Program identifies hundreds of planned projects. Savings By<br />

Design projects for the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> were not calculated for projects which are<br />

currently on the <strong>UC</strong>OP list of Savings By Design projects underway through the current<br />

program. It was assumed that these projects are too advanced in the design process to switch<br />

to a deeper savings investment based on the proposed SEP process. In addition projects were<br />

not included on the SEP list if they are shown with an occupancy date of 2007-08 or 2008-09. It<br />

is assumed that these projects are too far along in design to allow significant changes. Once<br />

the new SEP program is underway, there may be an opportunity to include some of these<br />

projects, or to replace recommended measures that could not be supported in the original<br />

budget.<br />

Also excluded from the SEP project list are buildings listed for occupancy in 2014-15 or later,<br />

parking structures, and general infrastructure projects. Several buildings were added to the list<br />

by request of a campus.<br />

The projects listed include new buildings and renovation of existing buildings. In some cases<br />

the projects are not defined, but fall under general budgets, such as <strong>Campus</strong> Approved Projects<br />

Under $5 Million. The total list assumes that energy efficiency is an integral part of each of<br />

these projects.<br />

8.5 Deferred Maintenance and Capital Renewal Projects<br />

There is a significant budget spent on deferred maintenance and capital renewal projects each<br />

year. This is an investment in returning buildings and equipment to proper operating condition.<br />

This often includes roof replacement, window replacement and chiller or boiler replacement.<br />

This project comes from a different source than the capital project funding.<br />

Each campus produces a list based on a combination of priorities, although energy savings are<br />

typically not a factor. Although projects typically may save a nominal amount of energy, the<br />

replacement of this type of equipment typically has a long simple payback if calculated on<br />

energy savings only. Certainly some capital investment could be used to increase the efficiency<br />

of a project by improving the U value of a roof, increasing the performance of glazing or<br />

improving the efficiency of a chiller or boiler.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-14 December 31, 2008<br />

Newcomb | Anderson | McCormick


The budget that each campus has to spend on these projects is highly variable. It can be in the<br />

range of $10 million per year in a good year.<br />

It has been estimated that about 12% of these projects have an energy savings component. An<br />

increment of $0.25 to $0.5 million per year of deferred maintenance and capital renewal projects<br />

is used in the SEP project list. The campuses could elect to include one or more of these<br />

projects per year in their SEP commitment.<br />

8.6 <strong>Campus</strong> Wide Projects<br />

8.6.1 <strong>Campus</strong> Wide Project 1. Refrigerators<br />

It is recommended that all pre-2001 refrigerator units be replaced by <strong>Energy</strong> Star units. Old<br />

refrigerators can consume twice the electricity of a current <strong>Energy</strong> Star unit. Refrigerators are<br />

especially prevalent in universities where they are widely used in both academic and residential<br />

settings. Electricity and cost savings were calculated using the <strong>Energy</strong> Star calculator adapted<br />

for replacement of pre-2001 residential-type refrigerators on campuses.<br />

Refrigerators in Housing – The number of refrigerators in housing per campus were estimated<br />

based on the total number of apartment-type housing and suite-type housing available on each<br />

campus. Where available, we used the numbers of housing refrigerators to be replaced, as<br />

specified by the campus.<br />

Refrigerators on <strong>Campus</strong> – The number of refrigerators on campus was estimated based data<br />

provided by the <strong>UC</strong>B BETS database and prorated by the number of enrolled students at each<br />

campus. The BETS database provides an inventory of refrigerators that were purchased before<br />

2001.<br />

8.6.2 <strong>Campus</strong> Wide Project 2. Lab Freezers<br />

It is recommended that all pre-2001 lab freezers be replaced by energy efficient units.<br />

According to New Brunswick Science (NBS), current energy efficient units consume half the<br />

amount of electricity of the industry average. Due to this significant waste of energy, <strong>Energy</strong><br />

Star is currently developing standards for the industry. These units are especially prevalent in<br />

universities where they are widely used in research settings. Electricity and cost savings are<br />

calculated using data for ultra-low temperature (-86°F) upright lab freezers provided by NBS.<br />

While the <strong>Energy</strong> Star standards are currently being developed, this calculation can serve as an<br />

estimate for -20° to -30°F lab freezers as well by using an average industry installed cost<br />

of $7,000. The number of ultra-low temperature lab freezers on each campus was estimated<br />

based on data provided by the <strong>UC</strong>B BETS database and prorated by the number of enrolled<br />

students at each campus.<br />

8.6.3 <strong>Campus</strong> Wide Project 3. Server Virtualization<br />

Server Virtualization maximizes the utilization of servers by installing virtualization software on<br />

existing servers and allows the elimination of idling or under-utilized physical servers. <strong>Energy</strong><br />

savings potential was calculated based on deemed values provided by the SCE "Virtual<br />

Machine" calculator, version 6. The baseline server assumed the default values provided by the<br />

SCE calculator, whereas the proposed VM server used an average of two servers'<br />

specifications, "HP DL 585" and "Dell Blade 1955", servers that <strong>UC</strong> Berkeley are considering for<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-15 December 31, 2008<br />

Newcomb | Anderson | McCormick


future VM projects. The number of "virtualizable servers" per campus was estimated using data<br />

provided by the <strong>UC</strong> Berkeley IT Department and then prorated by the number of enrolled<br />

students per campus in Fall 2006. This includes both the decentralized servers across campus<br />

and servers that are in the data center servers. A ratio of ten baseline servers consolidated<br />

onto one virtual machine was used based on a conservative estimate from past partnership<br />

projects.<br />

Note that this project is based on the reduction in the number of servers operating and their<br />

local air conditioning load. Where a large air handler was operating continuously to cool a<br />

server, this measure was included in the HVAC projects.<br />

8.6.4 <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT<br />

Network computer power management software is recommended to power down computers<br />

that are on the network when they are not being used. Network PC power management<br />

software energy savings potential was calculated based on deemed values provided by the<br />

Verdiem PG&E work paper. Installed cost was estimated by the retail price of the software with<br />

installation, and with additional maintenance and support costs. For each campus, the number<br />

of computers on campus was estimated based on data provided by <strong>UC</strong> Berkeley's BETS<br />

database and prorated by the number of enrolled students per campus in Fall 2006. The BETS<br />

database showed the number of computers on campus older than 5 years. To be conservative,<br />

we estimated that half of these computers represented the number of managed, networkedcomputers<br />

on which power management software could be installed. However, we recommend<br />

that power management software be installed on all managed, networked-computers.<br />

CRT monitor to LCD monitor conversions were also recommended for each campus. Both the<br />

energy savings potential and cost were based on the <strong>Energy</strong> Star calculator for LCDs, adapted<br />

to represent conventional 17" CRT monitors to be replaced by <strong>Energy</strong> Star 17" LCDs. We<br />

recommend, however, that all CRTs be replaced with <strong>Energy</strong> Star LCDs to maximize energy<br />

savings.<br />

8.6.5 <strong>Campus</strong> Wide Project 5. Install Controllers on Vending Machines<br />

Vending machines and sliding-door coolers can easily be retrofit to use approximately 40<br />

percent less energy using inexpensive controllers. To examine the potential for this efficiency<br />

measure, counts of sliding door coolers and two types of vending machines, refrigerated and<br />

non-refrigerated, were collected from the <strong>UC</strong> campuses. Information about existing measures to<br />

reduce the energy consumption of these machines (e.g. requiring service providers to use<br />

<strong>Energy</strong> Star machines) was also gathered to avoid duplication of those efforts. For campuses<br />

that were not able to provide vending machine data, typical values determined for the rest of the<br />

<strong>UC</strong> system were applied.<br />

Based on the reported or estimated number of vending machines on each campus and the<br />

estimated annual energy usage of a machine, the existing energy consumption of all vending<br />

machines was calculated for each campus. For campuses that had not implemented controls or<br />

had done so only to a limited extent, full use of controllers on all campus vending machines and<br />

sliding-door coolers is recommended. The energy and cost savings associated with<br />

implementing this measure are calculated based on typical energy savings listed in the<br />

Database for <strong>Energy</strong> Efficient Resources (2005) and reported by equipment manufacturers.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-16 December 31, 2008<br />

Newcomb | Anderson | McCormick


8.7 Other Projects<br />

8.7.1 Swimming Pools<br />

The <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> includes energy savings and cost estimates for a number of energy<br />

efficiency measures for swimming pools. Four potential measures have been identified for<br />

campus pools and information is provided for each individual pool when appropriate.<br />

8.7.2 Pool Project 1. Variable Speed Drives and High Efficiency Motors for Filter Pumps<br />

Pool filter pumps are often continuously run at a constant flow rate regardless of usage and<br />

cleanliness standards. Codes typically require certain circulation rates when the pool is<br />

occupied. This measure includes installing a variable speed drive with control system and,<br />

when appropriate, replacing the motor with a premium efficiency motor. The energy savings<br />

calculations for this project assume that the pump will be slowed down to 50% of its normal<br />

speed during unoccupied hours (8 hours per day for most pools).<br />

8.7.3 Pool Project 2. Pool Covers<br />

Heated pools and spas lose approximately 70% of their energy to evaporation. Since<br />

evaporation is the major source of heat loss for pools, covering the pool when it is not in use is<br />

an effective manner of minimizing water and heat loss. This project includes standard insulating<br />

pool blankets, storage reels, and a power winder. <strong>Energy</strong> savings are modeled using the<br />

RETScreen4 software. The calculations assume that pool covers will be used eight hours per<br />

day.<br />

8.7.4 Pool Project 3. Solar Water Heating<br />

Solar water heating can significantly reduce pool operating cost by decreasing heating<br />

requirements. This measure is for a solar pool heating system of unglazed collectors with a total<br />

collecting area equal to 60% of the size of the area of the pool. <strong>Energy</strong> savings are modeled<br />

using RETScreen4 software. The calculations assume that pool covers are installed and used to<br />

minimize heat loss.<br />

8.7.5 Pool Project 4. Boiler Replacement<br />

This project replaces standard boilers for pool heating with dedicated high efficiency condensing<br />

boilers. The energy savings calculations for this measure assume 80% thermal efficiency for the<br />

currently installed boiler. Although some condensing boilers for pool heating claim up to 98%<br />

thermal efficiency, a conservative estimate of 90% thermal efficiency was used for the<br />

replacement boiler. The baseline energy consumption for this measure assumes that both pool<br />

covers and solar water heating are used. Information is not provided for pools that are heated<br />

using the central loop or a non-dedicated boiler.<br />

8.7.6 Domestic Solar Hot Water<br />

The use of solar hot water heating was explored as a possible measure to reduce energy use in<br />

campus residences. Total domestic hot water consumption was estimated for large residence<br />

halls and apartment buildings based on occupancy data collected from the campuses. Then,<br />

using data on the solar resource available on each campus and an assumed fraction of total<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-17 December 31, 2008<br />

Newcomb | Anderson | McCormick


water use to be provided, a solar hot water system was sized to meet demand. The cost of an<br />

appropriate system – active, closed-loop, with glazed flat-plate collectors – was then estimated<br />

to determine the cost effectiveness of this measure.<br />

Paybacks for domestic solar hot water were close to 80 years and therefore this measure was<br />

not recommended. However, in certain circumstances domestic solar hot water may prove more<br />

attractive. For example, where a solar hot water system has already been in use, adding or<br />

upgrading panels while preserving existing storage and pipes may offer a cost-effective<br />

measure. Also, access to state or federal tax credits and/or utility incentives – currently in pilot<br />

phase – could greatly increase the attractiveness of this measure.<br />

8.8 Custom Projects<br />

8.8.1 <strong>UC</strong>LA Custom Project 1. Boiler Replacement<br />

This project considers replacing existing old inefficient boilers with new energy efficient boilers.<br />

Existing boilers are old non-condensing boilers. Existing boilers do not capture latent heat from<br />

flue gases resulting in lower combustion efficiency. With condensing boilers 90-98% thermal<br />

efficiency is possible allowing significant natural gas savings. Conventional non condensing<br />

boilers are 70-80% efficient and require return water temperatures at comparatively higher<br />

temperatures. Condensing boilers have a specially designed heat exchanger which allows<br />

boiler to operate at lower return water temperatures and comparatively at higher delta T<br />

(difference between return water temperature and supply water temperature). Operating boiler<br />

at lower temperature reduces heat loss and standby losses.<br />

8.8.2 <strong>UC</strong>LA Custom Project 2. Chiller Replacement (SRLF, UNEX, Willshire <strong>Center</strong>)<br />

This project considers replacing existing old inefficient chillers with new energy efficient and<br />

environmental friendly chillers. Existing chillers are old and often require costly maintenance<br />

and downtime. Old chillers do not have good full load and part load efficiencies. In other words<br />

power (KW) used per cooling tons (ton) is comparatively high and therefore provides an<br />

opportunity for electric energy and demand savings. Chillers efficiencies are typically higher or<br />

are often designed for full load which occurs only for few hours per year. Rest of the time<br />

chillers see fewer loads or run at part load. Since cooling load is significantly driven by outside<br />

air and humidity, cooling needs also vary.<br />

Old chillers also use refrigerants containing Ozone-destroying Chlorofluorocarbons (CFC) which<br />

are no longer used in new chillers. New chillers use more environmental friendly<br />

Hydrochlroflurocarbon (HFC) refrigerants. Continuing use of old chillers with outdated<br />

technology and banned refrigerant causes wastage of energy and higher operating costs. Old<br />

chillers require refrigerants which are costly to obtain from a dwindling reclaimed supply. Also it<br />

becomes difficult, costlier and requires longer downtime to obtain parts for old chillers.<br />

Since building depends on local chillers for cooling needs and does not use chilled water from<br />

campus central plant, it is important to have efficient chillers to avoid hefty demand charges.<br />

New efficient chillers provides an opportunity to implement energy conservation measures such<br />

as chilled water supply reset, variable flow, condenser water reset etc without chiller penalty.<br />

With advanced chiller controls it is possible to limit demand and optimize chiller plant energy<br />

use. New chillers with advanced controls provide flexibility in plant operation and effectively use<br />

of plant equipment.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-18 December 31, 2008<br />

Newcomb | Anderson | McCormick


8.8.3 <strong>UC</strong>LA Custom Project 3. TOD Controls on Exhaust Fans<br />

This project considers installing Time of Day Controls (TOD) on Toilet Exhaust Fans. Existing<br />

toilet fans run continuously and are not controlled through building energy management system.<br />

Fan with higher horsepower impose significant operating costs, both electric energy use and<br />

demand charges. Therefore with the time of day controls, fan operating hours will be matched<br />

with building occupancy schedule and controlled through building energy management system.<br />

This will allow fan to run only when building is occupied and turn off automatically when building<br />

is unoccupied.<br />

If required occupancy sensors can be also integrated with fan so that whenever occupancy<br />

detected, fan will be turn on. Time of day control on fan will significantly reduce electric energy<br />

usage charges.<br />

8.8.4 <strong>UC</strong>LA Custom Project 4. Condenser Water Reset<br />

This project considers implementing condenser water reset control strategy for water cooled<br />

chillers through use of existing building direct digital controls (DDC). In condenser water reset<br />

control, water supplied to chiller condenser is varied according to outside air wet bulb<br />

temperature. With condenser water reset methodology, variable set point is used to control<br />

condenser water entering temperature. Every cooling tower can cool water up to certain limits<br />

depending on tower design and ambient wet bulb temperature. Since tower size is fixed, only<br />

driving factor is ambient wet bulb temperature. Cooling tower can cool water to temperatures<br />

equal to “wet bulb temperature + cooling tower approach”. Approach is defined as the difference<br />

between cooling tower leaving water temperature and ambient wet bulb temperature. In other<br />

words if ambient wet bulb temperature is 50°F with cooling tower design approach of 14°F,<br />

cooling tower can cool water to temperature of 64°F. Most of the Chiller Manufacturer’s<br />

literature indicates that a one-degree drop in condenser entering water temperature will reduce<br />

chiller energy consumption by two percent. Due to location of the building, ambient conditions<br />

favor use of condenser water reset and fan power usage due to condenser water reset will be<br />

comparatively less than the energy used for the chiller. An algorithm will set upper and lower<br />

limits on condenser water temperature to protect chiller from damage and by restricting set point<br />

to minimum approach, fan speed will not be increased in vain to achieve impossibly low<br />

temperatures. Without condenser water reset strategy, Cooling tower will run at fixed low<br />

temperature wasting fan energy during conditions when cooling tower cannot achieve the setpoint<br />

due to higher outside air wet-bulb temperature/ or due to high cooling loads on chiller.<br />

Condenser water reset strategy calculates overall system load, chiller characteristics (kW/ton),<br />

outside air wet bulb (enthalpy) and determines the best possible condenser water set-point<br />

under given circumstances for an efficient plant operation.<br />

To implement condenser water reset strategy, a wet bulb temperature sensor and humidity<br />

sensor will be installed in cooling tower yard. The existing DDC panel will be programmed to<br />

add an algorithm to reset (lower) condenser water entering temperature based on ambient wet<br />

bulb temperature. This algorithm will be used to control cooling tower fan VFD to maintain preset<br />

temperature at existing temperature sensors.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-19 December 31, 2008<br />

Newcomb | Anderson | McCormick


8.8.5 <strong>UC</strong>LA Custom Project 5. Install VFDs on Cooling Towers<br />

This project considers installing Variable Frequency drives (VFD) on Cooling Tower Fan. With<br />

VFD, fan speed is regulated to meet the required cooling needs. Since cooling tower is<br />

designed based on outside air wet bulb temperature, variation in wet bulb temperature affects<br />

tower performance. Highest wet bulb temperature for a particular location occurs only few hours<br />

per year; and it is not required to run tower fan at design speed (100%) for remaining hours. Fan<br />

speed can be reduced to meet cooling needs and therefore allowing significant electric energy<br />

and demand savings. VFD allows soft start and reduces wear and tear of fan belts, bearings.<br />

The power requirement of cooling tower fan varies as a cube of its speed. The VFD allows the<br />

cooling tower fan to operate at whatever speed is required to meet the cooing needs. Typically<br />

the fan runs at only 40 - 70% of design speed, thus saving 50% or more of the energy<br />

consumed by fixed speed system. Every time the actual wet bulb temperature is lower than the<br />

design wet bulb, an energy saving potential exists. Changes in the ambient wet bulb<br />

temperatures allow the fan speed to be regulated. Running fan at lower speed reduces energy<br />

consumed by the fan’s motor. The magnitude of this saving potential depends upon wet bulb<br />

temperature fluctuations. In addition to fan energy savings, running fan at lower speed reduces<br />

evaporation rate of treated water.<br />

8.8.6 <strong>UC</strong>LA Custom Project 6. Variable Speed Drives on Pumps<br />

This project considers installing Variable Frequency drives (VFD) on HVAC centrifugal pumps to<br />

vary pump speed by varying electrical frequency input to pump motor in relation to system<br />

heating and cooling load. This project focuses on pumps which run at fixed speed and do not<br />

alter flow of water in accordance with the HVAC system load requirements. In other words these<br />

pumps run at design speed (100%) independent of system characteristics wasting pumping<br />

energy and imposing electric demand charges on the campus. Generally pumps are designed<br />

to run at rated speed to meet the peak HVAC system demand which occurs only few hours per<br />

year. Rest of the time, due to the diversity in the system, the system does not require pump to<br />

deliver design flow (since the peak for each zone does not occur at the same time). Therefore<br />

system requires less flow than the design flow providing an opportunity to save pump energy by<br />

reducing pump speed to meet reduced system flow requirements. Speed reduction results in a<br />

more significant energy reduction. The larger the flow reduction from the designed operating<br />

point, the larger the energy savings. Since flow rate is directly proportional to pump speed and<br />

the differential pressure is directly proportional to the square of the pump speed, power usage is<br />

directly proportional to the cube of the pump speed. For example, reducing speed by 50%<br />

requires only 12.5% of the power needed at full speed.<br />

The project involves installing Variable Speed Drives on pumps and differential pressure<br />

transmitter in HVAC loop to control and monitor pump speed. Pump VFD and differential<br />

pressure transmitter will be connected to existing building energy management system.<br />

Also existing bypass valves in loop will be disabled for successful implementation of this ECM.<br />

This ECM assumes that existing pump motors are inverter duty type.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-20 December 31, 2008<br />

Newcomb | Anderson | McCormick


9. BUILDING OVERVIEW & PROJECTS<br />

The following pages provide an overview of the recommended projects and summary of<br />

information for the associated buildings. The section is organized sequentially according to the<br />

Building Key, and each contains the following information for each SEP Building.<br />

• Basic information about the building is contained in the header.<br />

• Annual historical energy use by utility for the FY 06/07 baseline, whether metered or<br />

extrapolated.<br />

• Monthly historical energy use by utility, where data is available.<br />

• Hourly load profiles by utility for one summer week and one winter week, where data is<br />

available.<br />

• Currently planned energy projects being implemented as part of the 2006-08<br />

<strong>UC</strong>/CSU/IOU Partnership cycle, and their associated savings as approved for the<br />

incentive application.<br />

• Projects identified by the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong>, and the projected savings and<br />

economics. The SEP ID Number is a key reference to find the applicable Project<br />

Summary.<br />

• Benchmarking information, calculating the baseline and projected energy uses after<br />

implementation of currently planned energy projects and after implementation of the<br />

projects identified in this SEP.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 9-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

834,200<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

PERLOFF HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4202<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

39,000<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1952<br />

Basic Gross Area (sf): 65,909<br />

Building Type: BASIC<br />

Primary Asset Type: Laboratory<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

PERLOFF HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4202<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

D1051 CAV to VAV - AHU 1, 2, 5W and 5E & Add Economizer<br />

D3003 Monitoring Based Commissioning<br />

LOS ANGELES<br />

1952<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

104,141 4.0 304 0 145,777 $20,070<br />

50,750 6.0 0 6,920 0 $8,266<br />

Basic Gross Area (sf): 65,909<br />

Building Type: BASIC<br />

Primary Asset Type: Laboratory<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$231,886 $56,783 $175,103 8.7<br />

Committed Tier:<br />

Backup<br />

$55,723 $19,100 $36,623 4.4<br />

Totals 154,891 10.0 304 6,920 145,777 $28,336 $287,609 $75,883 $211,726 7.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

834,200 39,000 12.7 0.6<br />

188.8<br />

834,200 39,000 12.7 0.6<br />

188.8<br />

562,687 28,280 8.5 0.4<br />

130.3<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

31.0%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

3,872,200<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

YOUNG LIBRY<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4203<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

181,200<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1964<br />

Basic Gross Area (sf): 305,919<br />

Building Type: BASIC<br />

Primary Asset Type: Telcom<br />

Secondary Asset Type: Library<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1048 SAF-1 & 2 SP Reset<br />

D1049 SAF-3 to 8 CAV to VAV<br />

D1050 SAF 9 CAV to VAV<br />

D3004 Monitoring Based Commissioning<br />

YOUNG LIBRY<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4203<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

D3005 SBD, New/Renov - Young Research Library Renovation<br />

LOS ANGELES<br />

1964<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

141,010 1.0 2,791 0 69,598 $32,145<br />

513,097 63.0 4,419 0 199,569 $82,063<br />

46,394 2.0 410 0 40,684 $8,912<br />

235,558 27.0 0 32,121 0 $38,367<br />

302,198 34.0 0 28,314 0 $42,141<br />

Basic Gross Area (sf): 305,919<br />

Building Type: BASIC<br />

Primary Asset Type: Telcom<br />

Secondary Asset Type: Library<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$61,824 $82,093 $12,365 0.4<br />

Committed Tier:<br />

Backup<br />

$260,501 $216,698 $52,100 0.6<br />

Committed Tier:<br />

Backup<br />

$33,239 $24,071 $9,168 1.0<br />

Committed Tier:<br />

Backup<br />

$258,643 $88,655 $169,988 4.4<br />

Committed Tier:<br />

Backup<br />

$442,353 $100,842 $341,511 8.1<br />

Totals 1,238,257 127.0 7,620 60,435 309,851 $203,628 $1,056,560 $512,359 $585,132 2.9<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

3,872,200 181,200 12.7 0.6<br />

188.8<br />

3,872,200 181,200 12.7 0.6<br />

188.8<br />

2,386,062 25,515 7.8 0.1<br />

88.2<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

53.3%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

4,611,100<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

GEOLOGY<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4228A<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

215,800<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1952<br />

Basic Gross Area (sf): 182,149<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1054 S-1, 5, 9, 10 to 12<br />

D1055 S-1(Geophysics)<br />

D1056 Aircuity<br />

D3008 Monitoring Based Commissioning<br />

GEOLOGY<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4228A<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1952<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

181,337 5.0 2,026 0 80,248 $32,167<br />

71,548 2.0 1,817 0 54,628 $19,735<br />

7,207 1.0 0 0 0 $634<br />

344,262 39.0 0 36,976 0 $50,599<br />

Basic Gross Area (sf): 182,149<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$176,117 $84,253 $91,864 2.9<br />

Committed Tier:<br />

Backup<br />

$45,741 $50,373 $9,148 0.5<br />

Committed Tier:<br />

Backup<br />

$48,656 $1,730 $46,926 74.0<br />

Committed Tier:<br />

Backup<br />

$307,998 $119,599 $188,399 3.7<br />

Totals 604,354 47.0 3,843 36,976 134,876 $103,136 $578,512 $255,955 $336,337 3.3<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

4,611,100 215,800 25.3 1.2<br />

377.7<br />

4,611,100 215,800 25.3 1.2<br />

377.7<br />

3,898,845 130,787 21.4 0.7<br />

291.0<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

23.0%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

6,784,350<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

MOLECULR SCI<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4228C<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

423,400<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1993<br />

Basic Gross Area (sf): 178,666<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


2006-2008 Partnership Projects<br />

<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

MOLECULR SCI<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4228C<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

<strong>Plan</strong>ned Electric <strong>Plan</strong>ned Gas<br />

Savings<br />

Savings<br />

Project Description<br />

(kWh/yr)<br />

(th/yr)<br />

Upgrade vent and controls and install ZP sensors on 194 fume hoods 0 167,232<br />

Upgrade vent and controls and install ZP sensors on 26 fume hoods 0 22,410<br />

D1015 AHU - 5 VIV to VAV & SP Reset<br />

D1016 AHU 1, 2, 3, 4 & 6 Aircuity<br />

D3009 Monitoring Based Commissioning<br />

1993<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

10,294 0.0 16 0 1,857 $1,111<br />

2,629,450 68.0 13,688 0 104,815 $313,196<br />

337,679 38.0 0 36,269 0 $49,632<br />

Basic Gross Area (sf): 178,666<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Cost<br />

($)<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$35,195 $3,027 $32,168 28.9<br />

Committed Tier:<br />

Backup<br />

$1,155,824 $822,292 $333,532 1.1<br />

Committed Tier:<br />

Backup<br />

$302,109 $117,312 $184,797 3.7<br />

Totals 2,977,423 106.0 13,704 36,269 106,672 $363,939 $1,493,128 $942,631 $550,497 1.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

6,784,350 423,400 38.0 2.4<br />

625.8<br />

6,784,350 233,758 38.0 1.3<br />

519.6<br />

3,721,589 26,189 20.8 0.1<br />

227.9<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

17.0%<br />

56.1%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,629,200<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

WOODEN/PS4<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4235<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

123,000<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1983<br />

Basic Gross Area (sf): 707,839<br />

Building Type: BASIC<br />

Primary Asset Type: Athletics<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1028 AHU 1 VIV to VAV<br />

D1029 AHU 3 VIV to VAV & SP Reset<br />

D1030 CAV to VAV<br />

D1031 AHU 1 (Mcquay) SP reset<br />

D1032 AHU 1 Pace) SP reset<br />

D1033 AHU 2 Pace) SP reset<br />

D1034 AHU 4 CAV to VAV & DCV<br />

D3011 Monitoring Based Commissioning<br />

WOODEN/PS4<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4235<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1983<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

22,785 0.0 183 0 10,374 $3,667<br />

58,384 1.0 434 0 24,388 $9,066<br />

236,777 57.0 -176 0 8,663 $20,419<br />

27,011 0.0 452 0 16,783 $5,922<br />

18,432 0.0 279 0 10,943 $3,847<br />

20,078 0.0 331 0 12,223 $4,359<br />

210,437 50.0 -282 0 2,584 $17,134<br />

159,945 18.0 0 21,811 0 $26,052<br />

D3203 Replace high pressure sodium fixtures with induction fixtures and install photocell control where appropriate<br />

397,003 45.0 0 0 0 $34,936<br />

Basic Gross Area (sf): 707,839<br />

Building Type: BASIC<br />

Primary Asset Type: Athletics<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$36,733 $9,748 $26,985 7.4<br />

Committed Tier:<br />

Backup<br />

$65,921 $24,120 $41,801 4.6<br />

Committed Tier:<br />

Backup<br />

$125,784 $56,290 $69,494 3.4<br />

Committed Tier:<br />

Backup<br />

$47,848 $15,355 $32,493 5.5<br />

Committed Tier:<br />

Backup<br />

$2,784 $10,012 $557 0.1<br />

Committed Tier:<br />

Backup<br />

$2,784 $11,303 $557 0.1<br />

Committed Tier:<br />

Backup<br />

$62,008 $47,476 $14,532 0.8<br />

Committed Tier:<br />

Backup<br />

$175,619 $60,198 $115,421 4.4<br />

Committed Tier:<br />

Backup<br />

$286,838 $95,281 $191,557 5.5<br />

Totals 1,150,852 171.0 1,221 21,811 85,958 $125,403 $806,319 $329,783 $493,397 3.9<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,629,200 123,000 3.7 0.2<br />

55.4<br />

2,629,200 123,000 3.7 0.2<br />

55.4<br />

1,409,582 85,927 2.0 0.1<br />

32.5<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

41.3%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

7,445,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

ENGR BLDG 4<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4256A<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

348,400<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1990<br />

Basic Gross Area (sf): 294,124<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1062 ACS - 1 to 5 - SP Reset<br />

D1063 ACS 8 (AHU-3) - Aircruity<br />

D1064 CF - 1 to 22 - VIV to VAV<br />

D1065 ACS 9 - CAV to VAV<br />

D3013 Monitoring Based Commissioning<br />

ENGR BLDG 4<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4256A<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1990<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

283,121 3.0 3,127 0 155,143 $51,915<br />

242,891 22.0 3,191 0 162,129 $49,169<br />

743,261 143.0 0 0 601,695 $103,530<br />

25,138 4.0 815 0 39,788 $9,208<br />

555,894 64.0 0 59,707 0 $81,705<br />

Basic Gross Area (sf): 294,124<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$126,983 $136,824 $25,397 0.5<br />

Committed Tier:<br />

Backup<br />

$1,551,693 $129,310 $1,422,383 28.9<br />

Committed Tier:<br />

Backup<br />

$755,712 $293,908 $461,804 4.5<br />

Committed Tier:<br />

Backup<br />

$32,243 $23,860 $8,383 0.9<br />

Committed Tier:<br />

Backup<br />

$497,340 $193,122 $304,218 3.7<br />

Totals 1,850,305 236.0 7,133 59,707 958,755 $295,529 $2,963,971 $777,024 $2,222,185 7.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

7,445,800 348,400 25.3 1.2<br />

377.7<br />

7,445,800 348,400 25.3 1.2<br />

377.7<br />

4,828,491 199,531 16.4 0.7<br />

235.9<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

37.5%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,394,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

FACMGMT BLDG<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4260<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

112,100<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1993<br />

Basic Gross Area (sf): 189,197<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Storage<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1002 AHU 1 & 2 - SP Reset<br />

D3014 Monitoring Based Commissioning<br />

FACMGMT BLDG<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4260<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1993<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

40,882 0.0 644 0 26,469 $8,811<br />

145,682 17.0 0 19,866 0 $23,729<br />

Basic Gross Area (sf): 189,197<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Storage<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$46,233 $22,944 $23,289 2.6<br />

Committed Tier:<br />

Backup<br />

$159,960 $54,830 $105,130 4.4<br />

Totals 186,564 17.0 644 19,866 26,469 $32,540 $206,192 $77,774 $128,419 3.9<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,394,800 112,100 12.7 0.6<br />

188.9<br />

2,394,800 112,100 12.7 0.6<br />

188.9<br />

2,187,061 84,184 11.6 0.4<br />

162.9<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

13.8%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

724,300<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

TIVERTON HSE<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

LOS ANGELES<br />

Building Key: 04C4265<br />

Funding Source: HOUSING<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

33,900<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1993<br />

Basic Gross Area (sf): 121,634<br />

Building Type: BASIC<br />

Primary Asset Type: Residential<br />

Secondary Asset Type: Commons<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D3015 Monitoring Based Commissioning<br />

D6010 CT VFDs<br />

TIVERTON HSE<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4265<br />

Funding Source: HOUSING<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1993<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

44,062 5.0 0 6,009 0 $7,177<br />

24,661 4.0 0 0 0 $2,170<br />

Basic Gross Area (sf): 121,634<br />

Building Type: BASIC<br />

Primary Asset Type: Residential<br />

Secondary Asset Type: Commons<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$48,381 $16,584 $31,797 4.4<br />

Committed Tier:<br />

Backup<br />

$10,928 $5,919 $5,009 2.3<br />

Totals 68,723 9.0 0 6,009 0 $9,347 $59,309 $22,503 $36,806 3.9<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

724,300 33,900 6.0 0.3<br />

88.8<br />

724,300 33,900 6.0 0.3<br />

88.8<br />

655,577 27,891 5.4 0.2<br />

78.1<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

12.1%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

3,989,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

WILSHIRE CTR<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4270<br />

Funding Source: OTHER<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

186,700<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1981<br />

Basic Gross Area (sf): 455,912<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Retail<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1027 AHU 1 & 2 SP Reset<br />

D3016 Monitoring Based Commissioning<br />

D6006 Replace Chiller<br />

WILSHIRE CTR<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4270<br />

Funding Source: OTHER<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1981<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

736,319 171.0 0 0 0 $64,796<br />

242,710 28.0 0 33,097 0 $39,533<br />

304,707 98.0 0 0 0 $26,814<br />

Basic Gross Area (sf): 455,912<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Retail<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$1,729,872 $176,717 $1,553,155 24.0<br />

Committed Tier:<br />

Backup<br />

$266,496 $91,347 $175,149 4.4<br />

Committed Tier:<br />

Backup<br />

$847,454 $73,130 $774,324 28.9<br />

Totals 1,283,736 297.0 0 33,097 0 $131,143 $2,843,822 $341,194 $2,502,628 19.1<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

3,989,800 186,700 8.8 0.4<br />

130.6<br />

3,989,800 186,700 8.8 0.4<br />

130.6<br />

2,706,064 153,603 5.9 0.3<br />

94.5<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

27.6%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

1,359,700<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

CANYON POINT<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

LOS ANGELES<br />

Building Key: 04C4302A<br />

Funding Source: HOUSING<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

63,600<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1991<br />

Basic Gross Area (sf): 107,419<br />

Building Type: BASIC<br />

Primary Asset Type: Residential<br />

Secondary Asset Type: Commons<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D3019 Monitoring Based Commissioning<br />

D6001 Replace Boiler<br />

CANYON POINT<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4302A<br />

Funding Source: HOUSING<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1991<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

82,713 9.0 0 11,279 0 $13,472<br />

0 0.0 0 2,494 0 $1,370<br />

Basic Gross Area (sf): 107,419<br />

Building Type: BASIC<br />

Primary Asset Type: Residential<br />

Secondary Asset Type: Commons<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$90,818 $31,130 $59,688 4.4<br />

Committed Tier:<br />

Backup<br />

$78,323 $2,494 $75,829 55.4<br />

Totals 82,713 9.0 0 13,773 0 $14,842 $169,140 $33,624 $135,517 9.1<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

1,359,700 63,600 12.7 0.6<br />

188.8<br />

1,359,700 63,600 12.7 0.6<br />

188.8<br />

1,276,987 49,827 11.9 0.5<br />

168.1<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

11.0%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

1,823,500<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

COVEL COMMON<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

LOS ANGELES<br />

Building Key: 04C4302D<br />

Funding Source: HOUSING<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

85,300<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1992<br />

Basic Gross Area (sf): 144,067<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Food Service<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

COVEL COMMON<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4302D<br />

Funding Source: HOUSING<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

D1006 DAC 1 to 4 & DAHU-1 - VIV to VAV SP Reset<br />

D3020 Monitoring Based Commissioning<br />

D6002 Replace Boiler<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1992<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

287,180 2.0 0 16,383 0 $34,268<br />

110,932 13.0 0 15,127 0 $18,069<br />

0 0.0 0 4,987 0 $2,738<br />

Basic Gross Area (sf): 144,067<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Food Service<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$105,987 $85,306 $21,197 0.6<br />

Committed Tier:<br />

Backup<br />

$121,803 $41,751 $80,052 4.4<br />

Committed Tier:<br />

Backup<br />

$156,646 $4,987 $151,659 55.4<br />

Totals 398,112 15.0 0 36,497 0 $55,075 $384,435 $132,044 $252,908 4.6<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

1,823,500 85,300 12.7 0.6<br />

188.8<br />

1,823,500 85,300 12.7 0.6<br />

188.8<br />

1,425,388 48,803 9.9 0.3<br />

135.2<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

28.4%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

896,400<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

KERCKHOFF<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

LOS ANGELES<br />

Building Key: 04C4310<br />

Funding Source: HOUSING<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

41,900<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1930<br />

Basic Gross Area (sf): 70,820<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Commons<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1007 AHU 1 SP Reset<br />

D1008 CAV to VAV - AHU 2<br />

D3021 Monitoring Based Commissioning<br />

KERCKHOFF<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4310<br />

Funding Source: HOUSING<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1930<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

31,578 0.0 451 0 18,206 $6,409<br />

29,236 1.0 226 0 12,178 $4,585<br />

54,531 6.0 0 7,436 0 $8,882<br />

Basic Gross Area (sf): 70,820<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Commons<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$2,784 $16,712 $557 0.1<br />

Committed Tier:<br />

Backup<br />

$28,262 $12,180 $16,082 3.5<br />

Committed Tier:<br />

Backup<br />

$59,875 $20,523 $39,352 4.4<br />

Totals 115,345 7.0 677 7,436 30,384 $19,876 $90,921 $49,415 $55,991 2.8<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

896,400 41,900 12.7 0.6<br />

188.8<br />

896,400 41,900 12.7 0.6<br />

188.8<br />

756,748 26,002 10.7 0.4<br />

146.1<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

22.6%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

3,169,500<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

GONDA CENTER<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4315<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

148,300<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1998<br />

Basic Gross Area (sf): 125,202<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1005 CV Rebalance<br />

D3022 Monitoring Based Commissioning<br />

GONDA CENTER<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4315<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1998<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

211,550 24.0 1,194 0 59,189 $28,923<br />

236,632 27.0 0 25,416 0 $34,780<br />

Basic Gross Area (sf): 125,202<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$86,096 $77,061 $17,219 0.6<br />

Committed Tier:<br />

Backup<br />

$211,707 $82,208 $129,499 3.7<br />

Totals 448,182 51.0 1,194 25,416 59,189 $63,703 $297,804 $159,269 $146,718 2.3<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

3,169,500 148,300 25.3 1.2<br />

377.6<br />

3,169,500 148,300 25.3 1.2<br />

377.6<br />

2,673,967 107,959 21.4 0.9<br />

304.9<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

19.3%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

3,486,400<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

LAW<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4317<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

163,100<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1951<br />

Basic Gross Area (sf): 275,439<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1043 SF 1 & 2 SP Reset<br />

D1044 SF 3 & 7 VIV to VAV & SP Reset<br />

D1045 S-4 CAV to VAV<br />

D1046 S-5 & 6 CAV to VAV<br />

D1047 S-8 CAV to VAV<br />

D3023 Monitoring Based Commissioning<br />

LAW<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4317<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1951<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

47,789 0.0 393 0 6,684 $6,787<br />

139,406 1.0 526 0 27,871 $16,922<br />

16,081 1.0 449 0 38,223 $6,302<br />

115,646 4.0 834 0 73,910 $19,439<br />

27,915 1.0 200 0 12,057 $4,319<br />

212,088 24.0 0 28,921 0 $34,545<br />

Basic Gross Area (sf): 275,439<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$46,817 $17,665 $29,152 4.3<br />

Committed Tier:<br />

Backup<br />

$96,194 $45,384 $50,810 3.0<br />

Committed Tier:<br />

Backup<br />

$30,085 $16,811 $13,274 2.1<br />

Committed Tier:<br />

Backup<br />

$81,053 $52,371 $28,682 1.5<br />

Committed Tier:<br />

Backup<br />

$30,759 $11,515 $19,244 4.5<br />

Committed Tier:<br />

Backup<br />

$232,872 $79,822 $153,050 4.4<br />

Totals 558,925 31.0 2,402 28,921 158,745 $88,314 $517,781 $223,568 $294,212 3.3<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

3,486,400 163,100 12.7 0.6<br />

188.8<br />

3,486,400 163,100 12.7 0.6<br />

188.8<br />

2,800,479 104,154 10.2 0.4<br />

141.9<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

24.8%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,111,900<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

POWELL LIB<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4318A<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

98,800<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1930<br />

Basic Gross Area (sf): 166,846<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1017 S-1 CAV to VAV<br />

D1018 AH 1 to 4, 17 & 37 CAV to VAV with DCV<br />

D1019 AH-19 CAV to VAV<br />

D1020 AH 18, 38 & 39 CAV to VAV<br />

D1021 AH 20 CAV to VAV<br />

D3024 Monitoring Based Commissioning<br />

POWELL LIB<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4318A<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1930<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

7,870 1.0 143 0 7,191 $1,933<br />

44,410 10.0 -23 0 4,351 $4,057<br />

79,947 7.0 532 0 38,959 $12,425<br />

23,523 5.0 -3 0 2,409 $2,206<br />

45,021 4.0 396 0 32,750 $8,211<br />

128,471 15.0 0 17,519 0 $20,925<br />

Basic Gross Area (sf): 166,846<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$36,901 $5,057 $31,844 16.5<br />

Committed Tier:<br />

Backup<br />

$48,385 $11,206 $37,179 9.2<br />

Committed Tier:<br />

Backup<br />

$46,563 $33,317 $13,246 1.1<br />

Committed Tier:<br />

Backup<br />

$19,798 $6,071 $13,727 6.2<br />

Committed Tier:<br />

Backup<br />

$44,343 $22,043 $22,300 2.7<br />

Committed Tier:<br />

Backup<br />

$141,062 $48,352 $92,710 4.4<br />

Totals 329,242 42.0 1,045 17,519 85,660 $49,759 $337,051 $126,046 $211,006 4.2<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,111,900 98,800 12.7 0.6<br />

188.8<br />

2,111,900 98,800 12.7 0.6<br />

188.8<br />

1,714,130 68,219 10.3 0.4<br />

146.1<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

22.6%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

5,432,900<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

LIFE SCIENCE<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4320<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

254,200<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1954<br />

Basic Gross Area (sf): 214,613<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Laboratory<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1009 Vivarium - CV Rebalance<br />

D1010 SF - 4 & 5 - Aircuity<br />

D3025 Monitoring Based Commissioning<br />

LIFE SCIENCE<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4320<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1954<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

0 0.0 725 0 43,530 $6,739<br />

350,121 32.0 5,889 0 299,188 $82,105<br />

405,619 46.0 0 43,566 0 $59,617<br />

Basic Gross Area (sf): 214,613<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Laboratory<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$58,784 $17,420 $41,364 6.1<br />

Committed Tier:<br />

Backup<br />

$2,503,946 $215,086 $2,288,860 27.9<br />

Committed Tier:<br />

Backup<br />

$362,894 $140,915 $221,979 3.7<br />

Totals 755,740 78.0 6,614 43,566 342,718 $148,461 $2,925,624 $373,421 $2,552,203 17.2<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

5,432,900 254,200 25.3 1.2<br />

377.6<br />

5,432,900 254,200 25.3 1.2<br />

377.6<br />

4,402,986 127,959 20.5 0.6<br />

269.7<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

28.6%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,387,400<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

DORIS STEIN<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4325<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

111,700<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1989<br />

Basic Gross Area (sf): 94,309<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Hospitals<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1061 AHU - 1, 2 & 3 VIV to VAV SP Reset<br />

D3026 Monitoring Based Commissioning<br />

DORIS STEIN<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4325<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1989<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

159,060 1.0 860 0 60,756 $22,569<br />

178,244 20.0 0 19,145 0 $26,198<br />

Basic Gross Area (sf): 94,309<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Hospitals<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$117,329 $60,590 $56,739 2.5<br />

Committed Tier:<br />

Backup<br />

$159,469 $61,924 $97,545 3.7<br />

Totals 337,304 21.0 860 19,145 60,756 $48,768 $276,798 $122,514 $154,284 3.2<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,387,400 111,700 25.3 1.2<br />

377.6<br />

2,387,400 111,700 25.3 1.2<br />

377.6<br />

2,001,491 81,805 21.2 0.9<br />

304.0<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

19.5%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

3,558,400<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

PUBLIC HLTH<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4331<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

166,500<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1968<br />

Basic Gross Area (sf): 140,563<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Office Support<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1041 CAV to VAV - AHU S-2 to S-9<br />

D1042 CV Rebalance - S-1<br />

D3027 Monitoring Based Commissioning<br />

PUBLIC HLTH<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4331<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1968<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

148,425 12.0 1,184 0 59,890 $23,358<br />

0 0.0 881 0 52,901 $8,190<br />

265,664 30.0 0 28,534 0 $39,047<br />

Basic Gross Area (sf): 140,563<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Office Support<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$219,224 $61,921 $157,303 6.7<br />

Committed Tier:<br />

Backup<br />

$26,664 $21,169 $5,495 0.7<br />

Committed Tier:<br />

Backup<br />

$237,681 $92,293 $145,388 3.7<br />

Totals 414,089 42.0 2,065 28,534 112,791 $70,594 $483,569 $175,383 $308,186 4.4<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

3,558,400 166,500 25.3 1.2<br />

377.7<br />

3,558,400 166,500 25.3 1.2<br />

377.7<br />

3,054,078 112,154 21.7 0.8<br />

302.3<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

20.0%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

1,777,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

M DAVIES CC<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4332E<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

83,200<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1962<br />

Basic Gross Area (sf): 70,228<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Office Support<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1040 AHU 1 CAV to VAV<br />

D3028 Monitoring Based Commissioning<br />

M DAVIES CC<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4332E<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1962<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

24,750 1.0 184 0 5,680 $3,548<br />

132,731 15.0 0 14,256 0 $19,509<br />

Basic Gross Area (sf): 70,228<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Office Support<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$26,360 $9,331 $17,029 4.8<br />

Committed Tier:<br />

Backup<br />

$118,751 $46,111 $72,640 3.7<br />

Totals 157,481 16.0 184 14,256 5,680 $23,057 $145,111 $55,442 $89,669 3.9<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

1,777,800 83,200 25.3 1.2<br />

377.7<br />

1,777,800 83,200 25.3 1.2<br />

377.7<br />

1,615,775 66,644 23.0 0.9<br />

330.5<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

12.5%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,225,300<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

JULES STEIN<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4333<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

104,100<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1967<br />

Basic Gross Area (sf): 87,905<br />

Building Type: COMPLEX<br />

Primary Asset Type: Hospitals<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1038 S-1, 5 & 6 CAV to VAV<br />

D1039 S2, 3 & 4Aircuity<br />

D3030 Monitoring Based Commissioning<br />

JULES STEIN<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4333<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

D3031 SBD, New/Renov - Jules Stein Eye Institute Seismic Repair<br />

LOS ANGELES<br />

1967<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

279,911 7.0 2,196 0 108,103 $43,540<br />

102,285 9.0 1,358 0 64,913 $20,571<br />

166,140 19.0 0 17,845 0 $24,419<br />

667,434 76.0 0 31,804 0 $76,198<br />

Basic Gross Area (sf): 87,905<br />

Building Type: COMPLEX<br />

Primary Asset Type: Hospitals<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$121,465 $115,384 $24,293 0.6<br />

Committed Tier:<br />

Backup<br />

$317,011 $53,987 $263,024 12.8<br />

Committed Tier:<br />

Backup<br />

$148,640 $57,719 $90,921 3.7<br />

Committed Tier:<br />

Backup<br />

$777,227 $191,988 $585,239 7.7<br />

Totals 1,215,770 111.0 3,554 49,649 173,016 $164,729 $1,364,343 $419,078 $963,477 5.8<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,225,300 104,100 25.3 1.2<br />

377.6<br />

2,225,300 104,100 25.3 1.2<br />

377.6<br />

871,117 10,026 9.9 0.1<br />

112.9<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

70.1%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

9,465,400<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

BOELTER HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4343<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

442,900<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1959<br />

Basic Gross Area (sf): 373,904<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Office Support<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1052 S-1 to 11 except 9 - CAV to VAV<br />

D1053 AH 4 to 7, 10 to 12 - SP Reset<br />

D3032 Monitoring Based Commissioning<br />

BOELTER HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4343<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1959<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

557,218 15.0 10,256 0 320,081 $125,633<br />

291,309 2.0 5,187 0 166,363 $64,659<br />

706,679 81.0 0 75,903 0 $103,868<br />

Basic Gross Area (sf): 373,904<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Office Support<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$358,186 $323,388 $71,637 0.6<br />

Committed Tier:<br />

Backup<br />

$161,132 $166,693 $32,226 0.5<br />

Committed Tier:<br />

Backup<br />

$632,242 $245,506 $386,736 3.7<br />

Totals 1,555,206 98.0 15,443 75,903 486,444 $294,160 $1,151,560 $735,587 $490,599 1.7<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

9,465,400 442,900 25.3 1.2<br />

377.7<br />

9,465,400 442,900 25.3 1.2<br />

377.7<br />

7,521,039 173,960 20.1 0.5<br />

252.5<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

33.1%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

9,286,400<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

MORTON MED<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4344<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

434,600<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1990<br />

Basic Gross Area (sf): 366,834<br />

Building Type: COMPLEX<br />

Primary Asset Type: Hospitals<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D3033 Monitoring Based Commissioning<br />

MORTON MED<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4344<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1990<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

693,316 79.0 0 74,467 0 $101,903<br />

Basic Gross Area (sf): 366,834<br />

Building Type: COMPLEX<br />

Primary Asset Type: Hospitals<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$620,286 $240,863 $379,423 3.7<br />

Totals 693,316 79.0 0 74,467 0 $101,903 $620,286 $240,863 $379,423 3.7<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

9,286,400 434,600 25.3 1.2<br />

377.7<br />

9,286,400 434,600 25.3 1.2<br />

377.7<br />

8,593,084 360,133 23.4 1.0<br />

338.0<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

10.5%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,559,200<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

MED PLZA 300<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4345<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

119,800<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1990<br />

Basic Gross Area (sf): 101,095<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Hospitals<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D3034 Monitoring Based Commissioning<br />

D6008 CW Reset<br />

MED PLZA 300<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4345<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1990<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

191,070 22.0 0 20,522 0 $28,083<br />

170,100 0.0 0 0 0 $14,969<br />

Basic Gross Area (sf): 101,095<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Hospitals<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$170,944 $66,379 $104,565 3.7<br />

Committed Tier:<br />

Backup<br />

$9,013 $40,824 $1,803 0.1<br />

Totals 361,170 22.0 0 20,522 0 $43,052 $179,957 $107,203 $106,368 2.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,559,200 119,800 25.3 1.2<br />

377.7<br />

2,559,200 119,800 25.3 1.2<br />

377.7<br />

2,198,030 99,278 21.7 1.0<br />

320.8<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

15.1%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

3,660,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

MACDONALDLAB<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4348<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

171,300<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1991<br />

Basic Gross Area (sf): 144,611<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1011 AHU 1 VIV to VAV & SP Reset<br />

D1012 AHU 2 Vivarium Aircuity<br />

D1013 Lab CAV to VAV with Aircuity<br />

D3035 Monitoring Based Commissioning<br />

MACDONALDLAB<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4348<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1991<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

9,792 -2.0 2 0 2,157 $1,009<br />

124,761 14.0 584 0 35,066 $16,408<br />

1,477,065 154.0 9,274 0 388,927 $205,550<br />

273,315 31.0 0 29,356 0 $40,172<br />

Basic Gross Area (sf): 144,611<br />

Building Type: COMPLEX<br />

Primary Asset Type: Office Support<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$46,015 $2,789 $43,226 42.8<br />

Committed Tier:<br />

Backup<br />

$495,153 $43,975 $451,178 27.5<br />

Committed Tier:<br />

Backup<br />

$4,023,619 $545,095 $3,478,524 16.9<br />

Committed Tier:<br />

Backup<br />

$244,525 $94,952 $149,573 3.7<br />

Totals 1,884,933 197.0 9,860 29,356 426,150 $263,138 $4,809,311 $686,811 $4,122,501 15.7<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

3,660,800 171,300 25.3 1.2<br />

377.7<br />

3,660,800 171,300 25.3 1.2<br />

377.7<br />

1,434,947 18,694 9.9 0.1<br />

114.5<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

69.7%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

1,252,500<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

SYCAMORE CT<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

LOS ANGELES<br />

Building Key: 04C4352<br />

Funding Source: HOUSING<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

58,600<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

2004<br />

Basic Gross Area (sf): 140,526<br />

Building Type: BASIC<br />

Primary Asset Type: Residential<br />

Secondary Asset Type: 01C1014 - Inactive<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D3036 Monitoring Based Commissioning<br />

SYCAMORE CT<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4352<br />

Funding Source: HOUSING<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

2004<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

76,192 9.0 0 10,390 0 $12,410<br />

Basic Gross Area (sf): 140,526<br />

Building Type: BASIC<br />

Primary Asset Type: Residential<br />

Secondary Asset Type: 01C1014 - Inactive<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$83,659 $28,676 $54,983 4.4<br />

Totals 76,192 9.0 0 10,390 0 $12,410 $83,659 $28,676 $54,983 4.4<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

1,252,500 58,600 8.9 0.4<br />

133.0<br />

1,252,500 58,600 8.9 0.4<br />

133.0<br />

1,176,308 48,210 8.4 0.3<br />

120.0<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

9.7%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

1,435,100<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

SAC<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4360<br />

Funding Source: OTHER<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

67,200<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1932<br />

Basic Gross Area (sf): 113,383<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Athletics<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1004 AHU 4 SP Reset<br />

D1024 AHU1 to 6 SP Reset<br />

D3037 Monitoring Based Commissioning<br />

SAC<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4360<br />

Funding Source: OTHER<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1932<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

32,518 0.0 512 0 17,290 $6,769<br />

116,981 1.0 1,640 0 70,765 $23,784<br />

87,305 10.0 0 11,905 0 $14,220<br />

D3217 Replace existing GYM HID fixtures with new fluorescent fixtures highbays w/sensors<br />

113,896 13.0 0 0 0 $10,023<br />

D3218 Replace gym HID and strength & conditioning fixtures with new fluorescent fixtures highbays (sensors in gyms only)<br />

229,211 30.0 0 0 0 $20,171<br />

Basic Gross Area (sf): 113,383<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Athletics<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$22,142 $17,524 $4,618 0.7<br />

Committed Tier:<br />

Backup<br />

$16,705 $62,162 $3,341 0.1<br />

Committed Tier:<br />

Backup<br />

$95,861 $32,858 $63,003 4.4<br />

Committed Tier:<br />

Backup<br />

$38,731 $27,335 $11,396 1.1<br />

Committed Tier:<br />

Backup<br />

$83,199 $55,011 $28,188 1.4<br />

Totals 579,911 54.0 2,152 11,905 88,055 $74,966 $256,638 $194,890 $110,546 1.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

1,435,100 67,200 12.7 0.6<br />

188.9<br />

1,435,100 67,200 12.7 0.6<br />

188.9<br />

784,745 28,395 6.9 0.3<br />

95.9<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

49.2%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,582,000<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

FOWLER MUSM<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4374<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

120,800<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1990<br />

Basic Gross Area (sf): 101,995<br />

Building Type: COMPLEX<br />

Primary Asset Type: Museums<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1003 AHU 1 & 2 SP Reset<br />

D3038 Monitoring Based Commissioning<br />

FOWLER MUSM<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4374<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1990<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

161,685 1.0 2,357 0 82,464 $32,396<br />

192,771 22.0 0 20,705 0 $28,333<br />

Basic Gross Area (sf): 101,995<br />

Building Type: COMPLEX<br />

Primary Asset Type: Museums<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$49,351 $84,100 $9,870 0.3<br />

Committed Tier:<br />

Backup<br />

$172,464 $66,970 $105,494 3.7<br />

Totals 354,456 23.0 2,357 20,705 82,464 $60,729 $221,815 $151,070 $115,364 1.9<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,582,000 120,800 25.3 1.2<br />

377.6<br />

2,582,000 120,800 25.3 1.2<br />

377.6<br />

2,161,573 70,633 21.2 0.7<br />

286.2<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

24.2%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,337,500<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

ROYCE HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4375<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

109,400<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1929<br />

Basic Gross Area (sf): 184,673<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Auditorium<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1022 AC 1 & 2 - SP Reset<br />

D1023 AC 3, 4, 6 to 8 - CAV to VAV<br />

D3039 Monitoring Based Commissioning<br />

ROYCE HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4375<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1929<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

41,632 0.0 765 0 29,290 $9,720<br />

116,731 11.0 -46 0 584 $10,057<br />

142,198 16.0 0 19,391 0 $23,161<br />

Basic Gross Area (sf): 184,673<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Auditorium<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$45,550 $25,178 $20,372 2.1<br />

Committed Tier:<br />

Backup<br />

$185,171 $27,553 $157,618 15.7<br />

Committed Tier:<br />

Backup<br />

$156,134 $53,519 $102,615 4.4<br />

Totals 300,561 27.0 719 19,391 29,874 $42,938 $386,856 $106,250 $280,605 6.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,337,500 109,400 12.7 0.6<br />

188.8<br />

2,337,500 109,400 12.7 0.6<br />

188.8<br />

2,013,040 81,022 10.9 0.4<br />

155.5<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

17.7%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

1,203,300<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

UNEX<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4415<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

56,300<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1971<br />

Basic Gross Area (sf): 95,065<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: College Lecture Cl<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1035 AHU 1 to 8 T-1 & T-2 CAV to VAV<br />

D3040 Monitoring Based Commissioning<br />

D6003 Replace Boiler<br />

D6005 Replace Chiller<br />

D6011 CT VFDs<br />

UNEX<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4415<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1971<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

412,262 21.0 0 34,433 0 $55,187<br />

73,200 8.0 0 9,982 0 $11,923<br />

0 0.0 0 5,938 0 $3,261<br />

212,201 72.0 0 0 0 $18,674<br />

11,650 2.0 0 0 0 $1,025<br />

Basic Gross Area (sf): 95,065<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: College Lecture Cl<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$3,048,573 $133,376 $2,915,197 52.8<br />

Committed Tier:<br />

Backup<br />

$80,373 $27,550 $52,823 4.4<br />

Committed Tier:<br />

Backup<br />

$156,646 $5,938 $150,708 46.2<br />

Committed Tier:<br />

Backup<br />

$352,860 $50,928 $301,932 16.2<br />

Committed Tier:<br />

Backup<br />

$7,599 $2,796 $4,803 4.7<br />

Totals 709,313 103.0 0 50,353 0 $90,069 $3,646,051 $220,588 $3,425,463 38.0<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

1,203,300 56,300 12.7 0.6<br />

188.8<br />

1,203,300 56,300 12.7 0.6<br />

188.8<br />

493,987 5,947 5.2 0.1<br />

59.5<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

68.5%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,889,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

SOUTHERN REGIONAL LIBRARY FACILITY<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4562<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

135,200<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1987<br />

Basic Gross Area (sf): 228,306<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1025 AHU 1, 2 & 4 SP Reset<br />

D1026 AHU 3 5 & SF-1 CAV to VAV with SP Reset<br />

D3042 Monitoring Based Commissioning<br />

D6004 Replace Chiller<br />

D6009 CW Reset<br />

SOUTHERN REGIONAL LIBRARY FACILITY<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4562<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1987<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

320,992 5.0 3,742 0 0 $48,795<br />

89,403 4.0 925 0 0 $12,947<br />

175,796 20.0 0 23,972 0 $28,634<br />

264,354 80.0 0 0 0 $23,263<br />

40,032 0.0 0 0 0 $3,523<br />

Basic Gross Area (sf): 228,306<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$72,370 $123,813 $14,474 0.3<br />

Committed Tier:<br />

Backup<br />

$132,983 $33,019 $99,964 7.7<br />

Committed Tier:<br />

Backup<br />

$193,024 $66,163 $126,861 4.4<br />

Committed Tier:<br />

Backup<br />

$387,408 $63,445 $323,963 13.9<br />

Committed Tier:<br />

Backup<br />

$9,013 $9,608 $1,803 0.5<br />

Totals 890,577 109.0 4,667 23,972 0 $117,162 $794,797 $296,048 $567,065 4.8<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,889,800 135,200 12.7 0.6<br />

188.8<br />

2,889,800 135,200 12.7 0.6<br />

188.8<br />

1,999,223 52,891 8.8 0.2<br />

112.8<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

40.2%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

2,901,700<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

BUNCHE HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4580<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

135,800<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1964<br />

Basic Gross Area (sf): 229,248<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Laboratory<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1060 Apply DDC controls, convert to VAV<br />

D3043 Monitoring Based Commissioning<br />

D6013 TOD EF<br />

BUNCHE HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C4580<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1964<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

1,411,691 67.0 7,204 0 0 $163,787<br />

176,521 20.0 0 24,071 0 $28,752<br />

8,081 0.0 0 0 0 $711<br />

Basic Gross Area (sf): 229,248<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Laboratory<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$3,634,425 $428,856 $3,205,569 19.6<br />

Committed Tier:<br />

Backup<br />

$193,820 $66,436 $127,384 4.4<br />

Committed Tier:<br />

Backup<br />

$2,253 $1,939 $451 0.6<br />

Totals 1,596,293 87.0 7,204 24,071 0 $193,250 $3,830,498 $497,231 $3,333,404 17.2<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

2,901,700 135,800 12.7 0.6<br />

188.8<br />

2,901,700 135,800 12.7 0.6<br />

188.8<br />

1,305,407 21,679 5.7 0.1<br />

67.8<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

64.1%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

396,300<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

COLLINS CTR<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515A<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

18,500<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1995<br />

Basic Gross Area (sf): 31,311<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Laboratory<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1001 AHU - 1 VIV to VAV SP Reset<br />

D3045 Monitoring Based Commissioning<br />

COLLINS CTR<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515A<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1995<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

61,694 0.0 418 0 25,367 $9,332<br />

24,109 3.0 0 3,288 0 $3,927<br />

Basic Gross Area (sf): 31,311<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Laboratory<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$40,897 $24,902 $15,995 1.7<br />

Committed Tier:<br />

Backup<br />

$26,473 $9,074 $17,399 4.4<br />

Totals 85,803 3.0 418 3,288 25,367 $13,259 $67,370 $33,976 $33,394 2.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

396,300 18,500 12.7 0.6<br />

188.7<br />

396,300 18,500 12.7 0.6<br />

188.7<br />

290,203 9,987 9.3 0.3<br />

126.8<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

32.8%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

700,500<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

GOLD HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515B<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

32,800<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1995<br />

Basic Gross Area (sf): 55,344<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: College Lecture Cl<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1014 AHU - 2, 7, 9 VIV to VAV SP Reset<br />

D3046 Monitoring Based Commissioning<br />

GOLD HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515B<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1995<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

135,028 1.0 991 0 57,174 $20,947<br />

42,615 5.0 0 5,811 0 $6,941<br />

Basic Gross Area (sf): 55,344<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: College Lecture Cl<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$115,534 $55,772 $59,762 2.9<br />

Committed Tier:<br />

Backup<br />

$46,791 $16,039 $30,752 4.4<br />

Totals 177,643 6.0 991 5,811 57,174 $27,888 $162,325 $71,811 $90,514 3.2<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

700,500 32,800 12.7 0.6<br />

188.9<br />

700,500 32,800 12.7 0.6<br />

188.9<br />

477,118 14,602 8.6 0.3<br />

114.7<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

39.3%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

918,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

ENTREP HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515C<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

43,000<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1995<br />

Basic Gross Area (sf): 72,591<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Auditorium<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1036 AHU - 3 VIV to VAV SP Reset<br />

D1037 VFD + DCV for a CAV system<br />

D3047 Monitoring Based Commissioning<br />

ENTREP HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515C<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1995<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

79,357 1.0 600 0 33,987 $12,432<br />

51,550 2.0 117 0 3,161 $5,379<br />

55,895 6.0 0 7,622 0 $9,104<br />

Basic Gross Area (sf): 72,591<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Auditorium<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$41,969 $33,071 $8,898 0.7<br />

Committed Tier:<br />

Backup<br />

$10,407 $14,441 $2,081 0.4<br />

Committed Tier:<br />

Backup<br />

$61,372 $21,037 $40,335 4.4<br />

Totals 186,802 9.0 717 7,622 37,148 $26,915 $113,748 $68,549 $51,314 1.9<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

918,800 43,000 12.7 0.6<br />

188.8<br />

918,800 43,000 12.7 0.6<br />

188.8<br />

702,280 26,416 9.7 0.4<br />

135.4<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

28.3%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

908,000<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

CORNELL HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515D<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

42,500<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1995<br />

Basic Gross Area (sf): 71,737<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: College Lecture Cl<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1057 AHU - 4 VIV to VAV SP Reset<br />

D3048 Monitoring Based Commissioning<br />

D6007 CW Reset<br />

CORNELL HALL<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515D<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1995<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

70,904 0.0 549 0 30,662 $11,197<br />

55,237 6.0 0 7,532 0 $8,997<br />

68,040 0.0 0 0 0 $5,988<br />

Basic Gross Area (sf): 71,737<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: College Lecture Cl<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$45,552 $29,767 $15,785 1.4<br />

Committed Tier:<br />

Backup<br />

$60,651 $20,789 $39,862 4.4<br />

Committed Tier:<br />

Backup<br />

$9,013 $16,330 $1,803 0.3<br />

Totals 194,181 6.0 549 7,532 30,662 $26,181 $115,217 $66,886 $57,450 2.2<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

908,000 42,500 12.7 0.6<br />

188.8<br />

908,000 42,500 12.7 0.6<br />

188.8<br />

689,289 28,106 9.6 0.4<br />

137.6<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

27.2%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

646,100<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

ROSNFLD LIBR<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515E<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

30,200<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1995<br />

Basic Gross Area (sf): 51,046<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1058 AHU - 6 VIV to VAV SP Reset<br />

D3049 Monitoring Based Commissioning<br />

ROSNFLD LIBR<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515E<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1995<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

77,567 1.0 582 0 33,154 $12,122<br />

39,305 4.0 0 5,360 0 $6,402<br />

Basic Gross Area (sf): 51,046<br />

Building Type: BASIC<br />

Primary Asset Type: Library<br />

Secondary Asset Type: Office<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$47,642 $32,257 $15,385 1.3<br />

Committed Tier:<br />

Backup<br />

$43,159 $14,793 $28,366 4.4<br />

Totals 116,872 5.0 582 5,360 33,154 $18,525 $90,800 $47,050 $43,751 2.4<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

646,100 30,200 12.7 0.6<br />

188.8<br />

646,100 30,200 12.7 0.6<br />

188.8<br />

502,705 17,565 9.8 0.3<br />

135.2<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

28.4%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


Historical <strong>Energy</strong> Use (06/07)<br />

Electricity<br />

(kWh/yr)<br />

429,800<br />

Steam<br />

(MMBTU/yr)<br />

Hot Water<br />

(MMBTU/yr)<br />

Monthly <strong>Energy</strong> Use (Electric)<br />

Metered Data Not Available<br />

Metered Data Not Available<br />

MULLIN CMNS<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515F<br />

Funding Source: STATE<br />

Year Built:<br />

Natural Gas<br />

(th/yr)<br />

20,100<br />

LOS ANGELES<br />

Chilled Water<br />

(ton-hr/yr)<br />

Extrapolated N/A N/A Extrapolated N/A<br />

Monthly <strong>Energy</strong> Use (Gas/Heating Hot Water/Steam)<br />

Monthly <strong>Energy</strong> Use (Chilled Water)<br />

1995<br />

Basic Gross Area (sf): 33,957<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Food Service<br />

Weekly Load Profile (Electric)<br />

Metered Data Not Available<br />

Weekly Load Profile (Natural Gas/Heating Hot Water/Steam)<br />

Metered Data Not Available<br />

Weekly Load Profile (Chilled Water)<br />

Metered Data Not Available Metered Data Not Available


<strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> Projects<br />

SEP ID<br />

Number Project Name<br />

D1059 AHU - 5 & 10 VIV to VAV SP Reset<br />

D3050 Monitoring Based Commissioning<br />

MULLIN CMNS<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location:<br />

Building Key: 04C515F<br />

Funding Source: STATE<br />

Year Built:<br />

Electric<br />

(kWh/yr)<br />

Peak<br />

Demand<br />

(kW)<br />

LOS ANGELES<br />

1995<br />

Building Savings Cost<br />

HW/Steam<br />

(MMBTU/yr)<br />

Gas<br />

(th/yr)<br />

Chilled<br />

Water<br />

(ton-hr/yr)<br />

Purchased<br />

Utility Cost<br />

Savings<br />

($/yr)<br />

82,155 1.0 599 0 34,737 $12,720<br />

26,147 3.0 0 3,565 0 $4,259<br />

Basic Gross Area (sf): 33,957<br />

Building Type: BASIC<br />

Primary Asset Type: Office<br />

Secondary Asset Type: Food Service<br />

Project<br />

Cost<br />

($)<br />

Gross<br />

Potential<br />

Incentive<br />

($)<br />

Net<br />

Cost ($)<br />

Committed Tier:<br />

Simple<br />

Payback<br />

(yr)<br />

Backup<br />

$74,077 $33,874 $40,203 3.2<br />

Committed Tier:<br />

Backup<br />

$28,708 $9,840 $18,868 4.4<br />

Totals 108,302 4.0 599 3,565 34,737 $16,978 $102,785 $43,714 $59,071 3.5<br />

Building<br />

Benchmarking<br />

Baseline<br />

Implement Partnership Projects<br />

Implement SEP Projects<br />

Equivalent<br />

Electricity<br />

(kWh/yr)<br />

Equivalent<br />

Natural Gas<br />

(th/yr)<br />

Equivalent Electric<br />

<strong>Energy</strong> Use Index<br />

(kWh/sf-yr)<br />

Assumed Incentives: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh<br />

th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm<br />

kWh/ton-hr: 0.8<br />

Cap 80% project cost<br />

th/ton-hr: 0.0<br />

Equivalent Natural<br />

Gas <strong>Energy</strong> Use<br />

Index (th/sf-yr)<br />

Source <strong>Energy</strong><br />

Use Index<br />

(kBTU/sf-yr)<br />

429,800 20,100 12.7 0.6<br />

188.8<br />

429,800 20,100 12.7 0.6<br />

188.8<br />

293,708 9,048 8.6 0.3<br />

115.2<br />

Percent<br />

Savings<br />

(%)<br />

N/A<br />

0.0%<br />

39.0%<br />

Source <strong>Energy</strong> Use Conversion Factors:<br />

10.239 kBTU per kWh 100 kBTU per th


10. PROJECT SUMMARIES<br />

The following pages provide a concise project summary for each SEP project. The section,<br />

organized by SEP ID Number, includes the following summary information, and additional<br />

information for each project can be found in the Appendices.<br />

• Basic information including the project SEP ID Number, name, and project location.<br />

• Project prioritization, as committed to by the campus upon review of the preliminary<br />

project list. Tier 1 projects formed a committed energy savings level to the Investor<br />

Owned Utilities. Tier 2 projects reflect the campus’ planned projects to achieve<br />

approximately 150% of the committed energy savings. Backup projects serve as<br />

potential projects the campus may consider or substitute for other projects at any time.<br />

It should be noted that energy savings for select projects may have been refined since<br />

the preliminary project list, as discussed in Section 2 of this report. (Note that all <strong>UC</strong>LA<br />

projects will be shown as “Backup” because the campus did not formally commit to<br />

projects in conjunction with the IOU deadlines.)<br />

• The Calculation File Name provides a reference for the file name, and path if applicable,<br />

of the energy calculation which is included as a soft copy in the appendix of this report.<br />

• The Project Description Reference provides the titles of the projects (Air Handler Project<br />

1, Lighting Project 3, etc) as defined in the <strong>Energy</strong> Efficiency Project Description section<br />

earlier in this report.<br />

• Building <strong>Energy</strong> Savings. The project energy savings are summarized at the building<br />

level, which include chilled water and heating hot water or steam, if supplied from a<br />

central plant, as well as the direct gas or electric savings. The total cost savings are<br />

estimated based on the purchased utility savings (including central plant and<br />

cogeneration impacts) and campus recharge rates.<br />

• Incentive Calculation Basis. The projected utility incentive is provided using the<br />

equivalent electric and gas savings, which convert chilled water and heating hot water or<br />

steam savings to electric or gas savings using the central plant efficiencies. The<br />

incentive shown in this section is the gross potential incentive, without consideration of a<br />

project cost cap.<br />

• Project Cost Summary. Details are displayed for the cost buildup, including appropriate<br />

multipliers and soft costs. If the source of a cost is the construction cost, contingency,<br />

engineering, construction management and project management is added. If the bare<br />

costs are known, the applicable city multipliers, tax, and O&P included obtaining the<br />

estimated construction cost, to which the soft costs are added.<br />

• Project Economics Summary. The project costs, savings and resulting simple payback<br />

are calculated. The utility incentive stated here takes into consideration the project cost<br />

cap, and is highlighted if it is capped by the project cost. The monetary savings is based<br />

on the purchased utility savings and campus recharge rate.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 10-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 1 VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: COLLINS CTR<br />

Building Key: 04C515A<br />

Basic Gross Area (sf): 31,311<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1001<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

61,694<br />

0.0<br />

0<br />

25,367<br />

418<br />

Equipment Description Qty<br />

\1. Collins CTR\1. <strong>UC</strong>LA CVRH_VAV Collins CTR AHU 1 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

81,988<br />

5,225<br />

Extended Bare<br />

Labor Cost ($)<br />

$24,902<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

30 hp VFD 1 $4,775.00 $4,894 $1,100.00 $1,233<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

License Fee (estimated per 1000 CFM) 25 $0.00 $0 $56.00 $1,569<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$11,839 $13,530<br />

$977<br />

$1,538<br />

$14,353<br />

$1,435<br />

$4,869<br />

$1,623<br />

$1,947<br />

N/A<br />

$1,624<br />

$15,154<br />

$1,515<br />

Totals: $15,789 $16,670<br />

Total Project Cost: $40,897<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $40,897<br />

Rebate/Incentive*:<br />

$24,902<br />

Net Project Cost: $15,995<br />

Net Simple Payback Period (yrs): 1.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

106,041<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$9,332


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 & 2 - SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FACMGMT BLDG<br />

Building Key: 04C4260<br />

Basic Gross Area (sf): 189,197<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1002<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

40,882<br />

0.0<br />

0<br />

26,469<br />

644<br />

Equipment Description Qty<br />

\10. Facilities Management\1. <strong>UC</strong>LA CVRH_VAV FacMgmt Bldg AHU 1, 2 - SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

62,057<br />

8,050<br />

Extended Bare<br />

Labor Cost ($)<br />

$22,944<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 2 $4,500.00 $9,225 $7,150.00 $16,030<br />

License Fee (estimated per 1000 CFM) 60 $0.00 $0 $56.00 $3,767<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$9,225 $19,797<br />

$761<br />

$1,198<br />

$11,184<br />

$1,118<br />

$5,504<br />

$1,835<br />

$2,202<br />

N/A<br />

$2,376<br />

$22,172<br />

$2,217<br />

Totals: $12,303 $24,390<br />

Total Project Cost: $46,233<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,233<br />

Rebate/Incentive*:<br />

$22,944<br />

Net Project Cost: $23,289<br />

Net Simple Payback Period (yrs): 2.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

100,125<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$8,811


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 & 2 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FOWLER MUSM<br />

Building Key: 04C4374<br />

Basic Gross Area (sf): 101,995<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1003<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

161,685<br />

1.0<br />

0<br />

82,464<br />

2,357<br />

Equipment Description Qty<br />

\11. Fowler Musm\1. <strong>UC</strong>LA CVRH_VAV_60 Fowler MusmAHU 1 & 2 SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

227,656<br />

29,463<br />

$84,100<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 2 $4,500.00 $9,225 $7,150.00 $16,030<br />

License Fee (estimated per 1000 CFM) 92 $0.00 $0 $56.00 $5,775<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$9,225 $21,806<br />

$761<br />

$1,198<br />

$11,184<br />

$1,118<br />

$5,875<br />

$1,958<br />

$2,350<br />

N/A<br />

$2,617<br />

$24,422<br />

$2,442<br />

Totals: $12,303 $26,865<br />

Total Project Cost: $49,351<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $49,351<br />

Rebate/Incentive*:<br />

$39,481<br />

Net Project Cost: $9,870<br />

Net Simple Payback Period (yrs): 0.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

368,136<br />

0<br />

$32,396<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 4 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SAC<br />

Building Key: 04C4360<br />

Basic Gross Area (sf): 113,383<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1004<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

32,518<br />

0.0<br />

0<br />

17,290<br />

512<br />

Equipment Description Qty<br />

\12. Gonda <strong>Center</strong>\1. <strong>UC</strong>LA CVRH_VAV Gonda <strong>Center</strong> AHU 4 SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

46,350<br />

6,400<br />

Extended Bare<br />

Labor Cost ($)<br />

$17,524<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

License Fee (estimated per 1000 CFM) 20 $0.00 $0 $56.00 $1,256<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$4,613 $9,271<br />

$381<br />

$599<br />

$5,592<br />

$559<br />

$2,636<br />

$879<br />

$1,054<br />

N/A<br />

$1,112<br />

$10,383<br />

$1,038<br />

Totals: $6,151 $11,421<br />

Total Project Cost: $22,142<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $22,142<br />

Rebate/Incentive*:<br />

$17,524<br />

Net Project Cost: $4,618<br />

Net Simple Payback Period (yrs): 0.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

76,916<br />

0<br />

$6,769


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CV Rebalance<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GONDA CENTER<br />

Building Key: 04C4315<br />

Basic Gross Area (sf): 125,202<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1005<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

211,550<br />

24.0<br />

0<br />

59,189<br />

1,194<br />

Equipment Description Qty<br />

\12. Gonda <strong>Center</strong>\2.1 <strong>UC</strong>LA HVAC Lab-1 Gonda <strong>Center</strong> CV Rebalance.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

258,901<br />

14,925<br />

$77,061<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Rebalance ($1.75 per square foot) 19,580 $0.00 $0 $1.75 $38,411<br />

40 hp VFD 1 $7,025.00 $7,201 $1,100.00 $1,233<br />

5 hp VFD 2 $1,675.00 $3,434 $455.00 $1,020<br />

1 hp VFD 1 $350.00 $359 $400.00<br />

$448<br />

2 hp VFD 2 $700.00 $1,435 $400.00<br />

$897<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$12,428 $42,009<br />

$1,025<br />

$1,614<br />

$15,068<br />

$1,507<br />

$10,250<br />

$3,417<br />

$4,100<br />

N/A<br />

$5,041<br />

$47,051<br />

$4,705<br />

Totals: $16,575 $51,756<br />

Total Project Cost: $86,096<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $86,096<br />

Rebate/Incentive*:<br />

$68,877<br />

Net Project Cost: $17,219<br />

Net Simple Payback Period (yrs): 0.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

328,672<br />

0<br />

$28,923<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: DAC 1 to 4 & DAHU-1 - VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: COVEL COMMON<br />

Building Key: 04C4302D<br />

Basic Gross Area (sf): 144,067<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1006<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

287,180<br />

2.0<br />

16,383<br />

Equipment Description Qty<br />

\14. Covel Commons\1. <strong>UC</strong>LA CVRH_VAV Covel Commons DAC 1 to 4 & DAHU-1 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

287,180<br />

16,383<br />

$85,306<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

VIV Removal 80 $0.00 $0 $100.00 $8,968<br />

Program SP reset 80 $100.00 $8,968<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

15 hp VFD 3 $2,275.00 $6,996 $820.00 $2,758<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

25 hp VFD 1 $3,925.00 $4,023 $1,100.00 $1,233<br />

40 hp VFD 2 $7,025.00 $14,401 $1,100.00 $2,466<br />

30 hp VFD 1 $4,775.00 $4,894 $1,100.00 $1,233<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$37,515 $27,666<br />

$3,095<br />

$4,873<br />

$45,483<br />

$4,548<br />

$12,617<br />

$4,206<br />

$5,047<br />

N/A<br />

$3,320<br />

$30,986<br />

$3,099<br />

Totals: $50,032 $34,085<br />

Total Project Cost: $105,987<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $105,987<br />

Rebate/Incentive*:<br />

$84,789<br />

Net Project Cost: $21,197<br />

Net Simple Payback Period (yrs): 0.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

389,410<br />

0<br />

$34,268<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: KERCKHOFF<br />

Building Key: 04C4310<br />

Basic Gross Area (sf): 70,820<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1007<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

31,578<br />

0.0<br />

0<br />

18,206<br />

451<br />

Equipment Description Qty<br />

\17. Kerckhoff\1. <strong>UC</strong>LA CVRH_VAV Kerckhoff Hall AHU 1SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

46,143<br />

5,638<br />

Extended Bare<br />

Labor Cost ($)<br />

$16,712<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Program SP Reset 16 $0.00 $0 $100.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$0 $1,794<br />

$0<br />

$0<br />

$0<br />

$0<br />

$331<br />

$110<br />

$133<br />

N/A<br />

$215<br />

$2,009<br />

$201<br />

Totals: $0 $2,210<br />

Total Project Cost: $2,784<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $2,784<br />

Rebate/Incentive*:<br />

$2,227<br />

Net Project Cost: $557<br />

Net Simple Payback Period (yrs): 0.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

72,829<br />

0<br />

$6,409


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CAV to VAV - AHU 2<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: KERCKHOFF<br />

Building Key: 04C4310<br />

Basic Gross Area (sf): 70,820<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1008<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

29,236<br />

1.0<br />

0<br />

12,178<br />

226<br />

Equipment Description Qty<br />

\17. Kerckhoff\2. <strong>UC</strong>LA MZ_DD_VAV Kerckkhoff AHU 2 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

38,978<br />

2,825<br />

Extended Bare<br />

Labor Cost ($)<br />

$12,180<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Dart @ zone 2 $440.00 $902 $128.00<br />

$287<br />

Dart Control 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

2 hp VFD 1 $700.00 $718 $400.00<br />

$448<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$12,572 $4,597<br />

$1,037<br />

$1,633<br />

$15,242<br />

$1,524<br />

$3,364<br />

$1,121<br />

$1,346<br />

N/A<br />

$552<br />

$5,149<br />

$515<br />

Totals: $16,766 $5,664<br />

Total Project Cost: $28,262<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $28,262<br />

Rebate/Incentive*:<br />

$12,180<br />

Net Project Cost: $16,082<br />

Net Simple Payback Period (yrs): 3.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

52,107<br />

0<br />

$4,585


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Vivarium - CV Rebalance<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LIFE SCIENCE<br />

Building Key: 04C4320<br />

Basic Gross Area (sf): 214,613<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1009<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

0<br />

43,530<br />

725<br />

Equipment Description Qty<br />

\18. Life Sciences\1. <strong>UC</strong>LA_HVAC Lab_Life Science_Vivarium SF-2 - CV Rebalance.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

34,824<br />

9,063<br />

Extended Bare<br />

Labor Cost ($)<br />

$17,420<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Rebalance ($1.75 per square foot) 12,359 $0.00 $0 $1.75 $24,245<br />

50 hp VFD 1 $7,650.00 $7,841 $1,375.00 $1,541<br />

2 hp VFD 1 $700.00 $718 $400.00<br />

$448<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$10,276 $26,745<br />

$848<br />

$1,335<br />

$12,458<br />

$1,246<br />

$6,998<br />

$2,333<br />

$2,799<br />

N/A<br />

$3,209<br />

$29,955<br />

$2,995<br />

Totals: $13,704 $32,950<br />

Total Project Cost: $58,784<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $58,784<br />

Rebate/Incentive*:<br />

$17,420<br />

Net Project Cost: $41,364<br />

Net Simple Payback Period (yrs): 6.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

76,582<br />

0<br />

$6,739


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SF - 4 & 5 - Aircuity<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LIFE SCIENCE<br />

Building Key: 04C4320<br />

Basic Gross Area (sf): 214,613<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1010<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

350,121<br />

32.0<br />

0<br />

299,188<br />

5,889<br />

Equipment Description Qty<br />

\18. Life Sciences\2. <strong>UC</strong>LA_HVAC Lab_Life Science SF-4 & 5 - Aircuity.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to Variable Air Volume &<br />

Laboratory Air Handler Project 2. Rebalance Variable Air Volume Laboratory (or Vivarium) Air Handlers.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 589,471<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

73,613<br />

Extended Bare<br />

Labor Cost ($)<br />

$215,086<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Fume Hood Conversion - CAV to VAV 60 $11,250.00 $691,875 $11,250.00 $756,675<br />

Aircuity, per sensor 15 $2,500.00 $38,438 $2,000.00 $33,630<br />

0.5 hp VFD 1 $175.00 $179 $350.00<br />

$392<br />

2 hp VFD 6 $700.00 $4,305 $400.00 $2,690<br />

3 hp VFD 1 $1,525.00 $1,563 $455.00<br />

$510<br />

5 hp VFD 3 $1,675.00 $5,151 $455.00 $1,530<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

25 hp VFD 1 $3,925.00 $4,023 $1,100.00 $1,233<br />

30 hp VFD 1 $4,775.00 $4,894 $1,100.00 $1,233<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$752,453 $798,505<br />

$62,077<br />

$97,744<br />

$912,273<br />

$91,227<br />

$298,089<br />

$99,363<br />

$119,236<br />

N/A<br />

$95,821<br />

$894,326<br />

$89,433<br />

Totals: $1,003,501 $983,758<br />

Total Project Cost: $2,503,946<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $2,503,946<br />

Rebate/Incentive*:<br />

$215,086<br />

Net Project Cost: $2,288,860<br />

Net Simple Payback Period (yrs): 27.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

933,010<br />

0<br />

$82,105<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 VIV to VAV & SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MACDONALDLAB<br />

Building Key: 04C4348<br />

Basic Gross Area (sf): 144,611<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1011<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

9,792<br />

-2.0<br />

0<br />

2,157<br />

Equipment Description Qty<br />

\19. Macdonald Lab\1. <strong>UC</strong>LA CVRH_VAV Macdonald lab AHU 1 VIV to VAV & SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

2<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

11,518<br />

25<br />

$2,789<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

50 hp VFD 1 $7,650.00 $7,841 $1,375.00 $1,541<br />

License Fee (estimated per 1000 CFM) 32 $0.00 $0 $56.00 $2,009<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$14,478 $13,970<br />

$1,194<br />

$1,881<br />

$17,553<br />

$1,755<br />

$5,478<br />

$1,826<br />

$2,191<br />

N/A<br />

$1,676<br />

$15,646<br />

$1,565<br />

Totals: $19,309 $17,211<br />

Total Project Cost: $46,015<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,015<br />

Rebate/Incentive*:<br />

$2,789<br />

Net Project Cost: $43,226<br />

Net Simple Payback Period (yrs): 42.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

11,470<br />

0<br />

$1,009<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 2 Vivarium Aircuity<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MACDONALDLAB<br />

Building Key: 04C4348<br />

Basic Gross Area (sf): 144,611<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1012<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

124,761<br />

14.0<br />

0<br />

35,066<br />

584<br />

Equipment Description Qty<br />

\19. Macdonald Lab\2 <strong>UC</strong>LA Lab Model Macdonald Lab AHU 2 Aircuity Vivarium.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to Variable Air Volume &<br />

Laboratory Air Handler Project 2. Rebalance Variable Air Volume Laboratory (or Vivarium) Air Handlers.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 152,814<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

7,300<br />

Extended Bare<br />

Labor Cost ($)<br />

$43,975<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Aircuity, per sensor 3 $2,500.00 $7,688 $2,000.00 $6,726<br />

Fume Hood Conversion - CAV to VAV 12 $11,250.00 $138,375 $11,250.00 $151,335<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$148,087 $158,672<br />

$12,217<br />

$19,236<br />

$179,541<br />

$17,954<br />

$58,947<br />

$19,649<br />

$23,579<br />

N/A<br />

$19,041<br />

$177,713<br />

$17,771<br />

Totals: $197,495 $195,484<br />

Total Project Cost: $495,153<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $495,153<br />

Rebate/Incentive*:<br />

$43,975<br />

Net Project Cost: $451,178<br />

Net Simple Payback Period (yrs): 27.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

186,450<br />

0<br />

$16,408<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Lab CAV to VAV with Aircuity<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MACDONALDLAB<br />

Building Key: 04C4348<br />

Basic Gross Area (sf): 144,611<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1013<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

1,477,065<br />

154.0<br />

0<br />

388,927<br />

9,274<br />

Equipment Description Qty<br />

\19. Macdonald Lab\3 <strong>UC</strong>LA .Lab Model Macdonald Lab.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

1,788,207<br />

115,925<br />

$545,095<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Aircuity, per sensor 30 $2,500.00 $76,875 $2,000.00 $67,260<br />

15 hp VFD 4 $2,275.00 $9,328 $820.00 $3,677<br />

25 hp VFD 2 $3,925.00 $8,046 $1,100.00 $2,466<br />

125 hp VFD 2 $12,900.00 $26,445 $1,800.00 $4,036<br />

Fume Hood Conversion - CAV to VAV 95 $11,250.00 $1,095,469 $11,250.00 $1,198,069<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$1,216,163 $1,275,507<br />

$100,333<br />

$157,980<br />

$1,474,475<br />

$147,448<br />

$479,002<br />

$159,667<br />

$191,601<br />

N/A<br />

$153,061<br />

$1,428,568<br />

$142,857<br />

Totals: $1,621,923 $1,571,425<br />

Total Project Cost: $4,023,619<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $4,023,619<br />

Rebate/Incentive*:<br />

$545,095<br />

Net Project Cost: $3,478,524<br />

Net Simple Payback Period (yrs): 16.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

2,335,790<br />

0<br />

$205,550<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 2, 7, 9 VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GOLD HALL<br />

Building Key: 04C515B<br />

Basic Gross Area (sf): 55,344<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1014<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

135,028<br />

1.0<br />

0<br />

57,174<br />

991<br />

Equipment Description Qty<br />

\2. Gold Hall\1. <strong>UC</strong>LA CVRH_VAV Gold Hall AHU 2, 7, 9 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

180,767<br />

12,388<br />

$55,772<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

50 hp VFD 1 $7,650.00 $7,841 $1,375.00 $1,541<br />

VIV Removal 48 $0.00 $0 $100.00 $5,381<br />

License Fee (estimated per 1000 CFM) 59 $0.00 $0 $56.00 $3,704<br />

SAV with InCite 3 $4,500.00 $13,838 $7,150.00 $24,045<br />

Dart Control 0 $8,710.00 $0 $2,900.00<br />

$0<br />

15 hp VFD 2 $2,275.00 $4,664 $820.00 $1,838<br />

5 hp VFD 2 $1,675.00 $3,434 $455.00 $1,020<br />

Dart @ Zone 0 $440.00 $0 $128.00<br />

$0<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$33,236 $38,449<br />

$2,742<br />

$4,317<br />

$40,295<br />

$4,029<br />

$13,754<br />

$4,585<br />

$5,502<br />

N/A<br />

$4,614<br />

$43,063<br />

$4,306<br />

Totals: $44,324 $47,369<br />

Total Project Cost: $115,534<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $115,534<br />

Rebate/Incentive*:<br />

$55,772<br />

Net Project Cost: $59,762<br />

Net Simple Payback Period (yrs): 2.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

238,032<br />

0<br />

$20,947<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 5 VIV to VAV & SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MOLECULR SCI<br />

Building Key: 04C4228C<br />

Basic Gross Area (sf): 178,666<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1015<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

10,294<br />

0.0<br />

0<br />

1,857<br />

Equipment Description Qty<br />

\22. Molecular Sci\1. <strong>UC</strong>LA CVRH_VAVMolecular Sci AHU 5 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

16<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

11,780<br />

200<br />

$3,027<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

3 hp VFD 1 $1,525.00 $1,563 $455.00<br />

$510<br />

License Fee (estimated per 1000 CFM) 16 $0.00 $0 $56.00 $1,004<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$9,635 $12,242<br />

$795<br />

$1,252<br />

$11,681<br />

$1,168<br />

$4,190<br />

$1,397<br />

$1,676<br />

N/A<br />

$1,469<br />

$13,712<br />

$1,371<br />

Totals: $12,850 $15,083<br />

Total Project Cost: $35,195<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $35,195<br />

Rebate/Incentive*:<br />

$3,027<br />

Net Project Cost: $32,168<br />

Net Simple Payback Period (yrs): 28.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

12,629<br />

0<br />

$1,111<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1, 2, 3, 4 & 6 Aircuity<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MOLECULR SCI<br />

Building Key: 04C4228C<br />

Basic Gross Area (sf): 178,666<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1016<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

2,629,450<br />

68.0<br />

0<br />

104,815<br />

13,688<br />

Equipment Description Qty<br />

\22. Molecular Sci\2. <strong>UC</strong>LA HVAC Lab Molecular Sci AHU 1, 2, 3, 4 & 6 Aircuity.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 3. Reduce Minimum Air Change Requirements through Continuous Monitoring.<br />

Scaled savings to account for previous hood project<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 2,713,302<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

171,100<br />

$822,292<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Rebalance ($1.75 per square foot) 175,000 $0.00 $0 $1.75 $343,306<br />

Aircuity, per sensor 80 $2,500.00 $205,000 $2,000.00 $179,360<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$205,000 $522,666<br />

$16,913<br />

$26,630<br />

$248,542<br />

$24,854<br />

$137,598<br />

$45,866<br />

$55,039<br />

N/A<br />

$62,720<br />

$585,386<br />

$58,539<br />

Totals: $273,396 $643,925<br />

Total Project Cost: $1,155,824<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $1,155,824<br />

Rebate/Incentive*:<br />

$822,292<br />

Net Project Cost: $333,532<br />

Net Simple Payback Period (yrs): 1.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

3,559,048<br />

0<br />

$313,196<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-1 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: POWELL LIB<br />

Building Key: 04C4318A<br />

Basic Gross Area (sf): 166,846<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1017<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

7,870<br />

1.0<br />

0<br />

7,191<br />

143<br />

Equipment Description Qty<br />

\23. Powell Lib\1. <strong>UC</strong>LA MZ_DD_VAV Powell Lib S-1 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

13,623<br />

1,788<br />

$5,057<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

Dart Control 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

Dart @ zone 9 $440.00 $4,059 $128.00 $1,291<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$16,728 $5,663<br />

$1,380<br />

$2,173<br />

$20,281<br />

$2,028<br />

$4,393<br />

$1,464<br />

$1,757<br />

N/A<br />

$680<br />

$6,343<br />

$634<br />

Totals: $22,309 $6,977<br />

Total Project Cost: $36,901<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $36,901<br />

Rebate/Incentive*:<br />

$5,057<br />

Net Project Cost: $31,844<br />

Net Simple Payback Period (yrs): 16.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

21,971<br />

0<br />

$1,933<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AH 1 to 4, 17 & 37 CAV to VAV with DCV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: POWELL LIB<br />

Building Key: 04C4318A<br />

Basic Gross Area (sf): 166,846<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1018<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

44,410<br />

10.0<br />

0<br />

4,351<br />

-23<br />

Equipment Description Qty<br />

\23. Powell Lib\2. <strong>UC</strong>LA DCV - SZ_VAV Powell Lib AH 1 to 4, 17 & 37 CAV to VAV & DCV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 3.<br />

Demand Control Ventilation.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 47,891<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

-288<br />

Extended Bare<br />

Labor Cost ($)<br />

$11,206<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Program VSD based on room T 96 $100.00 $10,762<br />

CO2 Sensor 6 $400.00 $2,460 $0.00<br />

$0<br />

3 hp VFD 4 $1,525.00 $6,253 $455.00 $2,040<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

Program DCV 24 $0.00 $0 $100.00 $2,690<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$13,069 $17,022<br />

$1,078<br />

$1,698<br />

$15,845<br />

$1,584<br />

$5,760<br />

$1,920<br />

$2,304<br />

N/A<br />

$2,043<br />

$19,065<br />

$1,907<br />

Totals: $17,429 $20,972<br />

Total Project Cost: $48,385<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $48,385<br />

Rebate/Incentive*:<br />

$11,206<br />

Net Project Cost: $37,179<br />

Net Simple Payback Period (yrs): 9.2<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

46,108<br />

0<br />

$4,057


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AH-19 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: POWELL LIB<br />

Building Key: 04C4318A<br />

Basic Gross Area (sf): 166,846<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1019<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

79,947<br />

7.0<br />

0<br />

38,959<br />

532<br />

Equipment Description Qty<br />

\23. Powell Lib\3. <strong>UC</strong>LA MZ_DD_VAV Powell Lib AH-19 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

111,114<br />

6,650<br />

$33,317<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

75 hp VFD 1 $11,500.00 $11,788 $1,600.00 $1,794<br />

Dart Control 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

Dart @ zone 4 $440.00 $1,804 $128.00<br />

$574<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$22,519 $5,618<br />

$1,858<br />

$2,925<br />

$27,302<br />

$2,730<br />

$5,543<br />

$1,848<br />

$2,217<br />

N/A<br />

$674<br />

$6,293<br />

$629<br />

Totals: $30,033 $6,922<br />

Total Project Cost: $46,563<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,563<br />

Rebate/Incentive*:<br />

$33,317<br />

Net Project Cost: $13,246<br />

Net Simple Payback Period (yrs): 1.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

141,194<br />

0<br />

$12,425<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AH 18, 38 & 39 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: POWELL LIB<br />

Building Key: 04C4318A<br />

Basic Gross Area (sf): 166,846<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1020<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

23,523<br />

5.0<br />

0<br />

2,409<br />

Equipment Description Qty<br />

\23. Powell Lib\4. <strong>UC</strong>LA DCV - SZ_VAV Powell Lib AH 18, 38 & 39 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

-3<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

25,450<br />

-38<br />

$6,071<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

3 hp VFD 1 $1,525.00 $1,563 $455.00<br />

$510<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

Program VSD based on room T 48 $100.00 $5,381<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$5,304 $7,012<br />

$438<br />

$689<br />

$0<br />

$0<br />

$1,296<br />

$432<br />

$518<br />

N/A<br />

$841<br />

$7,853<br />

$785<br />

Totals: $0 $8,639<br />

Total Project Cost: $10,885<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $10,885<br />

Rebate/Incentive*:<br />

$6,071<br />

Net Project Cost: $4,814<br />

Net Simple Payback Period (yrs): 2.2<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

25,070<br />

0<br />

$2,206<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AH 20 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: POWELL LIB<br />

Building Key: 04C4318A<br />

Basic Gross Area (sf): 166,846<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1021<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

45,021<br />

4.0<br />

0<br />

32,750<br />

396<br />

Equipment Description Qty<br />

\23. Powell Lib\5. <strong>UC</strong>LA CVRH_VAV Powell Lib AH 20 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

71,221<br />

4,950<br />

Extended Bare<br />

Labor Cost ($)<br />

$22,043<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

30 hp VFD 1 $4,775.00 $4,894 $1,100.00 $1,233<br />

Dart @ Controls 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

Dart @ Zones 10 $440.00 $4,510 $128.00 $1,435<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$20,357 $6,530<br />

$1,679<br />

$2,644<br />

$24,680<br />

$2,468<br />

$5,279<br />

$1,760<br />

$2,112<br />

N/A<br />

$784<br />

$7,313<br />

$731<br />

Totals: $27,148 $8,045<br />

Total Project Cost: $44,343<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $44,343<br />

Rebate/Incentive*:<br />

$22,043<br />

Net Project Cost: $22,300<br />

Net Simple Payback Period (yrs): 2.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

93,311<br />

0<br />

$8,211


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AC 1 & 2 - SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ROYCE HALL<br />

Building Key: 04C4375<br />

Basic Gross Area (sf): 184,673<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1022<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

41,632<br />

0.0<br />

0<br />

29,290<br />

765<br />

Equipment Description Qty<br />

\24. Royce Hall\1. <strong>UC</strong>LA CVRH_VAV Royce Hall AC-1 & 2 - SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

65,064<br />

9,563<br />

Extended Bare<br />

Labor Cost ($)<br />

$25,178<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 2 $4,500.00 $9,225 $7,150.00 $16,030<br />

License Fee (estimated per 1000 CFM) 53 $0.00 $0 $56.00 $3,327<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$9,225 $19,357<br />

$761<br />

$1,198<br />

$11,184<br />

$1,118<br />

$5,423<br />

$1,808<br />

$2,169<br />

N/A<br />

$2,323<br />

$21,680<br />

$2,168<br />

Totals: $12,303 $23,848<br />

Total Project Cost: $45,550<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $45,550<br />

Rebate/Incentive*:<br />

$25,178<br />

Net Project Cost: $20,372<br />

Net Simple Payback Period (yrs): 2.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

110,457<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$9,720


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AC 3, 4, 6 to 8 - CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ROYCE HALL<br />

Building Key: 04C4375<br />

Basic Gross Area (sf): 184,673<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1023<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

116,731<br />

11.0<br />

0<br />

584<br />

-46<br />

Equipment Description Qty<br />

\24. Royce Hall\2. <strong>UC</strong>LA DCV - SZ_VAV_60 Royce Hall AC 3,4,6,7,8 - CAv to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 6.<br />

Convert Air Handlers to Direct Digital Control.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 117,198<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

-575<br />

Extended Bare<br />

Labor Cost ($)<br />

$27,553<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

2 hp VFD 3 $700.00 $2,153 $400.00 $1,345<br />

5 hp VFD 3 $1,675.00 $5,151 $455.00 $1,530<br />

20 hp VFD 2 $3,375.00 $6,919 $820.00 $1,838<br />

SZ CAV to VAV (105 points) 5 $11,063.41 $56,700 $6,743.98 $37,800<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$70,922 $42,514<br />

$5,851<br />

$9,213<br />

$85,986<br />

$8,599<br />

$22,044<br />

$7,348<br />

$8,818<br />

N/A<br />

$5,102<br />

$47,615<br />

$4,762<br />

Totals: $94,584 $52,377<br />

Total Project Cost: $185,171<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $185,171<br />

Rebate/Incentive*:<br />

$27,553<br />

Net Project Cost: $157,618<br />

Net Simple Payback Period (yrs): 15.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

114,281<br />

0<br />

$10,057<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU1 to 6 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SAC<br />

Building Key: 04C4360<br />

Basic Gross Area (sf): 113,383<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1024<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

116,981<br />

1.0<br />

0<br />

70,765<br />

1,640<br />

Equipment Description Qty<br />

\25. SAC\1. <strong>UC</strong>LA CVRH_VAV SAC AHU 1 to 6 SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

173,593<br />

20,500<br />

$62,162<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Program SP Reset 96 $0.00 $0 $100.00 $10,762<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$0 $10,762<br />

$0<br />

$0<br />

$0<br />

$0<br />

$1,989<br />

$663<br />

$795<br />

N/A<br />

$1,291<br />

$12,053<br />

$1,205<br />

Totals: $0 $13,258<br />

Total Project Cost: $16,705<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $16,705<br />

Rebate/Incentive*:<br />

$13,364<br />

Net Project Cost: $3,341<br />

Net Simple Payback Period (yrs): 0.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

270,268<br />

0<br />

$23,784<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1, 2 & 4 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SOUTHERN REGIONAL LIBRARY FACI<br />

Building Key: 04C4562<br />

Basic Gross Area (sf): 228,306<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1025<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

320,992<br />

5.0<br />

0<br />

0<br />

3,742<br />

Equipment Description Qty<br />

\26. Sourthern Regional Library FAC\1. <strong>UC</strong>LA CVRH_VAV SRLF AHU 1, 2 & 4 SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

320,992<br />

46,775<br />

$123,813<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 3 $4,500.00 $13,838 $7,150.00 $24,045<br />

License Fee (estimated per 1000 CFM) 121 $0.00 $0 $56.00 $7,596<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$13,838 $31,641<br />

$1,142<br />

$1,797<br />

$16,777<br />

$1,678<br />

$8,615<br />

$2,872<br />

$3,446<br />

N/A<br />

$3,797<br />

$35,438<br />

$3,544<br />

Totals: $18,454 $38,982<br />

Total Project Cost: $72,370<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $72,370<br />

Rebate/Incentive*:<br />

$57,896<br />

Net Project Cost: $14,474<br />

Net Simple Payback Period (yrs): 0.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

554,493<br />

0<br />

$48,795<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 3 5 & SF-1 CAV to VAV with SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SOUTHERN REGIONAL LIBRARY FACI<br />

Building Key: 04C4562<br />

Basic Gross Area (sf): 228,306<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1026<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

89,403<br />

4.0<br />

0<br />

0<br />

925<br />

Equipment Description Qty<br />

\26. Sourthern Regional Library FAC\2. <strong>UC</strong>LA CVRH_VAV SRLF AHU 3, 5, SF-1 CAV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

89,403<br />

11,563<br />

Extended Bare<br />

Labor Cost ($)<br />

$33,019<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 3 $4,500.00 $13,838 $7,150.00 $24,045<br />

Dart @ Zone 6 $0.00 $0 $56.00<br />

$377<br />

License Fee (estimated per 1000 CFM) 11 $0.00 $0 $56.00<br />

$691<br />

7.5 hp VFD 2 $1,975.00 $4,049 $545.00 $1,222<br />

2 hp VFD 1 $700.00 $718 $400.00<br />

$448<br />

Dart Control 3 $8,710.00 $26,783 $2,900.00 $9,753<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$45,387 $36,536<br />

$3,744<br />

$5,896<br />

$55,027<br />

$5,503<br />

$15,831<br />

$5,277<br />

$6,333<br />

N/A<br />

$4,384<br />

$40,920<br />

$4,092<br />

Totals: $60,530 $45,012<br />

Total Project Cost: $132,983<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $132,983<br />

Rebate/Incentive*:<br />

$33,019<br />

Net Project Cost: $99,964<br />

Net Simple Payback Period (yrs): 7.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

147,123<br />

0<br />

$12,947<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 & 2 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WILSHIRE CTR<br />

Building Key: 04C4270<br />

Basic Gross Area (sf): 455,912<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1027<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

736,319<br />

171.0<br />

Equipment Description Qty<br />

\27. Wilshire CTR\1. <strong>UC</strong>LA CVRH_VAV_60 Wilshire CTR AHU 1 & 2 SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

736,319<br />

0<br />

$176,717<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Program SP Reset 32 $0.00 $0 $100.00 $3,587<br />

0 $0.00 $0 $56.00<br />

$0<br />

Zone Level Controller & DDC - cooling only 252 $2,458.54 $635,041 $1,498.66 $423,359<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$635,041 $426,947<br />

$52,391<br />

$82,492<br />

$769,924<br />

$76,992<br />

$205,937<br />

$68,646<br />

$82,375<br />

N/A<br />

$51,234<br />

$478,180<br />

$47,818<br />

Totals: $846,916 $525,998<br />

Total Project Cost: $1,729,872<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $1,729,872<br />

Rebate/Incentive*:<br />

$176,717<br />

Net Project Cost: $1,553,155<br />

Net Simple Payback Period (yrs): 24.0<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

736,319<br />

0<br />

$64,796<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 VIV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1028<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

22,785<br />

0.0<br />

0<br />

10,374<br />

183<br />

Equipment Description Qty<br />

\28. Woodenps4\1. <strong>UC</strong>LA CVRH_VAV Woodenps4 AHU 1 VIV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 6.<br />

Convert Air Handlers to Direct Digital Control.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 31,084<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

2,288<br />

$9,748<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

CAV - RH to VAV - RH (17 points) 1 $8,956.10 $9,180 $5,459.41 $6,120<br />

0 $4,500.00 $0 $7,150.00<br />

$0<br />

0 $0.00 $0 $56.00<br />

$0<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$13,229 $9,343<br />

$1,091<br />

$1,718<br />

$16,039<br />

$1,604<br />

$4,373<br />

$1,458<br />

$1,749<br />

N/A<br />

$1,121<br />

$10,464<br />

$1,046<br />

Totals: $17,642 $11,510<br />

Total Project Cost: $36,733<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $36,733<br />

Rebate/Incentive*:<br />

$9,748<br />

Net Project Cost: $26,985<br />

Net Simple Payback Period (yrs): 7.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

41,673<br />

0<br />

$3,667<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 3 VIV to VAV & SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1029<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

58,384<br />

1.0<br />

0<br />

24,388<br />

434<br />

Equipment Description Qty<br />

\28. Woodenps4\2. <strong>UC</strong>LA CVRH_VAV Woodenps4 AHU 3 VIV to VAV SP reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume, Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers & Air Handler Project 6. Convert Air Handlers to<br />

Direct Digital Control.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 77,894<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

5,425<br />

Extended Bare<br />

Labor Cost ($)<br />

$24,120<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

30 hp VFD 1 $4,775.00 $4,894 $1,100.00 $1,233<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

License Fee (estimated per 1000 CFM) 26 $0.00 $0 $56.00 $1,632<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

CAV - RH to VAV - RH (17 points) 1 $8,956.10 $9,180 $5,459.41 $6,120<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$21,019 $19,713<br />

$1,734<br />

$2,730<br />

$25,483<br />

$2,548<br />

$7,848<br />

$2,616<br />

$3,139<br />

N/A<br />

$2,366<br />

$22,079<br />

$2,208<br />

Totals: $28,031 $24,287<br />

Total Project Cost: $65,921<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $65,921<br />

Rebate/Incentive*:<br />

$24,120<br />

Net Project Cost: $41,801<br />

Net Simple Payback Period (yrs): 4.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

103,025<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$9,066


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1030<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

236,777<br />

57.0<br />

0<br />

8,663<br />

-176<br />

Equipment Description Qty<br />

\28. Woodenps4\3. DCV - SZ_VAV Woodenps4 AHU 2, 5 & 6 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 6.<br />

Convert Air Handlers to Direct Digital Control.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 243,707<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

-2,200<br />

Extended Bare<br />

Labor Cost ($)<br />

$56,290<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SZ CAV to VAV (63 points) 3 $11,063.41 $34,020 $6,743.98 $22,680<br />

7.5 hp VFD 2 $1,975.00 $4,049 $545.00 $1,222<br />

15 hp VFD 3 $2,275.00 $6,996 $820.00 $2,758<br />

25 hp VFD 1 $3,925.00 $4,023 $1,100.00 $1,233<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$49,087 $27,893<br />

$4,050<br />

$6,376<br />

$59,514<br />

$5,951<br />

$14,974<br />

$4,991<br />

$5,990<br />

N/A<br />

$3,347<br />

$31,240<br />

$3,124<br />

Totals: $65,465 $34,364<br />

Total Project Cost: $125,784<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $125,784<br />

Rebate/Incentive*:<br />

$56,290<br />

Net Project Cost: $69,494<br />

Net Simple Payback Period (yrs): 3.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

232,032<br />

0<br />

$20,419<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 (Mcquay) SP reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1031<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

27,011<br />

0.0<br />

0<br />

16,783<br />

452<br />

Equipment Description Qty<br />

\28. Woodenps4\4.. <strong>UC</strong>LA CVRH_VAV Woodenps4 AHU 1 (Mcquay) SP reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers & Air Handler Project 6.<br />

Convert Air Handlers to Direct Digital Control.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 40,437<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

5,650<br />

Extended Bare<br />

Labor Cost ($)<br />

$15,355<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

License Fee (estimated per 1000 CFM) 28 $0.00 $0 $56.00 $1,758<br />

CAV - RH to VAV - RH (17 points) 1 $8,956.10 $9,180 $5,459.41 $6,120<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$13,793 $15,893<br />

$1,138<br />

$1,792<br />

$16,722<br />

$1,672<br />

$5,696<br />

$1,899<br />

$2,278<br />

N/A<br />

$1,907<br />

$17,800<br />

$1,780<br />

Totals: $18,394 $19,580<br />

Total Project Cost: $47,848<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $47,848<br />

Rebate/Incentive*:<br />

$15,355<br />

Net Project Cost: $32,493<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

67,300<br />

0<br />

$5,922


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 Pace) SP reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1032<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

18,432<br />

0.0<br />

0<br />

10,943<br />

279<br />

Equipment Description Qty<br />

\28. Woodenps4\5.. <strong>UC</strong>LA CVRH_VAV Woodenps4 AHU 1 (Pace) SP reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

27,186<br />

3,488<br />

Extended Bare<br />

Labor Cost ($)<br />

$10,012<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Program SP Reset 16 $0.00 $0 $100.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$0 $1,794<br />

$0<br />

$0<br />

$0<br />

$0<br />

$331<br />

$110<br />

$133<br />

N/A<br />

$215<br />

$2,009<br />

$201<br />

Totals: $0 $2,210<br />

Total Project Cost: $2,784<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $2,784<br />

Rebate/Incentive*:<br />

$2,227<br />

Net Project Cost: $557<br />

Net Simple Payback Period (yrs): 0.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

43,721<br />

0<br />

$3,847


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 2 Pace) SP reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1033<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

20,078<br />

0.0<br />

0<br />

12,223<br />

331<br />

Equipment Description Qty<br />

\28. Woodenps4\6.. <strong>UC</strong>LA CVRH_VAV Woodenps4 AHU 2 (Pace) SP reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

29,856<br />

4,138<br />

Extended Bare<br />

Labor Cost ($)<br />

$11,303<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Program SP Reset 16 $0.00 $0 $100.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$0 $1,794<br />

$0<br />

$0<br />

$0<br />

$0<br />

$331<br />

$110<br />

$133<br />

N/A<br />

$215<br />

$2,009<br />

$201<br />

Totals: $0 $2,210<br />

Total Project Cost: $2,784<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $2,784<br />

Rebate/Incentive*:<br />

$2,227<br />

Net Project Cost: $557<br />

Net Simple Payback Period (yrs): 0.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

49,533<br />

0<br />

$4,359


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 4 CAV to VAV & DCV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1034<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

210,437<br />

50.0<br />

0<br />

2,584<br />

-282<br />

Equipment Description Qty<br />

\28. Woodenps4\7. DCV - SZ_VAV Woodenps4 AHU 4 CAV to VAV DCV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume, Air Handler Project 6.<br />

Convert Air Handlers to Direct Digital Control & Air Handler Project 3. Demand Control Ventilation.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

212,504<br />

-3,525<br />

$47,476<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Program DCV 4 $100.00 $448<br />

CO2 Sensor 1 $400.00 $410<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

75 hp VFD 1 $11,500.00 $11,788 $1,600.00 $1,794<br />

SZ CAV to VAV (21 points) 1 $11,063.41 $11,340 $6,743.98 $7,560<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$26,997 $10,721<br />

$2,227<br />

$3,507<br />

$32,731<br />

$3,273<br />

$7,382<br />

$2,461<br />

$2,953<br />

N/A<br />

$1,287<br />

$12,008<br />

$1,201<br />

Totals: $36,004 $13,209<br />

Total Project Cost: $62,008<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $62,008<br />

Rebate/Incentive*:<br />

$47,476<br />

Net Project Cost: $14,532<br />

Net Simple Payback Period (yrs): 0.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

194,701<br />

0<br />

$17,134<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 to 8 T-1 & T-2 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: UNEX<br />

Building Key: 04C4415<br />

Basic Gross Area (sf): 95,065<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1035<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

412,262<br />

21.0<br />

34,433<br />

Equipment Description Qty<br />

\29. Unex\1. <strong>UC</strong>LA MZ_DD_VAV Unex AHU 1 to 8 T-1 & T-2 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 1. Convert Constant Volume Air Handlers and Terminal Boxes to Variable Air Volume & Air<br />

Handler Project 6. Convert Air Handlers to Direct Digital Control.<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

412,262<br />

34,433<br />

$133,376<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

20 hp VFD 7 $3,375.00 $24,216 $820.00 $6,435<br />

7.5 hp VFD 2 $1,975.00 $4,049 $545.00 $1,222<br />

DD CAV to VAV (207 points) 9 $12,117.07 $111,780 $7,386.26 $74,520<br />

Zone Level Controller & DDC - dual duct 212 $4,097.56 $890,400 $2,497.77 $593,600<br />

DART Control 8 $8,710.00 $71,422 $2,900.00 $26,007<br />

Dart @ Zone 106 $440.00 $47,806 $128.00 $15,210<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$1,151,389 $717,503<br />

$94,990<br />

$149,565<br />

$1,395,944<br />

$139,594<br />

$362,925<br />

$120,975<br />

$145,170<br />

N/A<br />

$86,100<br />

$803,604<br />

$80,360<br />

Totals: $1,535,538 $883,964<br />

Total Project Cost: $3,048,573<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $3,048,573<br />

Rebate/Incentive*:<br />

$133,376<br />

Net Project Cost: $2,915,197<br />

Net Simple Payback Period (yrs): 52.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

627,124<br />

0<br />

$55,187<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 3 VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENTREP HALL<br />

Building Key: 04C515C<br />

Basic Gross Area (sf): 72,591<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1036<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

79,357<br />

1.0<br />

0<br />

33,987<br />

600<br />

Equipment Description Qty<br />

\3. Entrep Hall\1. <strong>UC</strong>LA CVRH_VAV Entrep Hall AHU 3 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

106,547<br />

7,500<br />

$33,071<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

30 hp VFD 1 $4,775.00 $4,894 $1,100.00 $1,233<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

License Fee (estimated per 1000 CFM) 36 $0.00 $0 $56.00 $2,260<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$11,839 $14,221<br />

$977<br />

$1,538<br />

$14,353<br />

$1,435<br />

$4,996<br />

$1,665<br />

$1,999<br />

N/A<br />

$1,707<br />

$15,928<br />

$1,593<br />

Totals: $15,789 $17,520<br />

Total Project Cost: $41,969<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,969<br />

Rebate/Incentive*:<br />

$33,071<br />

Net Project Cost: $8,898<br />

Net Simple Payback Period (yrs): 0.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

141,268<br />

0<br />

$12,432<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: VFD + DCV for a CAV system<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENTREP HALL<br />

Building Key: 04C515C<br />

Basic Gross Area (sf): 72,591<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1037<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

51,550<br />

2.0<br />

0<br />

3,161<br />

117<br />

Equipment Description Qty<br />

\3. Entrep Hall\2. <strong>UC</strong>LA DCV - SZ_VAV_60 Entrep Hall AHU 8 DCV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 3.<br />

Demand Control Ventilation.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 54,079<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

1,463<br />

Extended Bare<br />

Labor Cost ($)<br />

$14,441<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

Program DCV 4 $0.00 $0 $100.00<br />

$448<br />

CO2 sensor 1 $400.00 $410 $0.00<br />

$0<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$4,459 $1,878<br />

$368<br />

$579<br />

$5,406<br />

$541<br />

$1,239<br />

$413<br />

$496<br />

N/A<br />

$225<br />

$2,103<br />

$210<br />

Totals: $5,946 $2,313<br />

Total Project Cost: $10,407<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $10,407<br />

Rebate/Incentive*:<br />

$8,326<br />

Net Project Cost: $2,081<br />

Net Simple Payback Period (yrs): 0.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

61,127<br />

0<br />

$5,379


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-1, 5 & 6 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: JULES STEIN<br />

Building Key: 04C4333<br />

Basic Gross Area (sf): 87,905<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1038<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

279,911<br />

7.0<br />

0<br />

108,103<br />

2,196<br />

Equipment Description Qty<br />

\30. Jules Stein\1. <strong>UC</strong>LA MZ_DD_VAV Jules Stein S-1, 5 & 6 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

366,393<br />

27,450<br />

$115,384<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

20 hp VFD 4 $3,375.00 $13,838 $820.00 $3,677<br />

Dart Control 3 $8,710.00 $26,783 $2,900.00 $9,753<br />

Dart @ zone 33 $440.00 $14,883 $128.00 $4,735<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$55,504 $18,165<br />

$4,579<br />

$7,210<br />

$67,293<br />

$6,729<br />

$14,460<br />

$4,820<br />

$5,784<br />

N/A<br />

$2,180<br />

$20,344<br />

$2,034<br />

Totals: $74,022 $22,379<br />

Total Project Cost: $121,465<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $121,465<br />

Rebate/Incentive*:<br />

$97,172<br />

Net Project Cost: $24,293<br />

Net Simple Payback Period (yrs): 0.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

494,776<br />

0<br />

$43,540<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S2, 3 & 4Aircuity<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: JULES STEIN<br />

Building Key: 04C4333<br />

Basic Gross Area (sf): 87,905<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1039<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

102,285<br />

9.0<br />

0<br />

64,913<br />

1,358<br />

Equipment Description Qty<br />

\30. Jules Stein\2. <strong>UC</strong>LA HVAC Lab Julies Stein Aircuity.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to Variable Air Volume &<br />

Laboratory Air Handler Project 2. Rebalance Variable Air Volume Laboratory (or Vivarium) Air Handlers.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 154,215<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

16,975<br />

Extended Bare<br />

Labor Cost ($)<br />

$53,987<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Aircuity, per sensor 3 $2,500.00 $7,688 $2,000.00 $6,726<br />

0.5 hp VFD 13 $175.00 $2,332 $350.00 $5,101<br />

2 hp VFD 1 $700.00 $718 $400.00<br />

$448<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

Rebalance ($1.75 per square foot) 7,500 $0.00 $0 $1.75 $14,713<br />

Autosash closure 32 $2,700.00 $88,560 $1,800.00 $64,570<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$103,038 $92,679<br />

$8,501<br />

$13,385<br />

$124,923<br />

$12,492<br />

$37,739<br />

$12,580<br />

$15,096<br />

N/A<br />

$11,121<br />

$103,800<br />

$10,380<br />

Totals: $137,416 $114,180<br />

Total Project Cost: $317,011<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $317,011<br />

Rebate/Incentive*:<br />

$53,987<br />

Net Project Cost: $263,024<br />

Net Simple Payback Period (yrs): 12.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

233,762<br />

0<br />

$20,571<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU 1 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: M DAVIES CC<br />

Building Key: 04C4332E<br />

Basic Gross Area (sf): 70,228<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1040<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

24,750<br />

1.0<br />

0<br />

5,680<br />

184<br />

Equipment Description Qty<br />

\31. M Davies CC\1. <strong>UC</strong>LA MZ_DD_VAV M davies CC AHU 1 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

29,294<br />

2,300<br />

$9,331<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Dart Control 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

Dart @ zone 2 $440.00 $902 $128.00<br />

$287<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$11,854 $4,149<br />

$978<br />

$1,540<br />

$14,372<br />

$1,437<br />

$3,138<br />

$1,046<br />

$1,255<br />

N/A<br />

$498<br />

$4,647<br />

$465<br />

Totals: $15,809 $5,111<br />

Total Project Cost: $26,360<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $26,360<br />

Rebate/Incentive*:<br />

$9,331<br />

Net Project Cost: $17,029<br />

Net Simple Payback Period (yrs): 4.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

40,321<br />

0<br />

$3,548<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CAV to VAV - AHU S-2 to S-9<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PUBLIC HLTH<br />

Building Key: 04C4331<br />

Basic Gross Area (sf): 140,563<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1041<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

148,425<br />

12.0<br />

0<br />

59,890<br />

1,184<br />

Equipment Description Qty<br />

\32. Public Hlth\1. <strong>UC</strong>LA MZ_DD_VAV Public hlth S-2 to 9 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

196,337<br />

14,800<br />

$61,921<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Dart @ zone 60 $440.00 $27,060 $128.00 $8,609<br />

Dart Control 8 $8,710.00 $71,422 $2,900.00 $26,007<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$98,482 $34,616<br />

$8,125<br />

$12,793<br />

$119,400<br />

$11,940<br />

$26,098<br />

$8,699<br />

$10,439<br />

N/A<br />

$4,154<br />

$38,770<br />

$3,877<br />

Totals: $131,340 $42,648<br />

Total Project Cost: $219,224<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $219,224<br />

Rebate/Incentive*:<br />

$61,921<br />

Net Project Cost: $157,303<br />

Net Simple Payback Period (yrs): 6.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

265,427<br />

0<br />

$23,358<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CV Rebalance - S-1<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PUBLIC HLTH<br />

Building Key: 04C4331<br />

Basic Gross Area (sf): 140,563<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1042<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

0<br />

52,901<br />

881<br />

Equipment Description Qty<br />

\32. Public Hlth\2. <strong>UC</strong>LA HVAC Lab Public Hlth Vivarium CV Rebalance S-1.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 2. Rebalance Variable Air Volume Laboratory (or Vivarium) Air Handlers.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

42,321<br />

11,013<br />

Extended Bare<br />

Labor Cost ($)<br />

$21,169<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Rebalance ($1.75 per square foot) 8,756 $0.00 $0 $1.75 $17,177<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$0 $17,177<br />

$0<br />

$0<br />

$0<br />

$0<br />

$3,174<br />

$1,058<br />

$1,270<br />

N/A<br />

$2,061<br />

$19,238<br />

$1,924<br />

Totals: $0 $21,162<br />

Total Project Cost: $26,664<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $26,664<br />

Rebate/Incentive*:<br />

$21,169<br />

Net Project Cost: $5,495<br />

Net Simple Payback Period (yrs): 0.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

93,063<br />

0<br />

$8,190


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SF 1 & 2 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LAW<br />

Building Key: 04C4317<br />

Basic Gross Area (sf): 275,439<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1043<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

47,789<br />

0.0<br />

0<br />

6,684<br />

393<br />

Equipment Description Qty<br />

\33. LAW\1. <strong>UC</strong>LA CVRH_VAV LAW SF 1 & 2 SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

53,136<br />

4,913<br />

Extended Bare<br />

Labor Cost ($)<br />

$17,665<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 2 $4,500.00 $9,225 $7,150.00 $16,030<br />

License Fee (estimated per 1000 CFM) 66 $0.00 $0 $56.00 $4,143<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$9,225 $20,174<br />

$761<br />

$1,198<br />

$11,184<br />

$1,118<br />

$5,573<br />

$1,858<br />

$2,229<br />

N/A<br />

$2,421<br />

$22,594<br />

$2,259<br />

Totals: $12,303 $24,854<br />

Total Project Cost: $46,817<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,817<br />

Rebate/Incentive*:<br />

$17,665<br />

Net Project Cost: $29,152<br />

Net Simple Payback Period (yrs): 4.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

77,125<br />

0<br />

$6,787


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SF 3 & 7 VIV to VAV & SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LAW<br />

Building Key: 04C4317<br />

Basic Gross Area (sf): 275,439<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1044<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

139,406<br />

1.0<br />

0<br />

27,871<br />

526<br />

Equipment Description Qty<br />

\33. LAW\2. <strong>UC</strong>LA CVRH_VAV LAW SF 3 & 7 VIV to VAV & SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

161,703<br />

6,575<br />

$45,384<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

License Fee (estimated per 1000 CFM) 66 $0.00 $0 $56.00 $4,143<br />

VIV Removal 32 $0.00 $0 $100.00 $3,587<br />

60 hp VFD 1 $8,375.00 $8,584 $1,600.00 $1,794<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

40 hp VFD 1 $7,025.00 $7,201 $1,100.00 $1,233<br />

SAV with InCite 2 $4,500.00 $9,225 $7,150.00 $16,030<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$30,801 $28,626<br />

$2,541<br />

$4,001<br />

$37,343<br />

$3,734<br />

$11,452<br />

$3,817<br />

$4,581<br />

N/A<br />

$3,435<br />

$32,061<br />

$3,206<br />

Totals: $41,078 $35,267<br />

Total Project Cost: $96,194<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,194<br />

Rebate/Incentive*:<br />

$45,384<br />

Net Project Cost: $50,810<br />

Net Simple Payback Period (yrs): 3.0<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

192,296<br />

0<br />

$16,922<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-4 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LAW<br />

Building Key: 04C4317<br />

Basic Gross Area (sf): 275,439<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1045<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

16,081<br />

1.0<br />

0<br />

38,223<br />

449<br />

Equipment Description Qty<br />

\33. LAW\3. <strong>UC</strong>LA CVRH_VAV LAW S 4 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

46,659<br />

5,613<br />

Extended Bare<br />

Labor Cost ($)<br />

$16,811<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

3 hp VFD 1 $1,525.00 $1,563 $455.00<br />

$510<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

Dart Controls 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

Dart @ zones 3 $440.00 $1,353 $128.00<br />

$430<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$13,561 $4,701<br />

$1,119<br />

$1,762<br />

$16,441<br />

$1,644<br />

$3,582<br />

$1,194<br />

$1,433<br />

N/A<br />

$564<br />

$5,266<br />

$527<br />

Totals: $18,085 $5,792<br />

Total Project Cost: $30,085<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $30,085<br />

Rebate/Incentive*:<br />

$16,811<br />

Net Project Cost: $13,274<br />

Net Simple Payback Period (yrs): 2.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

71,619<br />

0<br />

$6,302


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-5 & 6 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LAW<br />

Building Key: 04C4317<br />

Basic Gross Area (sf): 275,439<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1046<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

115,646<br />

4.0<br />

0<br />

73,910<br />

834<br />

Equipment Description Qty<br />

\33. LAW\4. <strong>UC</strong>LA MZ_DD_VAV_60 LAW S-5 & 6 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

174,774<br />

10,425<br />

$52,371<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

DART Control 2 $8,710.00 $17,856 $2,900.00 $6,502<br />

Dart @ Zone 27 $440.00 $12,177 $128.00 $3,874<br />

20 hp VFD 2 $3,375.00 $6,919 $820.00 $1,838<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$36,951 $12,214<br />

$3,048<br />

$4,800<br />

$44,800<br />

$4,480<br />

$9,649<br />

$3,216<br />

$3,860<br />

N/A<br />

$1,466<br />

$13,680<br />

$1,368<br />

Totals: $49,280 $15,048<br />

Total Project Cost: $81,053<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $81,053<br />

Rebate/Incentive*:<br />

$52,371<br />

Net Project Cost: $28,682<br />

Net Simple Payback Period (yrs): 1.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

220,903<br />

0<br />

$19,439<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-8 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LAW<br />

Building Key: 04C4317<br />

Basic Gross Area (sf): 275,439<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1047<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

27,915<br />

1.0<br />

0<br />

12,057<br />

200<br />

Equipment Description Qty<br />

\33. LAW\5. <strong>UC</strong>LA CVRH_VAV LAW S 8 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

37,561<br />

2,500<br />

Extended Bare<br />

Labor Cost ($)<br />

$11,515<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

Dart Controls 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

Dart @ zones 3 $440.00 $1,353 $128.00<br />

$430<br />

3 hp VFD 1 $1,525.00 $1,563 $455.00<br />

$510<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$13,868 $4,802<br />

$1,144<br />

$1,801<br />

$16,814<br />

$1,681<br />

$3,662<br />

$1,221<br />

$1,465<br />

N/A<br />

$576<br />

$5,379<br />

$538<br />

Totals: $18,495 $5,917<br />

Total Project Cost: $30,759<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $30,759<br />

Rebate/Incentive*:<br />

$11,515<br />

Net Project Cost: $19,244<br />

Net Simple Payback Period (yrs): 4.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

49,076<br />

0<br />

$4,319


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SAF-1 & 2 SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: YOUNG LIBRY<br />

Building Key: 04C4203<br />

Basic Gross Area (sf): 305,919<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1048<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

141,010<br />

1.0<br />

0<br />

69,598<br />

2,791<br />

Equipment Description Qty<br />

\34. Young Libry\1. <strong>UC</strong>LA MZ_DD_VAV Young Libry SAF 1 & 2 SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

196,688<br />

34,888<br />

$82,093<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with Incite 2 $4,500.00 $9,225 $7,150.00 $16,030<br />

License Fee (estimated per 1000 CFM) 220 $0.00 $0 $56.00 $13,811<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$9,225 $29,841<br />

$761<br />

$1,198<br />

$11,184<br />

$1,118<br />

$7,360<br />

$2,453<br />

$2,944<br />

N/A<br />

$3,581<br />

$33,422<br />

$3,342<br />

Totals: $12,303 $36,764<br />

Total Project Cost: $61,824<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $61,824<br />

Rebate/Incentive*:<br />

$49,460<br />

Net Project Cost: $12,365<br />

Net Simple Payback Period (yrs): 0.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

365,279<br />

0<br />

$32,145<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SAF-3 to 8 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: YOUNG LIBRY<br />

Building Key: 04C4203<br />

Basic Gross Area (sf): 305,919<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1049<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

513,097<br />

63.0<br />

0<br />

199,569<br />

4,419<br />

Equipment Description Qty<br />

\34. Young Libry\2. <strong>UC</strong>LA MZ_DD_VAV Young Libry SAF 3 to 8 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

672,752<br />

55,238<br />

$216,698<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Dart @ Control 6 $8,710.00 $53,567 $2,900.00 $19,505<br />

Dart @ Zone 74 $440.00 $33,374 $128.00 $10,618<br />

20 hp VFD 5 $3,375.00 $17,297 $820.00 $4,596<br />

7.5 hp VFD 6 $1,975.00 $12,146 $545.00 $3,666<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$118,716 $39,305<br />

$9,794<br />

$15,421<br />

$143,931<br />

$14,393<br />

$31,012<br />

$10,337<br />

$12,405<br />

N/A<br />

$4,717<br />

$44,021<br />

$4,402<br />

Totals: $158,324 $48,423<br />

Total Project Cost: $260,501<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $260,501<br />

Rebate/Incentive*:<br />

$208,401<br />

Net Project Cost: $52,100<br />

Net Simple Payback Period (yrs): 0.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

932,532<br />

0<br />

$82,063<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SAF 9 CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: YOUNG LIBRY<br />

Building Key: 04C4203<br />

Basic Gross Area (sf): 305,919<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1050<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

46,394<br />

2.0<br />

0<br />

40,684<br />

410<br />

Equipment Description Qty<br />

\34. Young Libry\3. <strong>UC</strong>LA MZ_DD_VAV Young Libry SAF 9 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

78,941<br />

5,125<br />

Extended Bare<br />

Labor Cost ($)<br />

$24,071<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

Dart @ Control 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

Dart @ Zone 8 $440.00 $3,608 $128.00 $1,148<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$14,868 $5,318<br />

$1,227<br />

$1,931<br />

$18,026<br />

$1,803<br />

$3,957<br />

$1,319<br />

$1,583<br />

N/A<br />

$638<br />

$5,956<br />

$596<br />

Totals: $19,828 $6,552<br />

Total Project Cost: $33,239<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $33,239<br />

Rebate/Incentive*:<br />

$24,071<br />

Net Project Cost: $9,168<br />

Net Simple Payback Period (yrs): 1.0<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

101,270<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$8,912


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CAV to VAV - AHU 1, 2, 5W and 5E & Add Economizer<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PERLOFF HALL<br />

Building Key: 04C4202<br />

Basic Gross Area (sf): 65,909<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1051<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

104,141<br />

4.0<br />

0<br />

145,777<br />

304<br />

Equipment Description Qty<br />

\35. Perloff Hall\1. <strong>UC</strong>LA MZ_DD_VAV Perloff Hall AHU 1, 2, 5W & 5E CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 9.<br />

Add Air Side Economizer.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 220,763<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

3,800<br />

Extended Bare<br />

Labor Cost ($)<br />

$56,783<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

5 hp VFD 4 $1,675.00 $6,868 $455.00 $2,040<br />

10 hp VFD 2 $1,975.00 $4,049 $545.00 $1,222<br />

Dart Control 4 $8,710.00 $35,711 $2,900.00 $13,004<br />

Dart @ zone 25 $440.00 $11,275 $128.00 $3,587<br />

Economizer 4 $9,000.00 $36,900 $6,000.00 $26,904<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$94,802 $46,757<br />

$7,821<br />

$12,315<br />

$114,938<br />

$11,494<br />

$27,605<br />

$9,202<br />

$11,042<br />

N/A<br />

$5,611<br />

$52,368<br />

$5,237<br />

Totals: $126,432 $57,605<br />

Total Project Cost: $231,886<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $231,886<br />

Rebate/Incentive*:<br />

$56,783<br />

Net Project Cost: $175,103<br />

Net Simple Payback Period (yrs): 8.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

228,070<br />

0<br />

$20,070<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-1 to 11 except 9 - CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BOELTER HALL<br />

Building Key: 04C4343<br />

Basic Gross Area (sf): 373,904<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1052<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

557,218<br />

15.0<br />

0<br />

320,081<br />

10,256<br />

Equipment Description Qty<br />

\36. Boelter Hall\1. <strong>UC</strong>LA MZ_DD_VAV Boelter Hall S-1 to 11 except 9 - CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

813,283<br />

128,200<br />

$323,388<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Dart Control 10 $8,710.00 $89,278 $2,900.00 $32,509<br />

3 hp VFD 3 $1,525.00 $4,689 $455.00 $1,530<br />

Dart @ zone 95 $440.00 $42,845 $128.00 $13,631<br />

5 hp VFD 2 $1,675.00 $3,434 $455.00 $1,020<br />

2 hp VFD 2 $700.00 $1,435 $400.00<br />

$897<br />

10 hp VFD 5 $1,975.00 $10,122 $545.00 $3,055<br />

15 hp VFD 4 $2,275.00 $9,328 $820.00 $3,677<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$161,130 $56,319<br />

$13,293<br />

$20,931<br />

$195,354<br />

$19,535<br />

$42,641<br />

$14,214<br />

$17,056<br />

N/A<br />

$6,758<br />

$63,077<br />

$6,308<br />

Totals: $214,889 $69,385<br />

Total Project Cost: $358,186<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $358,186<br />

Rebate/Incentive*:<br />

$286,549<br />

Net Project Cost: $71,637<br />

Net Simple Payback Period (yrs): 0.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,427,651<br />

0<br />

$125,633<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AH 4 to 7, 10 to 12 - SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BOELTER HALL<br />

Building Key: 04C4343<br />

Basic Gross Area (sf): 373,904<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1053<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

291,309<br />

2.0<br />

0<br />

166,363<br />

5,187<br />

Equipment Description Qty<br />

\36. Boelter Hall\2. <strong>UC</strong>LA CVRH_VAV Boelter Hall AH 4 to 7, 10 to 12 - SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

424,399<br />

64,838<br />

$166,693<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 7 $4,500.00 $32,288 $7,150.00 $56,106<br />

License Fee (estimated per 1000 CFM) 203 $0.00 $0 $56.00 $12,744<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$32,288 $68,850<br />

$2,664<br />

$4,194<br />

$39,145<br />

$3,915<br />

$19,182<br />

$6,394<br />

$7,673<br />

N/A<br />

$8,262<br />

$77,112<br />

$7,711<br />

Totals: $43,060 $84,823<br />

Total Project Cost: $161,132<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $161,132<br />

Rebate/Incentive*:<br />

$128,906<br />

Net Project Cost: $32,226<br />

Net Simple Payback Period (yrs): 0.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

734,759<br />

0<br />

$64,659<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-1, 5, 9, 10 to 12<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GEOLOGY<br />

Building Key: 04C4228A<br />

Basic Gross Area (sf): 182,149<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1054<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

181,337<br />

5.0<br />

0<br />

80,248<br />

2,026<br />

Equipment Description Qty<br />

\37. Geology\1. <strong>UC</strong>LA MZ_DD_VAV GEOLOGY S-1, 5, 9, 10 to 12 CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

245,535<br />

25,325<br />

$84,253<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Dart Control 6 $8,710.00 $53,567 $2,900.00 $19,505<br />

Dart @ zone 31 $440.00 $13,981 $128.00 $4,448<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

7.5 hp VFD 4 $1,975.00 $8,098 $545.00 $2,444<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$79,386 $27,518<br />

$6,549<br />

$10,312<br />

$96,248<br />

$9,625<br />

$20,966<br />

$6,989<br />

$8,387<br />

N/A<br />

$3,302<br />

$30,821<br />

$3,082<br />

Totals: $105,873 $33,903<br />

Total Project Cost: $176,117<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $176,117<br />

Rebate/Incentive*:<br />

$84,253<br />

Net Project Cost: $91,864<br />

Net Simple Payback Period (yrs): 2.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

365,538<br />

0<br />

$32,167<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: S-1(Geophysics)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GEOLOGY<br />

Building Key: 04C4228A<br />

Basic Gross Area (sf): 182,149<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1055<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

71,548<br />

2.0<br />

0<br />

54,628<br />

1,817<br />

Equipment Description Qty<br />

\37. Geology\2. <strong>UC</strong>LA MZ_DD_VAV GEOLOGY S-1(Geophysics) CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

115,250<br />

22,713<br />

$50,373<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

Dart Control 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

Dart @ zone 17 $440.00 $7,667 $128.00 $2,439<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$20,644 $7,119<br />

$1,703<br />

$2,682<br />

$25,028<br />

$2,503<br />

$5,445<br />

$1,815<br />

$2,178<br />

N/A<br />

$854<br />

$7,974<br />

$797<br />

Totals: $27,531 $8,771<br />

Total Project Cost: $45,741<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $45,741<br />

Rebate/Incentive*:<br />

$36,593<br />

Net Project Cost: $9,148<br />

Net Simple Payback Period (yrs): 0.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,261<br />

0<br />

$19,735<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Aircuity<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GEOLOGY<br />

Building Key: 04C4228A<br />

Basic Gross Area (sf): 182,149<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1056<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

7,207<br />

Equipment Description Qty<br />

\37. Geology\3. <strong>UC</strong>LA HVAC Lab GEOLOGY Aircuity.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to Variable Air Volume &<br />

Laboratory Air Handler Project 2. Rebalance Variable Air Volume Laboratory (or Vivarium) Air Handlers.<br />

1.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 7,207<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

$1,730<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

2 hp VFD 1 $700.00 $718 $400.00<br />

$448<br />

Aircuity, per sensor 2 $2,500.00 $5,125 $2,000.00 $4,484<br />

Rebalance 5,000 $0.00 $0 $1.75 $9,809<br />

0.25 hp VFD 21 $87.50 $1,883 $350.00 $8,239<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$7,726 $22,981<br />

$637<br />

$1,004<br />

$9,367<br />

$937<br />

$5,792<br />

$1,931<br />

$2,317<br />

N/A<br />

$2,758<br />

$25,738<br />

$2,574<br />

Totals: $10,304 $28,312<br />

Total Project Cost: $48,656<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $48,656<br />

Rebate/Incentive*:<br />

$1,730<br />

Net Project Cost: $46,926<br />

Net Simple Payback Period (yrs): 74.0<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

7,207<br />

0<br />

$634<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 4 VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CORNELL HALL<br />

Building Key: 04C515D<br />

Basic Gross Area (sf): 71,737<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1057<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

70,904<br />

0.0<br />

0<br />

30,662<br />

549<br />

Equipment Description Qty<br />

\4. Cornell Hall\1. <strong>UC</strong>LA CVRH_VAV Cornell Hall AHU 4 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

95,434<br />

6,863<br />

Extended Bare<br />

Labor Cost ($)<br />

$29,767<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

40 hp VFD 1 $7,025.00 $7,201 $1,100.00 $1,233<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

License Fee (estimated per 1000 CFM) 33 $0.00 $0 $56.00 $2,072<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$14,145 $14,033<br />

$1,167<br />

$1,837<br />

$17,149<br />

$1,715<br />

$5,423<br />

$1,808<br />

$2,169<br />

N/A<br />

$1,684<br />

$15,717<br />

$1,572<br />

Totals: $18,864 $17,288<br />

Total Project Cost: $45,552<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $45,552<br />

Rebate/Incentive*:<br />

$29,767<br />

Net Project Cost: $15,785<br />

Net Simple Payback Period (yrs): 1.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

127,238<br />

0<br />

$11,197<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 6 VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ROSNFLD LIBR<br />

Building Key: 04C515E<br />

Basic Gross Area (sf): 51,046<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1058<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

77,567<br />

1.0<br />

0<br />

33,154<br />

582<br />

Equipment Description Qty<br />

\5. Rosnfld LBR\1. <strong>UC</strong>LA CVRH_VAV Rosnfld LBR AHU 6 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

104,090<br />

7,275<br />

$32,257<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

40 hp VFD 1 $7,025.00 $7,201 $1,100.00 $1,233<br />

SAV with InCite 1 $4,500.00 $4,613 $7,150.00 $8,015<br />

License Fee (estimated per 1000 CFM) 35 $0.00 $0 $56.00 $2,197<br />

VIV Removal 16 $0.00 $0 $100.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$15,273 $14,158<br />

$1,260<br />

$1,984<br />

$18,516<br />

$1,852<br />

$5,672<br />

$1,891<br />

$2,269<br />

N/A<br />

$1,699<br />

$15,857<br />

$1,586<br />

Totals: $20,368 $17,443<br />

Total Project Cost: $47,642<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $47,642<br />

Rebate/Incentive*:<br />

$32,257<br />

Net Project Cost: $15,385<br />

Net Simple Payback Period (yrs): 1.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

137,755<br />

0<br />

$12,122<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 5 & 10 VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MULLIN CMNS<br />

Building Key: 04C515F<br />

Basic Gross Area (sf): 33,957<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1059<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

82,155<br />

1.0<br />

0<br />

34,737<br />

599<br />

Equipment Description Qty<br />

\6. Mullin CMNS\1. <strong>UC</strong>LA CVRH_VAV Mullin CMNS AHU 5 & 10 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

109,945<br />

7,488<br />

$33,874<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

License Fee (estimated per 1000 CFM) 36 $0.00 $0 $56.00 $2,260<br />

VIV Removal 32 $0.00 $0 $100.00 $3,587<br />

25 hp VFD 1 $3,925.00 $4,023 $1,100.00 $1,233<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

SAV with InCite 2 $4,500.00 $9,225 $7,150.00 $16,030<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$20,756 $25,252<br />

$1,712<br />

$2,696<br />

$25,165<br />

$2,516<br />

$8,819<br />

$2,940<br />

$3,527<br />

N/A<br />

$3,030<br />

$28,282<br />

$2,828<br />

Totals: $27,681 $31,110<br />

Total Project Cost: $74,077<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $74,077<br />

Rebate/Incentive*:<br />

$33,874<br />

Net Project Cost: $40,203<br />

Net Simple Payback Period (yrs): 3.2<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

144,543<br />

0<br />

$12,720<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Apply DDC controls, convert to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BUNCHE HALL<br />

Building Key: 04C4580<br />

Basic Gross Area (sf): 229,248<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1060<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

1,411,691<br />

67.0<br />

0<br />

0<br />

7,204<br />

Equipment Description Qty<br />

\7. Bunche Hall\1. <strong>UC</strong>LA MZ_DD_VAV_60 Bunche Hall CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 1. Convert Constant Volume Air Handlers and Terminal Boxes to Variable Air Volume & Air<br />

Handler Project 6. Convert Air Handlers to Direct Digital Control.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

1,411,691<br />

90,050<br />

$428,856<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

30 hp VFD 2 $4,775.00 $9,789 $1,100.00 $2,466<br />

5 hp VFD 5 $1,675.00 $8,584 $455.00 $2,550<br />

Zone Level Typical DD Controls: DD Mixing Box 211 $5,597.56 $1,210,612 $3,997.77 $945,597<br />

40 hp VFD 3 $7,025.00 $21,602 $1,100.00 $3,699<br />

25 hp VFD 1 $3,925.00 $4,023 $1,100.00 $1,233<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

7.5 hp VFD 2 $1,975.00 $4,049 $545.00 $1,222<br />

75 hp VFD 1 $11,500.00 $11,788 $1,600.00 $1,794<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$1,275,930 $960,091<br />

$105,264<br />

$165,743<br />

$1,546,938<br />

$154,694<br />

$432,670<br />

$144,223<br />

$173,068<br />

N/A<br />

$115,211<br />

$1,075,302<br />

$107,530<br />

Totals: $1,701,632 $1,182,832<br />

Total Project Cost: $3,634,425<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $3,634,425<br />

Rebate/Incentive*:<br />

$428,856<br />

Net Project Cost: $3,205,569<br />

Net Simple Payback Period (yrs): 19.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,861,221<br />

0<br />

$163,787<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: AHU - 1, 2 & 3 VIV to VAV SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: DORIS STEIN<br />

Building Key: 04C4325<br />

Basic Gross Area (sf): 94,309<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1061<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

159,060<br />

1.0<br />

0<br />

60,756<br />

860<br />

Equipment Description Qty<br />

\8. Doris Stein\1. <strong>UC</strong>LA CVRH_VAV Doris Stein AHU 1, 2 & 3 VIV to VAV SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume & Air Handler Project 4.<br />

Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

207,665<br />

10,750<br />

$60,590<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

License Fee (estimated per 1000 CFM) 51 $0.00 $0 $56.00 $3,202<br />

VIV Removal 48 $0.00 $0 $100.00 $5,381<br />

30 hp VFD 1 $4,775.00 $4,894 $1,100.00 $1,233<br />

25 hp VFD 2 $3,925.00 $8,046 $1,100.00 $2,466<br />

20 hp VFD 1 $3,375.00 $3,459 $820.00<br />

$919<br />

10 hp VFD 2 $1,975.00 $4,049 $545.00 $1,222<br />

SAV with InCite 3 $4,500.00 $13,838 $7,150.00 $24,045<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$34,286 $38,468<br />

$2,829<br />

$4,454<br />

$41,569<br />

$4,157<br />

$13,968<br />

$4,656<br />

$5,587<br />

N/A<br />

$4,616<br />

$43,084<br />

$4,308<br />

Totals: $45,726 $47,393<br />

Total Project Cost: $117,329<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $117,329<br />

Rebate/Incentive*:<br />

$60,590<br />

Net Project Cost: $56,739<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

256,468<br />

0<br />

$22,569<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: ACS - 1 to 5 - SP Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENGR BLDG 4<br />

Building Key: 04C4256A<br />

Basic Gross Area (sf): 294,124<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1062<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

283,121<br />

3.0<br />

0<br />

155,143<br />

3,127<br />

Equipment Description Qty<br />

\9. Engineering IV\1. <strong>UC</strong>LA CVRH_VAV Engineering IV ACS 1 to 5 - SP Reset.xls<br />

Project Description Reference(s): Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers .<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

407,235<br />

39,088<br />

$136,824<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

SAV with InCite 5 $4,500.00 $23,063 $7,150.00 $40,076<br />

License Fee (estimated per 1000 CFM) 267 $0.00 $0 $56.00 $16,761<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$23,063 $56,837<br />

$1,903<br />

$2,996<br />

$27,961<br />

$2,796<br />

$15,117<br />

$5,039<br />

$6,047<br />

N/A<br />

$6,820<br />

$63,657<br />

$6,366<br />

Totals: $30,757 $70,023<br />

Total Project Cost: $126,983<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $126,983<br />

Rebate/Incentive*:<br />

$101,586<br />

Net Project Cost: $25,397<br />

Net Simple Payback Period (yrs): 0.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

589,949<br />

0<br />

$51,915<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: ACS 8 (AHU-3) - Aircruity<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENGR BLDG 4<br />

Building Key: 04C4256A<br />

Basic Gross Area (sf): 294,124<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1063<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

242,891<br />

22.0<br />

0<br />

162,129<br />

3,191<br />

Equipment Description Qty<br />

\9. Engineering IV\2. <strong>UC</strong>LA HVAC Lab Engineering IV ACS 8 - Aircuity.xls<br />

Project Description Reference(s): Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to Variable Air Volume &<br />

Laboratory Air Handler Project 2. Rebalance Variable Air Volume Laboratory (or Vivarium) Air Handlers.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 372,594<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

39,888<br />

Extended Bare<br />

Labor Cost ($)<br />

$129,310<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

0.5 hp VFD 11 $175.00 $1,973 $350.00 $4,316<br />

1 hp VFD 5 $350.00 $1,794 $400.00 $2,242<br />

0.25 hp VFD 1 $87.50 $90 $350.00<br />

$392<br />

3 hp VFD 2 $1,525.00 $3,126 $455.00 $1,020<br />

Aircuity, per sensor 15 $2,500.00 $38,438 $2,000.00 $33,630<br />

Autosash closure 30 $2,700.00 $83,025 $1,800.00 $60,534<br />

Fume Hood Conversion - CAV to VAV 30 $11,250.00 $345,938 $11,250.00 $378,338<br />

7.5 hp VFD 2 $1,975.00 $4,049 $545.00 $1,222<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$478,432 $481,694<br />

$39,471<br />

$62,148<br />

$580,050<br />

$58,005<br />

$184,725<br />

$61,575<br />

$73,890<br />

N/A<br />

$57,803<br />

$539,497<br />

$53,950<br />

Totals: $638,055 $593,447<br />

Total Project Cost: $1,551,693<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $1,551,693<br />

Rebate/Incentive*:<br />

$129,310<br />

Net Project Cost: $1,422,383<br />

Net Simple Payback Period (yrs): 28.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

558,742<br />

0<br />

$49,169<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CF - 1 to 22 - VIV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENGR BLDG 4<br />

Building Key: 04C4256A<br />

Basic Gross Area (sf): 294,124<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1064<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

743,261<br />

143.0<br />

0<br />

601,695<br />

Equipment Description Qty<br />

\9. Engineering IV\3. <strong>UC</strong>LA CVRH_VAV Engineering IV CF - 1 to 22 - VIV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

1,224,617<br />

0<br />

$293,908<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

30 hp VFD 4 $4,775.00 $19,578 $1,100.00 $4,932<br />

VIV Removal 352 $0.00 $0 $100.00 $39,459<br />

Dart @ Zone 22 $440.00 $9,922 $128.00 $3,157<br />

2 hp VFD 1 $700.00 $718 $400.00<br />

$448<br />

Dart Control 22 $8,710.00 $196,411 $2,900.00 $71,520<br />

50 hp VFD 2 $7,650.00 $15,683 $1,375.00 $3,083<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

5 hp VFD 1 $1,675.00 $1,717 $455.00<br />

$510<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

20 hp VFD 3 $3,375.00 $10,378 $820.00 $2,758<br />

25 hp VFD 4 $3,925.00 $16,093 $1,100.00 $4,932<br />

40 hp VFD 6 $7,025.00 $43,204 $1,100.00 $7,399<br />

7.5 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$320,082 $140,339<br />

$26,407<br />

$41,579<br />

$388,067<br />

$38,807<br />

$89,966<br />

$29,989<br />

$35,986<br />

N/A<br />

$16,841<br />

$157,180<br />

$15,718<br />

Totals: $426,874 $172,898<br />

Total Project Cost: $755,712<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $755,712<br />

Rebate/Incentive*:<br />

$293,908<br />

Net Project Cost: $461,804<br />

Net Simple Payback Period (yrs): 4.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,176,481<br />

0<br />

$103,530<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: ACS 9 - CAV to VAV<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENGR BLDG 4<br />

Building Key: 04C4256A<br />

Basic Gross Area (sf): 294,124<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D1065<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

25,138<br />

4.0<br />

0<br />

39,788<br />

815<br />

Equipment Description Qty<br />

\9. Engineering IV\4. <strong>UC</strong>LA CVRH_VAV Engineering IV ACS 9 - CAV to VAV.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume.<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

56,968<br />

10,188<br />

Extended Bare<br />

Labor Cost ($)<br />

$23,860<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Dart @ Zone 8 $440.00 $3,608 $128.00 $1,148<br />

Dart Control 1 $8,710.00 $8,928 $2,900.00 $3,251<br />

10 hp VFD 1 $1,975.00 $2,024 $545.00<br />

$611<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$14,560 $5,010<br />

$1,201<br />

$1,891<br />

$17,653<br />

$1,765<br />

$3,838<br />

$1,279<br />

$1,535<br />

N/A<br />

$601<br />

$5,611<br />

$561<br />

Totals: $19,418 $6,172<br />

Total Project Cost: $32,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $32,243<br />

Rebate/Incentive*:<br />

$23,860<br />

Net Project Cost: $8,383<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

104,641<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$9,208


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Outpatient Wing Seismic Renovation<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: MED PLZA 100<br />

Building Key: 04C4006<br />

Basic Gross Area (sf): 50,679<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3001<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

388,131<br />

44.0<br />

36,365<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

388,131<br />

36,365<br />

$129,516<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$204,957<br />

$51,239<br />

$76,859<br />

$25,620<br />

$30,743<br />

N/A<br />

$204,956<br />

$51,239<br />

Totals: $256,196 $256,195<br />

Total Project Cost: $645,613<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $645,613<br />

Rebate/Incentive*:<br />

$129,516<br />

Net Project Cost: $516,097<br />

Net Simple Payback Period (yrs): 9.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

615,049<br />

0<br />

$54,124<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Lake Arrowhead Facility Improvements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ARWHD LODGE<br />

Building Key: 04C4201<br />

Basic Gross Area (sf): 17,785<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3002<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

45,881<br />

5.0<br />

4,299<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

45,881<br />

4,299<br />

Extended Bare<br />

Labor Cost ($)<br />

$15,310<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$24,227<br />

$2,423<br />

$7,995<br />

$2,665<br />

$3,198<br />

N/A<br />

$24,227<br />

$2,423<br />

Totals: $26,650 $26,650<br />

Total Project Cost: $67,157<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $67,157<br />

Rebate/Incentive*:<br />

$15,310<br />

Net Project Cost: $51,847<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

72,707<br />

0<br />

$6,398


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PERLOFF HALL<br />

Building Key: 04C4202<br />

Basic Gross Area (sf): 65,909<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3003<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

50,750<br />

6.0<br />

6,920<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

50,750<br />

6,920<br />

Extended Bare<br />

Labor Cost ($)<br />

$19,100<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$10,051<br />

$1,005<br />

$6,634<br />

$2,211<br />

$2,653<br />

N/A<br />

$30,153<br />

$3,015<br />

Totals: $11,056 $33,168<br />

Total Project Cost: $55,723<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $55,723<br />

Rebate/Incentive*:<br />

$19,100<br />

Net Project Cost: $36,623<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

93,931<br />

0<br />

$8,266


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: YOUNG LIBRY<br />

Building Key: 04C4203<br />

Basic Gross Area (sf): 305,919<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3004<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

235,558<br />

27.0<br />

32,121<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

235,558<br />

32,121<br />

$88,655<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$46,653<br />

$4,665<br />

$30,791<br />

$10,264<br />

$12,316<br />

N/A<br />

$139,958<br />

$13,996<br />

Totals: $51,318 $153,954<br />

Total Project Cost: $258,643<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $258,643<br />

Rebate/Incentive*:<br />

$88,655<br />

Net Project Cost: $169,988<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

435,993<br />

0<br />

$38,367<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Young Research Library Renovation<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: YOUNG LIBRY<br />

Building Key: 04C4203<br />

Basic Gross Area (sf): 305,919<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3005<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

302,198<br />

34.0<br />

28,314<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

302,198<br />

28,314<br />

$100,842<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$159,579<br />

$15,958<br />

$52,661<br />

$17,554<br />

$21,064<br />

N/A<br />

$159,579<br />

$15,958<br />

Totals: $175,537 $175,537<br />

Total Project Cost: $442,353<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $442,353<br />

Rebate/Incentive*:<br />

$100,842<br />

Net Project Cost: $341,511<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

478,877<br />

0<br />

$42,141<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Pauley Pavilion Renovation and Expansion<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PAULEY<br />

Building Key: 04C4204<br />

Basic Gross Area (sf): 204,465<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3006<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

784,215<br />

90.0<br />

73,476<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

784,215<br />

73,476<br />

$261,688<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$414,113<br />

$41,411<br />

$136,657<br />

$45,552<br />

$54,663<br />

N/A<br />

$414,113<br />

$41,411<br />

Totals: $455,524 $455,524<br />

Total Project Cost: $1,147,921<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $1,147,921<br />

Rebate/Incentive*:<br />

$261,688<br />

Net Project Cost: $886,233<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,242,705<br />

0<br />

$109,358<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - CHS Parking E General Clinical Research<br />

<strong>Center</strong>/Biomarker Seismic Renovation<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG ST CHS<br />

Building Key: 04C4211<br />

Basic Gross Area (sf): 652,811<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3007<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

160,920<br />

18.0<br />

7,668<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

160,920<br />

7,668<br />

$46,289<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$67,603<br />

$6,760<br />

$22,309<br />

$7,436<br />

$8,924<br />

N/A<br />

$67,602<br />

$6,760<br />

Totals: $74,363 $74,362<br />

Total Project Cost: $187,394<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $187,394<br />

Rebate/Incentive*:<br />

$46,289<br />

Net Project Cost: $141,105<br />

Net Simple Payback Period (yrs): 7.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

208,768<br />

0<br />

$18,372<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GEOLOGY<br />

Building Key: 04C4228A<br />

Basic Gross Area (sf): 182,149<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3008<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

344,262<br />

39.0<br />

36,976<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

344,262<br />

36,976<br />

$119,599<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$55,555<br />

$5,556<br />

$36,666<br />

$12,222<br />

$14,667<br />

N/A<br />

$166,666<br />

$16,667<br />

Totals: $61,111 $183,333<br />

Total Project Cost: $307,998<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $307,998<br />

Rebate/Incentive*:<br />

$119,599<br />

Net Project Cost: $188,399<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

574,992<br />

0<br />

$50,599<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MOLECULR SCI<br />

Building Key: 04C4228C<br />

Basic Gross Area (sf): 178,666<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3009<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

337,679<br />

38.0<br />

36,269<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

337,679<br />

36,269<br />

$117,312<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$54,493<br />

$5,449<br />

$35,965<br />

$11,988<br />

$14,386<br />

N/A<br />

$163,479<br />

$16,348<br />

Totals: $59,942 $179,827<br />

Total Project Cost: $302,109<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $302,109<br />

Rebate/Incentive*:<br />

$117,312<br />

Net Project Cost: $184,797<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

563,998<br />

0<br />

$49,632<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Police Station Replacement Building<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: POLICE STN<br />

Building Key: 04C4230<br />

Basic Gross Area (sf): 11,617<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3010<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

74,296<br />

8.0<br />

6,961<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

74,296<br />

6,961<br />

Extended Bare<br />

Labor Cost ($)<br />

$24,792<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$39,232<br />

$3,923<br />

$12,946<br />

$4,315<br />

$5,179<br />

N/A<br />

$39,231<br />

$3,923<br />

Totals: $43,155 $43,154<br />

Total Project Cost: $108,750<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $108,750<br />

Rebate/Incentive*:<br />

$24,792<br />

Net Project Cost: $83,958<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

117,733<br />

0<br />

$10,360<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3011<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

159,945<br />

18.0<br />

21,811<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

159,945<br />

21,811<br />

$60,198<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$31,677<br />

$3,168<br />

$20,907<br />

$6,969<br />

$8,363<br />

N/A<br />

$95,032<br />

$9,503<br />

Totals: $34,845 $104,535<br />

Total Project Cost: $175,619<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $175,619<br />

Rebate/Incentive*:<br />

$60,198<br />

Net Project Cost: $115,421<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

296,046<br />

0<br />

$26,052<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Dykstra Repairs and Refurbishment<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: DYKSTRA HALL<br />

Building Key: 04C4246<br />

Basic Gross Area (sf): 163,262<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3012<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

1,503,493<br />

172.0<br />

71,643<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

1,503,493<br />

71,643<br />

$432,481<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$631,607<br />

$63,161<br />

$208,430<br />

$69,477<br />

$83,372<br />

N/A<br />

$631,606<br />

$63,161<br />

Totals: $694,768 $694,767<br />

Total Project Cost: $1,750,813<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $1,750,813<br />

Rebate/Incentive*:<br />

$432,481<br />

Net Project Cost: $1,318,332<br />

Net Simple Payback Period (yrs): 7.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,950,545<br />

0<br />

$171,648<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENGR BLDG 4<br />

Building Key: 04C4256A<br />

Basic Gross Area (sf): 294,124<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3013<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

555,894<br />

64.0<br />

59,707<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

555,894<br />

59,707<br />

$193,122<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$89,708<br />

$8,971<br />

$59,207<br />

$19,736<br />

$23,683<br />

N/A<br />

$269,123<br />

$26,912<br />

Totals: $98,679 $296,035<br />

Total Project Cost: $497,340<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $497,340<br />

Rebate/Incentive*:<br />

$193,122<br />

Net Project Cost: $304,218<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

928,466<br />

0<br />

$81,705<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FACMGMT BLDG<br />

Building Key: 04C4260<br />

Basic Gross Area (sf): 189,197<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3014<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

145,682<br />

17.0<br />

19,866<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

145,682<br />

19,866<br />

$54,830<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$28,853<br />

$2,885<br />

$19,043<br />

$6,348<br />

$7,617<br />

N/A<br />

$86,558<br />

$8,656<br />

Totals: $31,738 $95,214<br />

Total Project Cost: $159,960<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $159,960<br />

Rebate/Incentive*:<br />

$54,830<br />

Net Project Cost: $105,130<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

269,646<br />

0<br />

$23,729<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: TIVERTON HSE<br />

Building Key: 04C4265<br />

Basic Gross Area (sf): 121,634<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3015<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

44,062<br />

5.0<br />

6,009<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

44,062<br />

6,009<br />

Extended Bare<br />

Labor Cost ($)<br />

$16,584<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$8,727<br />

$873<br />

$5,760<br />

$1,920<br />

$2,304<br />

N/A<br />

$26,180<br />

$2,618<br />

Totals: $9,600 $28,798<br />

Total Project Cost: $48,381<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $48,381<br />

Rebate/Incentive*:<br />

$16,584<br />

Net Project Cost: $31,797<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

81,558<br />

0<br />

$7,177


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WILSHIRE CTR<br />

Building Key: 04C4270<br />

Basic Gross Area (sf): 455,912<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3016<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

242,710<br />

28.0<br />

33,097<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

242,710<br />

33,097<br />

$91,347<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,069<br />

$4,807<br />

$31,726<br />

$10,575<br />

$12,690<br />

N/A<br />

$144,208<br />

$14,421<br />

Totals: $52,876 $158,629<br />

Total Project Cost: $266,496<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $266,496<br />

Rebate/Incentive*:<br />

$91,347<br />

Net Project Cost: $175,149<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

449,235<br />

0<br />

$39,533<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Rieber Repairs and Refurbishment<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: RIEBER HALL<br />

Building Key: 04C4298<br />

Basic Gross Area (sf): 199,076<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3017<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

490,519<br />

56.0<br />

45,959<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

490,519<br />

45,959<br />

$163,684<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$259,025<br />

$25,903<br />

$85,478<br />

$28,493<br />

$34,191<br />

N/A<br />

$259,024<br />

$25,902<br />

Totals: $284,928 $284,926<br />

Total Project Cost: $718,016<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $718,016<br />

Rebate/Incentive*:<br />

$163,684<br />

Net Project Cost: $554,332<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

777,303<br />

0<br />

$68,403<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Hedrick Repairs and Refurbishment<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: HEDRICK HALL<br />

Building Key: 04C4299<br />

Basic Gross Area (sf): 198,485<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3018<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

458,131<br />

52.0<br />

42,924<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

458,131<br />

42,924<br />

$152,875<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$241,920<br />

$24,192<br />

$79,834<br />

$26,611<br />

$31,933<br />

N/A<br />

$241,920<br />

$24,192<br />

Totals: $266,112 $266,112<br />

Total Project Cost: $670,602<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $670,602<br />

Rebate/Incentive*:<br />

$152,875<br />

Net Project Cost: $517,727<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

725,977<br />

0<br />

$63,886<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CANYON POINT<br />

Building Key: 04C4302A<br />

Basic Gross Area (sf): 107,419<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3019<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

82,713<br />

9.0<br />

11,279<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

82,713<br />

11,279<br />

Extended Bare<br />

Labor Cost ($)<br />

$31,130<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$16,381<br />

$1,638<br />

$10,812<br />

$3,604<br />

$4,325<br />

N/A<br />

$49,144<br />

$4,914<br />

Totals: $18,019 $54,058<br />

Total Project Cost: $90,818<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $90,818<br />

Rebate/Incentive*:<br />

$31,130<br />

Net Project Cost: $59,688<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

153,094<br />

0<br />

$13,472<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: COVEL COMMON<br />

Building Key: 04C4302D<br />

Basic Gross Area (sf): 144,067<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3020<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

110,932<br />

13.0<br />

15,127<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

110,932<br />

15,127<br />

$41,751<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$21,970<br />

$2,197<br />

$14,500<br />

$4,833<br />

$5,800<br />

N/A<br />

$65,911<br />

$6,591<br />

Totals: $24,167 $72,502<br />

Total Project Cost: $121,803<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $121,803<br />

Rebate/Incentive*:<br />

$41,751<br />

Net Project Cost: $80,052<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

205,324<br />

0<br />

$18,069<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: KERCKHOFF<br />

Building Key: 04C4310<br />

Basic Gross Area (sf): 70,820<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3021<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

54,531<br />

6.0<br />

7,436<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

54,531<br />

7,436<br />

Extended Bare<br />

Labor Cost ($)<br />

$20,523<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$10,800<br />

$1,080<br />

$7,128<br />

$2,376<br />

$2,851<br />

N/A<br />

$32,400<br />

$3,240<br />

Totals: $11,880 $35,640<br />

Total Project Cost: $59,875<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $59,875<br />

Rebate/Incentive*:<br />

$20,523<br />

Net Project Cost: $39,352<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

100,932<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$8,882


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GONDA CENTER<br />

Building Key: 04C4315<br />

Basic Gross Area (sf): 125,202<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3022<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

236,632<br />

27.0<br />

25,416<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

236,632<br />

25,416<br />

$82,208<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$38,187<br />

$3,819<br />

$25,203<br />

$8,401<br />

$10,081<br />

N/A<br />

$114,560<br />

$11,456<br />

Totals: $42,006 $126,016<br />

Total Project Cost: $211,707<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $211,707<br />

Rebate/Incentive*:<br />

$82,208<br />

Net Project Cost: $129,499<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

395,228<br />

0<br />

$34,780<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LAW<br />

Building Key: 04C4317<br />

Basic Gross Area (sf): 275,439<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3023<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

212,088<br />

24.0<br />

28,921<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

212,088<br />

28,921<br />

$79,822<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$42,004<br />

$4,200<br />

$27,723<br />

$9,241<br />

$11,089<br />

N/A<br />

$126,013<br />

$12,601<br />

Totals: $46,204 $138,614<br />

Total Project Cost: $232,872<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $232,872<br />

Rebate/Incentive*:<br />

$79,822<br />

Net Project Cost: $153,050<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

392,555<br />

0<br />

$34,545<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: POWELL LIB<br />

Building Key: 04C4318A<br />

Basic Gross Area (sf): 166,846<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3024<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

128,471<br />

15.0<br />

17,519<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

128,471<br />

17,519<br />

$48,352<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$25,444<br />

$2,544<br />

$16,793<br />

$5,598<br />

$6,717<br />

N/A<br />

$76,332<br />

$7,633<br />

Totals: $27,988 $83,965<br />

Total Project Cost: $141,062<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $141,062<br />

Rebate/Incentive*:<br />

$48,352<br />

Net Project Cost: $92,710<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

237,790<br />

0<br />

$20,925<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LIFE SCIENCE<br />

Building Key: 04C4320<br />

Basic Gross Area (sf): 214,613<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3025<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

405,619<br />

46.0<br />

43,566<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

405,619<br />

43,566<br />

$140,915<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$65,457<br />

$6,546<br />

$43,202<br />

$14,401<br />

$17,281<br />

N/A<br />

$196,371<br />

$19,637<br />

Totals: $72,003 $216,008<br />

Total Project Cost: $362,894<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $362,894<br />

Rebate/Incentive*:<br />

$140,915<br />

Net Project Cost: $221,979<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

677,471<br />

0<br />

$59,617<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: DORIS STEIN<br />

Building Key: 04C4325<br />

Basic Gross Area (sf): 94,309<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3026<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

178,244<br />

20.0<br />

19,145<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

178,244<br />

19,145<br />

$61,924<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$28,764<br />

$2,876<br />

$18,984<br />

$6,328<br />

$7,594<br />

N/A<br />

$86,293<br />

$8,629<br />

Totals: $31,640 $94,922<br />

Total Project Cost: $159,469<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $159,469<br />

Rebate/Incentive*:<br />

$61,924<br />

Net Project Cost: $97,545<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

297,709<br />

0<br />

$26,198<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PUBLIC HLTH<br />

Building Key: 04C4331<br />

Basic Gross Area (sf): 140,563<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3027<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

265,664<br />

30.0<br />

28,534<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

265,664<br />

28,534<br />

$92,293<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$42,872<br />

$4,287<br />

$28,295<br />

$9,432<br />

$11,318<br />

N/A<br />

$128,615<br />

$12,862<br />

Totals: $47,159 $141,477<br />

Total Project Cost: $237,681<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $237,681<br />

Rebate/Incentive*:<br />

$92,293<br />

Net Project Cost: $145,388<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

443,716<br />

0<br />

$39,047<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: M DAVIES CC<br />

Building Key: 04C4332E<br />

Basic Gross Area (sf): 70,228<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3028<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

132,731<br />

15.0<br />

14,256<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

132,731<br />

14,256<br />

$46,111<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$21,420<br />

$2,142<br />

$14,137<br />

$4,712<br />

$5,655<br />

N/A<br />

$64,259<br />

$6,426<br />

Totals: $23,562 $70,685<br />

Total Project Cost: $118,751<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $118,751<br />

Rebate/Incentive*:<br />

$46,111<br />

Net Project Cost: $72,640<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

221,688<br />

0<br />

$19,509<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - CHS South Tower Seismic Renovation<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: SEMEL INST<br />

Building Key: 04C4332F<br />

Basic Gross Area (sf): 280,188<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3029<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

1,222,992<br />

140.0<br />

114,587<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

1,222,992<br />

114,587<br />

$408,105<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$645,817<br />

$161,454<br />

$242,181<br />

$80,727<br />

$96,872<br />

N/A<br />

$645,816<br />

$161,454<br />

Totals: $807,271 $807,270<br />

Total Project Cost: $2,034,322<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $2,034,322<br />

Rebate/Incentive*:<br />

$408,105<br />

Net Project Cost: $1,626,217<br />

Net Simple Payback Period (yrs): 9.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,938,015<br />

0<br />

$170,545<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: JULES STEIN<br />

Building Key: 04C4333<br />

Basic Gross Area (sf): 87,905<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3030<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

166,140<br />

19.0<br />

17,845<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

166,140<br />

17,845<br />

$57,719<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$26,811<br />

$2,681<br />

$17,695<br />

$5,898<br />

$7,078<br />

N/A<br />

$80,433<br />

$8,043<br />

Totals: $29,492 $88,476<br />

Total Project Cost: $148,640<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $148,640<br />

Rebate/Incentive*:<br />

$57,719<br />

Net Project Cost: $90,921<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

277,493<br />

0<br />

$24,419<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Jules Stein Eye Institute Seismic Repair<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: JULES STEIN<br />

Building Key: 04C4333<br />

Basic Gross Area (sf): 87,905<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3031<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

667,434<br />

76.0<br />

31,804<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

667,434<br />

31,804<br />

$191,988<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$280,385<br />

$28,039<br />

$92,527<br />

$30,842<br />

$37,011<br />

N/A<br />

$280,385<br />

$28,039<br />

Totals: $308,424 $308,424<br />

Total Project Cost: $777,227<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $777,227<br />

Rebate/Incentive*:<br />

$191,988<br />

Net Project Cost: $585,239<br />

Net Simple Payback Period (yrs): 7.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

865,891<br />

0<br />

$76,198<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BOELTER HALL<br />

Building Key: 04C4343<br />

Basic Gross Area (sf): 373,904<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3032<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

706,679<br />

81.0<br />

75,903<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

706,679<br />

75,903<br />

$245,506<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$114,041<br />

$11,404<br />

$75,267<br />

$25,089<br />

$30,107<br />

N/A<br />

$342,122<br />

$34,212<br />

Totals: $125,445 $376,334<br />

Total Project Cost: $632,242<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $632,242<br />

Rebate/Incentive*:<br />

$245,506<br />

Net Project Cost: $386,736<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,180,314<br />

0<br />

$103,868<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MORTON MED<br />

Building Key: 04C4344<br />

Basic Gross Area (sf): 366,834<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3033<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

693,316<br />

79.0<br />

74,467<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

693,316<br />

74,467<br />

$240,863<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$111,884<br />

$11,188<br />

$73,844<br />

$24,615<br />

$29,537<br />

N/A<br />

$335,653<br />

$33,565<br />

Totals: $123,072 $369,218<br />

Total Project Cost: $620,286<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $620,286<br />

Rebate/Incentive*:<br />

$240,863<br />

Net Project Cost: $379,423<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,157,990<br />

0<br />

$101,903<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MED PLZA 300<br />

Building Key: 04C4345<br />

Basic Gross Area (sf): 101,095<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3034<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

191,070<br />

22.0<br />

20,522<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

191,070<br />

20,522<br />

$66,379<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$30,834<br />

$3,083<br />

$20,350<br />

$6,783<br />

$8,140<br />

N/A<br />

$92,502<br />

$9,250<br />

Totals: $33,917 $101,752<br />

Total Project Cost: $170,944<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $170,944<br />

Rebate/Incentive*:<br />

$66,379<br />

Net Project Cost: $104,565<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

319,127<br />

0<br />

$28,083<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MACDONALDLAB<br />

Building Key: 04C4348<br />

Basic Gross Area (sf): 144,611<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3035<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

273,315<br />

31.0<br />

29,356<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

273,315<br />

29,356<br />

$94,952<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$44,106<br />

$4,411<br />

$29,110<br />

$9,703<br />

$11,644<br />

N/A<br />

$132,319<br />

$13,232<br />

Totals: $48,517 $145,551<br />

Total Project Cost: $244,525<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $244,525<br />

Rebate/Incentive*:<br />

$94,952<br />

Net Project Cost: $149,573<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

456,496<br />

0<br />

$40,172<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SYCAMORE CT<br />

Building Key: 04C4352<br />

Basic Gross Area (sf): 140,526<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3036<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

76,192<br />

9.0<br />

10,390<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

76,192<br />

10,390<br />

Extended Bare<br />

Labor Cost ($)<br />

$28,676<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$15,090<br />

$1,509<br />

$9,959<br />

$3,320<br />

$3,984<br />

N/A<br />

$45,270<br />

$4,527<br />

Totals: $16,599 $49,797<br />

Total Project Cost: $83,659<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $83,659<br />

Rebate/Incentive*:<br />

$28,676<br />

Net Project Cost: $54,983<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

141,026<br />

0<br />

$12,410<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SAC<br />

Building Key: 04C4360<br />

Basic Gross Area (sf): 113,383<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3037<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

87,305<br />

10.0<br />

11,905<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

87,305<br />

11,905<br />

Extended Bare<br />

Labor Cost ($)<br />

$32,858<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$17,291<br />

$1,729<br />

$11,412<br />

$3,804<br />

$4,565<br />

N/A<br />

$51,873<br />

$5,187<br />

Totals: $19,020 $57,060<br />

Total Project Cost: $95,861<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $95,861<br />

Rebate/Incentive*:<br />

$32,858<br />

Net Project Cost: $63,003<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

161,592<br />

0<br />

$14,220<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FOWLER MUSM<br />

Building Key: 04C4374<br />

Basic Gross Area (sf): 101,995<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3038<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

192,771<br />

22.0<br />

20,705<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

192,771<br />

20,705<br />

$66,970<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$31,108<br />

$3,111<br />

$20,531<br />

$6,844<br />

$8,213<br />

N/A<br />

$93,325<br />

$9,333<br />

Totals: $34,219 $102,658<br />

Total Project Cost: $172,464<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $172,464<br />

Rebate/Incentive*:<br />

$66,970<br />

Net Project Cost: $105,494<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

321,970<br />

0<br />

$28,333<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ROYCE HALL<br />

Building Key: 04C4375<br />

Basic Gross Area (sf): 184,673<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3039<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

142,198<br />

16.0<br />

19,391<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

142,198<br />

19,391<br />

$53,519<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$28,163<br />

$2,816<br />

$18,587<br />

$6,196<br />

$7,435<br />

N/A<br />

$84,488<br />

$8,449<br />

Totals: $30,979 $92,937<br />

Total Project Cost: $156,134<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $156,134<br />

Rebate/Incentive*:<br />

$53,519<br />

Net Project Cost: $102,615<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

263,198<br />

0<br />

$23,161<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: UNEX<br />

Building Key: 04C4415<br />

Basic Gross Area (sf): 95,065<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3040<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

73,200<br />

8.0<br />

9,982<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

73,200<br />

9,982<br />

Extended Bare<br />

Labor Cost ($)<br />

$27,550<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,497<br />

$1,450<br />

$9,568<br />

$3,189<br />

$3,827<br />

N/A<br />

$43,492<br />

$4,349<br />

Totals: $15,947 $47,841<br />

Total Project Cost: $80,373<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $80,373<br />

Rebate/Incentive*:<br />

$27,550<br />

Net Project Cost: $52,823<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

135,488<br />

0<br />

$11,923<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Clark Library Seismic Correction<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CLARK LIB<br />

Building Key: 04C4451<br />

Basic Gross Area (sf): 15,302<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3041<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

61,938<br />

7.0<br />

5,803<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

61,938<br />

5,803<br />

Extended Bare<br />

Labor Cost ($)<br />

$20,668<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$32,708<br />

$3,271<br />

$10,793<br />

$3,598<br />

$4,317<br />

N/A<br />

$32,707<br />

$3,271<br />

Totals: $35,979 $35,978<br />

Total Project Cost: $90,665<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $90,665<br />

Rebate/Incentive*:<br />

$20,668<br />

Net Project Cost: $69,997<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

98,149<br />

0<br />

$8,637


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SOUTHERN REGIONAL LIBRARY FACI<br />

Building Key: 04C4562<br />

Basic Gross Area (sf): 228,306<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3042<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

175,796<br />

20.0<br />

23,972<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

175,796<br />

23,972<br />

$66,163<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$34,817<br />

$3,482<br />

$22,979<br />

$7,660<br />

$9,192<br />

N/A<br />

$104,450<br />

$10,445<br />

Totals: $38,299 $114,895<br />

Total Project Cost: $193,024<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $193,024<br />

Rebate/Incentive*:<br />

$66,163<br />

Net Project Cost: $126,861<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

325,381<br />

0<br />

$28,634<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BUNCHE HALL<br />

Building Key: 04C4580<br />

Basic Gross Area (sf): 229,248<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3043<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

176,521<br />

20.0<br />

24,071<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

176,521<br />

24,071<br />

$66,436<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$34,960<br />

$3,496<br />

$23,074<br />

$7,691<br />

$9,230<br />

N/A<br />

$104,881<br />

$10,488<br />

Totals: $38,456 $115,369<br />

Total Project Cost: $193,820<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $193,820<br />

Rebate/Incentive*:<br />

$66,436<br />

Net Project Cost: $127,384<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

326,724<br />

0<br />

$28,752<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Santa Monica/Orthopaedic Replacement Hospital<br />

and Parking Structure<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - SANTA MO<br />

Building: SMH WST TOWR<br />

Building Key: 04C510F<br />

Basic Gross Area (sf): 202,568<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3044<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

2,748,782<br />

314.0<br />

130,982<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

2,748,782<br />

130,982<br />

$790,690<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$1,154,741<br />

$288,685<br />

$433,028<br />

$144,343<br />

$173,211<br />

N/A<br />

$1,154,741<br />

$288,685<br />

Totals: $1,443,426 $1,443,426<br />

Total Project Cost: $3,637,434<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $3,637,434<br />

Rebate/Incentive*:<br />

$790,690<br />

Net Project Cost: $2,846,744<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

2,748,782<br />

163,728<br />

$351,590<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: COLLINS CTR<br />

Building Key: 04C515A<br />

Basic Gross Area (sf): 31,311<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3045<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

24,109<br />

3.0<br />

3,288<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

24,109<br />

3,288<br />

$9,074<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$4,775<br />

$478<br />

$3,152<br />

$1,051<br />

$1,261<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,325<br />

$1,433<br />

Totals: $5,253 $15,758<br />

Total Project Cost: $26,473<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $26,473<br />

Rebate/Incentive*:<br />

$9,074<br />

Net Project Cost: $17,399<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,626<br />

0<br />

$3,927<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: GOLD HALL<br />

Building Key: 04C515B<br />

Basic Gross Area (sf): 55,344<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3046<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

42,615<br />

5.0<br />

5,811<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

42,615<br />

5,811<br />

Extended Bare<br />

Labor Cost ($)<br />

$16,039<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$8,440<br />

$844<br />

$5,570<br />

$1,857<br />

$2,228<br />

N/A<br />

$25,320<br />

$2,532<br />

Totals: $9,284 $27,852<br />

Total Project Cost: $46,791<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,791<br />

Rebate/Incentive*:<br />

$16,039<br />

Net Project Cost: $30,752<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

78,876<br />

0<br />

$6,941


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ENTREP HALL<br />

Building Key: 04C515C<br />

Basic Gross Area (sf): 72,591<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3047<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

55,895<br />

6.0<br />

7,622<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

55,895<br />

7,622<br />

Extended Bare<br />

Labor Cost ($)<br />

$21,037<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$11,070<br />

$1,107<br />

$7,306<br />

$2,435<br />

$2,922<br />

N/A<br />

$33,210<br />

$3,321<br />

Totals: $12,177 $36,531<br />

Total Project Cost: $61,372<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $61,372<br />

Rebate/Incentive*:<br />

$21,037<br />

Net Project Cost: $40,335<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

103,456<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$9,104


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CORNELL HALL<br />

Building Key: 04C515D<br />

Basic Gross Area (sf): 71,737<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3048<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

55,237<br />

6.0<br />

7,532<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

55,237<br />

7,532<br />

Extended Bare<br />

Labor Cost ($)<br />

$20,789<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$10,940<br />

$1,094<br />

$7,220<br />

$2,407<br />

$2,888<br />

N/A<br />

$32,820<br />

$3,282<br />

Totals: $12,034 $36,102<br />

Total Project Cost: $60,651<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $60,651<br />

Rebate/Incentive*:<br />

$20,789<br />

Net Project Cost: $39,862<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

102,237<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$8,997


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ROSNFLD LIBR<br />

Building Key: 04C515E<br />

Basic Gross Area (sf): 51,046<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3049<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

39,305<br />

4.0<br />

5,360<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

39,305<br />

5,360<br />

Extended Bare<br />

Labor Cost ($)<br />

$14,793<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$7,785<br />

$779<br />

$5,138<br />

$1,713<br />

$2,055<br />

N/A<br />

$23,354<br />

$2,335<br />

Totals: $8,564 $25,689<br />

Total Project Cost: $43,159<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $43,159<br />

Rebate/Incentive*:<br />

$14,793<br />

Net Project Cost: $28,366<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

72,751<br />

0<br />

$6,402


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MULLIN CMNS<br />

Building Key: 04C515F<br />

Basic Gross Area (sf): 33,957<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3050<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

26,147<br />

3.0<br />

3,565<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

26,147<br />

3,565<br />

$9,840<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$5,178<br />

$518<br />

$3,418<br />

$1,139<br />

$1,367<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$15,535<br />

$1,554<br />

Totals: $5,696 $17,089<br />

Total Project Cost: $28,708<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $28,708<br />

Rebate/Incentive*:<br />

$9,840<br />

Net Project Cost: $18,868<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

48,393<br />

0<br />

$4,259<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - CNSI-BSL3 Laboratory<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CNSI - BSL 3 LABORATORY<br />

Building Key: 04CTBD1<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3051<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

80,532<br />

9.0<br />

3,837<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

80,532<br />

3,837<br />

Extended Bare<br />

Labor Cost ($)<br />

$23,165<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$33,831<br />

$3,383<br />

$11,164<br />

$3,721<br />

$4,466<br />

N/A<br />

$33,831<br />

$3,383<br />

Totals: $37,214 $37,214<br />

Total Project Cost: $93,780<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $93,780<br />

Rebate/Incentive*:<br />

$23,165<br />

Net Project Cost: $70,615<br />

Net Simple Payback Period (yrs): 7.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

104,475<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$9,194


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - South <strong>Campus</strong> Student <strong>Center</strong><br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SOUTH CAMPUS STUDENT CTR<br />

Building Key: 04CTBD2<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3052<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

89,910<br />

10.0<br />

8,424<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

89,910<br />

8,424<br />

Extended Bare<br />

Labor Cost ($)<br />

$30,002<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$47,478<br />

$4,748<br />

$15,668<br />

$5,223<br />

$6,267<br />

N/A<br />

$47,477<br />

$4,748<br />

Totals: $52,226 $52,225<br />

Total Project Cost: $131,608<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $131,608<br />

Rebate/Incentive*:<br />

$30,002<br />

Net Project Cost: $101,606<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

142,476<br />

0<br />

$12,538<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Hilgard Graduate Student Housing<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: HILGARD GRAD STUD HOUSING<br />

Building Key: 04CTBD3<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3053<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

138,371<br />

16.0<br />

12,965<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

138,371<br />

12,965<br />

$46,174<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$73,070<br />

$7,307<br />

$24,113<br />

$8,038<br />

$9,645<br />

N/A<br />

$73,069<br />

$7,307<br />

Totals: $80,377 $80,376<br />

Total Project Cost: $202,549<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $202,549<br />

Rebate/Incentive*:<br />

$46,174<br />

Net Project Cost: $156,375<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

219,273<br />

0<br />

$19,296<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Southwest <strong>Campus</strong> Housing Commons Building<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SOUTHWEST CAMPUS HOUSING CO<br />

Building Key: 04CTBD4<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3054<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

87,413<br />

10.0<br />

8,190<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

87,413<br />

8,190<br />

Extended Bare<br />

Labor Cost ($)<br />

$29,169<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$46,158<br />

$4,616<br />

$15,232<br />

$5,077<br />

$6,093<br />

N/A<br />

$46,158<br />

$4,616<br />

Totals: $50,774 $50,774<br />

Total Project Cost: $127,950<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $127,950<br />

Rebate/Incentive*:<br />

$29,169<br />

Net Project Cost: $98,781<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

138,519<br />

0<br />

$12,190<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Telemedicine and Prime Facilities Phase 2<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: TELEMEDICINE AND PRIME FACILITIE<br />

Building Key: 04CTBD5<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3055<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

382,712<br />

44.0<br />

18,237<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

382,712<br />

18,237<br />

$110,088<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$160,776<br />

$16,078<br />

$53,056<br />

$17,685<br />

$21,222<br />

N/A<br />

$160,776<br />

$16,078<br />

Totals: $176,854 $176,854<br />

Total Project Cost: $445,671<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $445,671<br />

Rebate/Incentive*:<br />

$110,088<br />

Net Project Cost: $335,583<br />

Net Simple Payback Period (yrs): 7.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

496,511<br />

0<br />

$43,693<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Letters and Science Expansion<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: LETTERS AND SCIENCE EXPANSION<br />

Building Key: 04CTBD6<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3056<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

349,650<br />

40.0<br />

32,760<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

349,650<br />

32,760<br />

$116,676<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$184,636<br />

$18,464<br />

$60,930<br />

$20,310<br />

$24,372<br />

N/A<br />

$184,635<br />

$18,464<br />

Totals: $203,100 $203,099<br />

Total Project Cost: $511,810<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $511,810<br />

Rebate/Incentive*:<br />

$116,676<br />

Net Project Cost: $395,134<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

554,072<br />

0<br />

$48,758<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - Northwest <strong>Campus</strong> Student Housing Unit<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: NORTHWEST CAMPUS STUDENT HO<br />

Building Key: 04CTBD7<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3057<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

2,112,945<br />

241.0<br />

197,970<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

2,112,945<br />

197,970<br />

$705,077<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$1,115,765<br />

$111,577<br />

$368,202<br />

$122,734<br />

$147,281<br />

N/A<br />

$1,115,765<br />

$111,577<br />

Totals: $1,227,342 $1,227,342<br />

Total Project Cost: $3,092,901<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $3,092,901<br />

Rebate/Incentive*:<br />

$705,077<br />

Net Project Cost: $2,387,824<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

3,348,278<br />

0<br />

$294,648<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: First Electric Savings Component of DM and CR Projects 2009<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3058<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Second Electric Savings Component of DM and CR Projects 2009<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3059<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Natural Gas Component of DM and CR Projects 2009<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3060<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

28,409<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

28,409<br />

Extended Bare<br />

Labor Cost ($)<br />

$28,409<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$125,000<br />

$12,500<br />

$41,250<br />

$13,750<br />

$16,500<br />

N/A<br />

$125,000<br />

$12,500<br />

Totals: $137,500 $137,500<br />

Total Project Cost: $346,500<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $346,500<br />

Rebate/Incentive*:<br />

$28,409<br />

Net Project Cost: $318,091<br />

Net Simple Payback Period (yrs): 20.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

177,272<br />

0<br />

$15,600<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: First Electric Savings Component of DM and CR Projects 2010<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3061<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Second Electric Savings Component of DM and CR Projects 2010<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3062<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Natural Gas Component of DM and CR Projects 2010<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3063<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

28,409<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

28,409<br />

Extended Bare<br />

Labor Cost ($)<br />

$28,409<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$125,000<br />

$12,500<br />

$41,250<br />

$13,750<br />

$16,500<br />

N/A<br />

$125,000<br />

$12,500<br />

Totals: $137,500 $137,500<br />

Total Project Cost: $346,500<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $346,500<br />

Rebate/Incentive*:<br />

$28,409<br />

Net Project Cost: $318,091<br />

Net Simple Payback Period (yrs): 20.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

177,272<br />

0<br />

$15,600<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: First Electric Savings Component of DM and CR Projects 2011<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3064<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Second Electric Savings Component of DM and CR Projects 2011<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3065<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Natural Gas Component of DM and CR Projects 2011<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3066<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

28,409<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

28,409<br />

Extended Bare<br />

Labor Cost ($)<br />

$28,409<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$125,000<br />

$12,500<br />

$41,250<br />

$13,750<br />

$16,500<br />

N/A<br />

$125,000<br />

$12,500<br />

Totals: $137,500 $137,500<br />

Total Project Cost: $346,500<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $346,500<br />

Rebate/Incentive*:<br />

$28,409<br />

Net Project Cost: $318,091<br />

Net Simple Payback Period (yrs): 20.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

177,272<br />

0<br />

$15,600<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: First Electric Savings Component of DM and CR Projects 2012<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3067<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Second Electric Savings Component of DM and CR Projects 2012<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3068<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Natural Gas Component of DM and CR Projects 2012<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3069<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

28,409<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

28,409<br />

Extended Bare<br />

Labor Cost ($)<br />

$28,409<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$125,000<br />

$12,500<br />

$41,250<br />

$13,750<br />

$16,500<br />

N/A<br />

$125,000<br />

$12,500<br />

Totals: $137,500 $137,500<br />

Total Project Cost: $346,500<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $346,500<br />

Rebate/Incentive*:<br />

$28,409<br />

Net Project Cost: $318,091<br />

Net Simple Payback Period (yrs): 20.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

177,272<br />

0<br />

$15,600<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: First Electric Savings Component of DM and CR Projects 2013<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3070<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Second Electric Savings Component of DM and CR Projects 2013<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3071<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Natural Gas Component of DM and CR Projects 2013<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3072<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

28,409<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

28,409<br />

Extended Bare<br />

Labor Cost ($)<br />

$28,409<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$125,000<br />

$12,500<br />

$41,250<br />

$13,750<br />

$16,500<br />

N/A<br />

$125,000<br />

$12,500<br />

Totals: $137,500 $137,500<br />

Total Project Cost: $346,500<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $346,500<br />

Rebate/Incentive*:<br />

$28,409<br />

Net Project Cost: $318,091<br />

Net Simple Payback Period (yrs): 20.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

177,272<br />

0<br />

$15,600<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: First Electric Savings Component of DM and CR Projects 2014<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3073<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Second Electric Savings Component of DM and CR Projects 2014<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3074<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

454,550<br />

52.0<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

454,550<br />

0<br />

$109,092<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$250,000<br />

$25,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$250,000<br />

$25,000<br />

Totals: $275,000 $275,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$109,092<br />

Net Project Cost: $583,908<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,550<br />

0<br />

$40,000<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Natural Gas Component of DM and CR Projects 2014<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3075<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

28,409<br />

Equipment Description Qty<br />

Deferred Maintenance and Capital Renewal Projects - Checked MZ 032708.xls<br />

Project Description Reference(s): Deferred Maintenance and Capital Renewal Projects.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

28,409<br />

Extended Bare<br />

Labor Cost ($)<br />

$28,409<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$125,000<br />

$12,500<br />

$41,250<br />

$13,750<br />

$16,500<br />

N/A<br />

$125,000<br />

$12,500<br />

Totals: $137,500 $137,500<br />

Total Project Cost: $346,500<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $346,500<br />

Rebate/Incentive*:<br />

$28,409<br />

Net Project Cost: $318,091<br />

Net Simple Payback Period (yrs): 20.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

177,272<br />

0<br />

$15,600<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3076<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3077<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3078<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3079<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3080<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3081<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3082<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3083<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: MBCx Central <strong>Plan</strong>t<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3084<br />

<strong>UC</strong> SEP Central <strong>Plan</strong>t MBCx - Checked MZ 032808.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

750,000<br />

86.0<br />

60,000<br />

Equipment Description Qty<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

750,000<br />

60,000<br />

$240,000<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$100,000<br />

$10,000<br />

$82,500<br />

$27,500<br />

$33,000<br />

N/A<br />

$400,000<br />

$40,000<br />

Totals: $110,000 $440,000<br />

Total Project Cost: $693,000<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $693,000<br />

Rebate/Incentive*:<br />

$240,000<br />

Net Project Cost: $453,000<br />

Net Simple Payback Period (yrs): 4.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,124,400<br />

0<br />

$98,947<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: CAMPUSWIDE - MED CTR<br />

Building Key: 04CWIDEM<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3085<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$3,720<br />

$5,579<br />

$1,860<br />

$2,232<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$3,720<br />

Totals: $18,599 $18,598<br />

Total Project Cost: $46,867<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,867<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $37,466<br />

Net Simple Payback Period (yrs): 9.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: CAMPUSWIDE - MED CTR<br />

Building Key: 04CWIDEM<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3086<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$3,720<br />

$5,579<br />

$1,860<br />

$2,232<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$3,720<br />

Totals: $18,599 $18,598<br />

Total Project Cost: $46,867<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,867<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $37,466<br />

Net Simple Payback Period (yrs): 9.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: CAMPUSWIDE - MED CTR<br />

Building Key: 04CWIDEM<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3087<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$3,720<br />

$5,579<br />

$1,860<br />

$2,232<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$3,720<br />

Totals: $18,599 $18,598<br />

Total Project Cost: $46,867<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,867<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $37,466<br />

Net Simple Payback Period (yrs): 9.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: CAMPUSWIDE - MED CTR<br />

Building Key: 04CWIDEM<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3088<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$3,720<br />

$5,579<br />

$1,860<br />

$2,232<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$3,720<br />

Totals: $18,599 $18,598<br />

Total Project Cost: $46,867<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $46,867<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $37,466<br />

Net Simple Payback Period (yrs): 9.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE - OTHER<br />

Building Key: 04CWIDEO<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3089<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE - OTHER<br />

Building Key: 04CWIDEO<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3090<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE - OTHER<br />

Building Key: 04CWIDEO<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3091<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE - OTHER<br />

Building Key: 04CWIDEO<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3092<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

28,172<br />

3.0<br />

2,640<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Capital Project Savings Potential (27 Mar) - Checked MZ 032708.xls<br />

Project Description Reference(s): New Construction and Renovation from Capital Program.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

28,172<br />

2,640<br />

$9,401<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$14,879<br />

$1,488<br />

$4,910<br />

$1,637<br />

$1,964<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$14,878<br />

$1,488<br />

Totals: $16,367 $16,366<br />

Total Project Cost: $41,243<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $41,243<br />

Rebate/Incentive*:<br />

$9,401<br />

Net Project Cost: $31,842<br />

Net Simple Payback Period (yrs): 8.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,646<br />

0<br />

$3,929<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Lab Freezers Phase 1 of 4: 20 Lab Freezer Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3093<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

77,280<br />

Equipment Description Qty<br />

Lab Freezer Projects SEP MZ 032708-Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 2. Lab Freezers .<br />

<strong>Energy</strong> Star Lab Freezer 20<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

9.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

77,280<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$18,547<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$280,000<br />

$28,000<br />

$46,200<br />

$15,400<br />

$18,480<br />

N/A<br />

Totals: $308,000 $0<br />

Total Project Cost: $388,080<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $388,080<br />

Rebate/Incentive*:<br />

$18,547<br />

Net Project Cost: $369,533<br />

Net Simple Payback Period (yrs): 54.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

77,280<br />

0<br />

$6,801<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Lab Freezers Phase 2 of 4: 20 Lab Freezer Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3094<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

77,280<br />

Equipment Description Qty<br />

Lab Freezer Projects SEP MZ 032708-Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 2. Lab Freezers .<br />

<strong>Energy</strong> Star Lab Freezer 20<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

9.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

77,280<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$18,547<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$280,000<br />

$28,000<br />

$46,200<br />

$15,400<br />

$18,480<br />

N/A<br />

Totals: $308,000 $0<br />

Total Project Cost: $388,080<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $388,080<br />

Rebate/Incentive*:<br />

$18,547<br />

Net Project Cost: $369,533<br />

Net Simple Payback Period (yrs): 54.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

77,280<br />

0<br />

$6,801<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Lab Freezers Phase 3 of 4: 20 Lab Freezer Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3095<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

77,280<br />

Equipment Description Qty<br />

Lab Freezer Projects SEP MZ 032708-Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 2. Lab Freezers .<br />

<strong>Energy</strong> Star Lab Freezer 20<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

9.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

77,280<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$18,547<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$280,000<br />

$28,000<br />

$46,200<br />

$15,400<br />

$18,480<br />

N/A<br />

Totals: $308,000 $0<br />

Total Project Cost: $388,080<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $388,080<br />

Rebate/Incentive*:<br />

$18,547<br />

Net Project Cost: $369,533<br />

Net Simple Payback Period (yrs): 54.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

77,280<br />

0<br />

$6,801<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Lab Freezers Phase 4 of 4: 6 Lab Freezer Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3096<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

23,184<br />

Equipment Description Qty<br />

Lab Freezer Projects SEP MZ 032708-Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 2. Lab Freezers .<br />

<strong>Energy</strong> Star Lab Freezer 6<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

3.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

23,184<br />

0<br />

$5,564<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$84,000<br />

$8,400<br />

$13,860<br />

$4,620<br />

$5,544<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

Totals: $92,400 $0<br />

Total Project Cost: $116,424<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $116,424<br />

Rebate/Incentive*:<br />

$5,564<br />

Net Project Cost: $110,860<br />

Net Simple Payback Period (yrs): 54.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

23,184<br />

0<br />

$2,040<br />

$0<br />

$0<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 1 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3097<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (<strong>Campus</strong>-wide) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 2 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3098<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (<strong>Campus</strong>-wide) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 3 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3099<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (<strong>Campus</strong>-wide) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 4 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3100<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (<strong>Campus</strong>-wide) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 5 of 5: 73 <strong>Energy</strong> Star Refrigerator Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3101<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

163,739<br />

19.0<br />

Equipment Description Qty<br />

Refrigerator (<strong>Campus</strong>-wide) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 73<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

163,739<br />

0<br />

$39,297<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$50,954<br />

$5,095<br />

$8,407<br />

$2,802<br />

$3,363<br />

N/A<br />

Totals: $56,049 $0<br />

Total Project Cost: $70,622<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $70,622<br />

Rebate/Incentive*:<br />

Net Project Cost: $31,325<br />

Net Simple Payback Period (yrs): 2.2<br />

$39,297<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

163,739<br />

0<br />

$14,409<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 1 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3102<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (Housing) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 2 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3103<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (Housing) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 3 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3104<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (Housing) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 4 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3105<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (Housing) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 5 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3106<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (Housing) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 6 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3107<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

224,300<br />

26.0<br />

Equipment Description Qty<br />

Refrigerator (Housing) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 100<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

224,300<br />

0<br />

$53,832<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$69,800<br />

$6,980<br />

$11,517<br />

$3,839<br />

$4,607<br />

N/A<br />

Totals: $76,780 $0<br />

Total Project Cost: $96,743<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $96,743<br />

Rebate/Incentive*:<br />

Net Project Cost: $42,911<br />

Net Simple Payback Period (yrs): 2.2<br />

$53,832<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

224,300<br />

0<br />

$19,738<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Refrigerators Phase 7 of 7: 69 <strong>Energy</strong> Star Refrigerator Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3108<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

154,767<br />

18.0<br />

Equipment Description Qty<br />

Refrigerator (Housing) Projects SEP MZ 032608.Checked by LCK.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 1. Refrigerators.<br />

<strong>Energy</strong> Star Refrigerator 69<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

154,767<br />

0<br />

$37,144<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,162<br />

$4,816<br />

$7,947<br />

$2,649<br />

$3,179<br />

N/A<br />

Totals: $52,978 $0<br />

Total Project Cost: $66,753<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $66,753<br />

Rebate/Incentive*:<br />

Net Project Cost: $29,609<br />

Net Simple Payback Period (yrs): 2.2<br />

$37,144<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

154,767<br />

0<br />

$13,619<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 1 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3109<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

LCD Monitor & Installation 40<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 2 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3110<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

LCD Monitor & Installation 40<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 3 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3111<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

LCD Monitor & Installation 40<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 4 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3112<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

LCD Monitor & Installation 40<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 5 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3113<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

LCD Monitor & Installation 40<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 6 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3114<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

LCD Monitor & Installation 40<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 7 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3115<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

LCD Monitor & Installation 40<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 8 of 9: 1000 Verdiem (PC Power Management)<br />

Installations and 40 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3116<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

213,796<br />

27.0<br />

Equipment Description Qty<br />

Verdiem (or similar) Software, Licence & Installation 1,000<br />

LCD Monitor & Installation 40<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

213,796<br />

0<br />

$51,311<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,200<br />

$4,820<br />

$8,118<br />

$2,706<br />

$3,247<br />

N/A<br />

$1,000<br />

$100<br />

Totals: $53,020 $1,100<br />

Total Project Cost: $68,191<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $68,191<br />

Rebate/Incentive*:<br />

$51,311<br />

Net Project Cost: $16,880<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

213,796<br />

0<br />

$18,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: LCD Phase 9 of 9: 222 Verdiem (PC Power Management) Installations<br />

and 9 CRT Replacements<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3117<br />

Verdiem & CRT Projects SEP MZ 032608 - TLH.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 4. Network Computer Power Management Software/CRT .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

47,463<br />

Equipment Description Qty<br />

Verdiem (or similar) Software, Licence & Installation 222<br />

LCD Monitor & Installation 35<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

6.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

47,463<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$11,391<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$19,320<br />

$1,932<br />

$3,332<br />

$1,111<br />

$1,333<br />

N/A<br />

$875<br />

$88<br />

Totals: $21,252 $963<br />

Total Project Cost: $27,990<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $27,990<br />

Rebate/Incentive*:<br />

$11,391<br />

Net Project Cost: $16,599<br />

Net Simple Payback Period (yrs): 4.0<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

47,463<br />

0<br />

$4,177


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Server Virtualization Phase 1 of 5: 10 VM Installations<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3118<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

280,000<br />

35.0<br />

Equipment Description Qty<br />

Virtualization Projects SEP MZ 032608 - Checked ADM 032808.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 3. Server Virtualization .<br />

Hardware, Software, License & Installation; VM or similar, per Virt 10<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

280,000<br />

0<br />

$67,200<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$210,000<br />

$21,000<br />

$34,650<br />

$11,550<br />

$13,860<br />

N/A<br />

Totals: $231,000 $0<br />

Total Project Cost: $291,060<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $291,060<br />

Rebate/Incentive*:<br />

Net Project Cost: $223,860<br />

Net Simple Payback Period (yrs): 9.1<br />

$67,200<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

280,000<br />

0<br />

$24,640<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Server Virtualization Phase 2 of 5: 10 VM Installations<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3119<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

280,000<br />

35.0<br />

Equipment Description Qty<br />

Virtualization Projects SEP MZ 032608 - Checked ADM 032808.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 3. Server Virtualization .<br />

Hardware, Software, License & Installation; VM or similar, per Virt 10<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

280,000<br />

0<br />

$67,200<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$210,000<br />

$21,000<br />

$34,650<br />

$11,550<br />

$13,860<br />

N/A<br />

Totals: $231,000 $0<br />

Total Project Cost: $291,060<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $291,060<br />

Rebate/Incentive*:<br />

Net Project Cost: $223,860<br />

Net Simple Payback Period (yrs): 9.1<br />

$67,200<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

280,000<br />

0<br />

$24,640<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Server Virtualization Phase 3 of 5: 10 VM Installations<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3120<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

280,000<br />

35.0<br />

Equipment Description Qty<br />

Virtualization Projects SEP MZ 032608 - Checked ADM 032808.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 3. Server Virtualization .<br />

Hardware, Software, License & Installation; VM or similar, per Virt 10<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

280,000<br />

0<br />

$67,200<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$210,000<br />

$21,000<br />

$34,650<br />

$11,550<br />

$13,860<br />

N/A<br />

Totals: $231,000 $0<br />

Total Project Cost: $291,060<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $291,060<br />

Rebate/Incentive*:<br />

Net Project Cost: $223,860<br />

Net Simple Payback Period (yrs): 9.1<br />

$67,200<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

280,000<br />

0<br />

$24,640<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Server Virtualization Phase 4 of 5: 10 VM Installations<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3121<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

280,000<br />

35.0<br />

Equipment Description Qty<br />

Virtualization Projects SEP MZ 032608 - Checked ADM 032808.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 3. Server Virtualization .<br />

Hardware, Software, License & Installation; VM or similar, per Virt 10<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

280,000<br />

0<br />

$67,200<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$210,000<br />

$21,000<br />

$34,650<br />

$11,550<br />

$13,860<br />

N/A<br />

Totals: $231,000 $0<br />

Total Project Cost: $291,060<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $291,060<br />

Rebate/Incentive*:<br />

Net Project Cost: $223,860<br />

Net Simple Payback Period (yrs): 9.1<br />

$67,200<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

280,000<br />

0<br />

$24,640<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Server Virtualization Phase 5 of 5: 5 VM Installations<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3122<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

140,000<br />

18.0<br />

Equipment Description Qty<br />

Virtualization Projects SEP MZ 032608 - Checked ADM 032808.xls<br />

Project Description Reference(s): <strong>Campus</strong> Wide Project 3. Server Virtualization .<br />

Hardware, Software, License & Installation; VM or similar, per Virt 5<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

140,000<br />

0<br />

$33,600<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$105,000<br />

$10,500<br />

$17,325<br />

$5,775<br />

$6,930<br />

N/A<br />

Totals: $115,500 $0<br />

Total Project Cost: $145,530<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $145,530<br />

Rebate/Incentive*:<br />

Net Project Cost: $111,930<br />

Net Simple Payback Period (yrs): 9.1<br />

$33,600<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

140,000<br />

0<br />

$12,320<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

$0<br />

$0


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MURPHY HALL<br />

Building Key: 04C4200<br />

Basic Gross Area (sf): 220,188<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3124<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

169,545<br />

19.0<br />

23,120<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

169,545<br />

23,120<br />

$63,811<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$33,579<br />

$3,358<br />

$22,162<br />

$7,387<br />

$8,865<br />

N/A<br />

$100,736<br />

$10,074<br />

Totals: $36,937 $110,810<br />

Total Project Cost: $186,161<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $186,161<br />

Rebate/Incentive*:<br />

$63,811<br />

Net Project Cost: $122,350<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

313,814<br />

0<br />

$27,616<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SLICHTER<br />

Building Key: 04C4227<br />

Basic Gross Area (sf): 62,557<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3128<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

48,169<br />

6.0<br />

6,568<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

48,169<br />

6,568<br />

Extended Bare<br />

Labor Cost ($)<br />

$18,129<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$9,540<br />

$954<br />

$6,296<br />

$2,099<br />

$2,519<br />

N/A<br />

$28,620<br />

$2,862<br />

Totals: $10,494 $31,482<br />

Total Project Cost: $52,890<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $52,890<br />

Rebate/Incentive*:<br />

$18,129<br />

Net Project Cost: $34,761<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

89,153<br />

0<br />

$7,845


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: YOUNG HALL<br />

Building Key: 04C4228B<br />

Basic Gross Area (sf): 297,589<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3131<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

562,443<br />

64.0<br />

60,411<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

562,443<br />

60,411<br />

$195,397<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$90,765<br />

$9,077<br />

$59,905<br />

$19,968<br />

$23,962<br />

N/A<br />

$272,294<br />

$27,229<br />

Totals: $99,842 $299,523<br />

Total Project Cost: $503,200<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $503,200<br />

Rebate/Incentive*:<br />

$195,397<br />

Net Project Cost: $307,803<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

939,408<br />

0<br />

$82,668<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FRANZ HALL<br />

Building Key: 04C4319<br />

Basic Gross Area (sf): 238,054<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3143<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

449,922<br />

51.0<br />

48,325<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

449,922<br />

48,325<br />

$156,306<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$72,606<br />

$7,261<br />

$47,920<br />

$15,973<br />

$19,168<br />

N/A<br />

$217,819<br />

$21,782<br />

Totals: $79,867 $239,601<br />

Total Project Cost: $402,529<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $402,529<br />

Rebate/Incentive*:<br />

$156,306<br />

Net Project Cost: $246,223<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

751,470<br />

0<br />

$66,129<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: REED RESRCH<br />

Building Key: 04C4329<br />

Basic Gross Area (sf): 69,176<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3147<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

130,743<br />

15.0<br />

14,043<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

130,743<br />

14,043<br />

$45,421<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$21,099<br />

$2,110<br />

$13,925<br />

$4,642<br />

$5,570<br />

N/A<br />

$63,296<br />

$6,330<br />

Totals: $23,209 $69,626<br />

Total Project Cost: $116,971<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $116,971<br />

Rebate/Incentive*:<br />

$45,421<br />

Net Project Cost: $71,550<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

218,371<br />

0<br />

$19,217<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BRAIN RSCH<br />

Building Key: 04C4332B<br />

Basic Gross Area (sf): 86,578<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3150<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

163,632<br />

19.0<br />

17,575<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

163,632<br />

17,575<br />

$56,847<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$26,406<br />

$2,641<br />

$17,428<br />

$5,809<br />

$6,971<br />

N/A<br />

$79,219<br />

$7,922<br />

Totals: $29,047 $87,141<br />

Total Project Cost: $146,396<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $146,396<br />

Rebate/Incentive*:<br />

$56,847<br />

Net Project Cost: $89,549<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

273,300<br />

0<br />

$24,050<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: DENTISTRY<br />

Building Key: 04C4334<br />

Basic Gross Area (sf): 204,369<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3154<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

386,257<br />

44.0<br />

41,487<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

386,257<br />

41,487<br />

$134,189<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$62,333<br />

$6,233<br />

$41,140<br />

$13,713<br />

$16,456<br />

N/A<br />

$186,998<br />

$18,700<br />

Totals: $68,566 $205,698<br />

Total Project Cost: $345,573<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $345,573<br />

Rebate/Incentive*:<br />

$134,189<br />

Net Project Cost: $211,384<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

645,136<br />

0<br />

$56,772<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SCHOENBERG<br />

Building Key: 04C4335<br />

Basic Gross Area (sf): 122,552<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3156<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

94,365<br />

11.0<br />

12,868<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

94,365<br />

12,868<br />

Extended Bare<br />

Labor Cost ($)<br />

$35,516<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$18,689<br />

$1,869<br />

$12,335<br />

$4,112<br />

$4,934<br />

N/A<br />

$56,068<br />

$5,607<br />

Totals: $20,558 $61,675<br />

Total Project Cost: $103,613<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $103,613<br />

Rebate/Incentive*:<br />

$35,516<br />

Net Project Cost: $68,097<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

174,661<br />

0<br />

$15,370<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FACTOR<br />

Building Key: 04C4336<br />

Basic Gross Area (sf): 199,857<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3158<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

377,730<br />

43.0<br />

40,571<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

377,730<br />

40,571<br />

$131,226<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$60,956<br />

$6,096<br />

$40,231<br />

$13,410<br />

$16,092<br />

N/A<br />

$182,869<br />

$18,287<br />

Totals: $67,052 $201,156<br />

Total Project Cost: $337,941<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $337,941<br />

Rebate/Incentive*:<br />

$131,226<br />

Net Project Cost: $206,715<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

630,893<br />

0<br />

$55,519<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MATH SCIENCE<br />

Building Key: 04C4359<br />

Basic Gross Area (sf): 224,078<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3164<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

423,507<br />

48.0<br />

45,488<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

423,507<br />

45,488<br />

$147,130<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$68,344<br />

$6,834<br />

$45,107<br />

$15,036<br />

$18,043<br />

N/A<br />

$205,031<br />

$20,503<br />

Totals: $75,178 $225,534<br />

Total Project Cost: $378,898<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $378,898<br />

Rebate/Incentive*:<br />

$147,130<br />

Net Project Cost: $231,768<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

707,352<br />

0<br />

$62,247<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: KNUDSEN HALL<br />

Building Key: 04C4363<br />

Basic Gross Area (sf): 164,702<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3168<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

311,287<br />

36.0<br />

33,435<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

311,287<br />

33,435<br />

$108,144<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$50,234<br />

$5,023<br />

$33,154<br />

$11,051<br />

$13,262<br />

N/A<br />

$150,702<br />

$15,070<br />

Totals: $55,257 $165,772<br />

Total Project Cost: $278,497<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $278,497<br />

Rebate/Incentive*:<br />

$108,144<br />

Net Project Cost: $170,353<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

519,921<br />

0<br />

$45,753<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BOYER HALL<br />

Building Key: 04C4403<br />

Basic Gross Area (sf): 133,042<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3172<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

251,449<br />

29.0<br />

27,008<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

251,449<br />

27,008<br />

$87,356<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$40,578<br />

$4,058<br />

$26,781<br />

$8,927<br />

$10,713<br />

N/A<br />

$121,733<br />

$12,173<br />

Totals: $44,636 $133,906<br />

Total Project Cost: $224,963<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $224,963<br />

Rebate/Incentive*:<br />

$87,356<br />

Net Project Cost: $137,607<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

419,979<br />

0<br />

$36,958<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MELNITZ HALL<br />

Building Key: 04C4577A<br />

Basic Gross Area (sf): 61,827<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3176<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

47,607<br />

5.0<br />

6,492<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

47,607<br />

6,492<br />

Extended Bare<br />

Labor Cost ($)<br />

$17,918<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$9,429<br />

$943<br />

$6,223<br />

$2,074<br />

$2,489<br />

N/A<br />

$28,286<br />

$2,829<br />

Totals: $10,372 $31,115<br />

Total Project Cost: $52,273<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $52,273<br />

Rebate/Incentive*:<br />

$17,918<br />

Net Project Cost: $34,355<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

88,117<br />

0<br />

$7,754


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MACGOWAN<br />

Building Key: 04C4578<br />

Basic Gross Area (sf): 129,542<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3178<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

99,747<br />

11.0<br />

13,602<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

99,747<br />

13,602<br />

Extended Bare<br />

Labor Cost ($)<br />

$37,541<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$19,755<br />

$1,976<br />

$13,038<br />

$4,346<br />

$5,215<br />

N/A<br />

$59,265<br />

$5,927<br />

Totals: $21,731 $65,192<br />

Total Project Cost: $109,522<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $109,522<br />

Rebate/Incentive*:<br />

$37,541<br />

Net Project Cost: $71,981<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

184,623<br />

0<br />

$16,247<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PUBLIC AFFAIRS<br />

Building Key: 04C4579<br />

Basic Gross Area (sf): 201,667<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3180<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

155,284<br />

18.0<br />

21,175<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

155,284<br />

21,175<br />

$58,443<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$30,754<br />

$3,075<br />

$20,298<br />

$6,766<br />

$8,119<br />

N/A<br />

$92,263<br />

$9,226<br />

Totals: $33,829 $101,489<br />

Total Project Cost: $170,502<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $170,502<br />

Rebate/Incentive*:<br />

$58,443<br />

Net Project Cost: $112,059<br />

Net Simple Payback Period (yrs): 4.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

287,416<br />

0<br />

$25,293<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WARREN HALL<br />

Building Key: 04C4581<br />

Basic Gross Area (sf): 102,205<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3183<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

193,167<br />

22.0<br />

20,748<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

193,167<br />

20,748<br />

$67,108<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$31,173<br />

$3,117<br />

$20,574<br />

$6,858<br />

$8,230<br />

N/A<br />

$93,518<br />

$9,352<br />

Totals: $34,290 $102,870<br />

Total Project Cost: $172,822<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $172,822<br />

Rebate/Incentive*:<br />

$67,108<br />

Net Project Cost: $105,714<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

322,635<br />

0<br />

$28,392<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: REHAB CENTER<br />

Building Key: 04C4594<br />

Basic Gross Area (sf): 142,566<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3185<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

269,450<br />

31.0<br />

28,941<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

269,450<br />

28,941<br />

$93,609<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$43,483<br />

$4,348<br />

$28,699<br />

$9,566<br />

$11,479<br />

N/A<br />

$130,448<br />

$13,045<br />

Totals: $47,831 $143,493<br />

Total Project Cost: $241,068<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $241,068<br />

Rebate/Incentive*:<br />

$93,609<br />

Net Project Cost: $147,459<br />

Net Simple Payback Period (yrs): 3.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

450,042<br />

0<br />

$39,604<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace 600 additional stairwell light fixtures with bi-level fixtures<br />

with occupancy sensors in campus buildings<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3192<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

210,000<br />

Equipment Description Qty<br />

<strong>Campus</strong>wide Bi-level Stairwell Lighting Custom Calc AML Checked TLH.xls<br />

Project Description Reference(s): Lighting Project 3. Stairwell Lighting.<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

210,000<br />

0<br />

$50,400<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Stairwell Fixture 600 $90.00 $55,350 $135.00 $90,801<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$55,350 $90,801<br />

$4,566<br />

$7,190<br />

$67,106<br />

$6,711<br />

$27,853<br />

$9,284<br />

$11,141<br />

N/A<br />

$10,896<br />

$101,697<br />

$10,170<br />

Totals: $73,817 $111,867<br />

Total Project Cost: $233,962<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $233,962<br />

Rebate/Incentive*:<br />

$50,400<br />

Net Project Cost: $183,562<br />

Net Simple Payback Period (yrs): 9.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

210,000<br />

0<br />

$18,480<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Retrofit existing 175-watt suspended metal halide fixtures with<br />

ceramic metal halide and replace quartz floods with fluorescent T5HO<br />

wall washes<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: ACKERMAN<br />

Building Key: 04C4582<br />

Basic Gross Area (sf): 213,143<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3193<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

222,825<br />

42.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Ackerman Bookstore SEP Custom Calculation.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

222,825<br />

0<br />

$53,478<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

100-watt CMH kit 300 $175.00 $53,813 $150.00 $50,445<br />

48-watt T5HO wall washer (24") 20 $100.00 $2,050 $80.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$55,863 $52,239<br />

$4,609<br />

$7,257<br />

$67,728<br />

$6,773<br />

$20,829<br />

$6,943<br />

$8,332<br />

N/A<br />

$6,269<br />

$58,507<br />

$5,851<br />

Totals: $74,500 $64,358<br />

Total Project Cost: $174,962<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $174,962<br />

Rebate/Incentive*:<br />

$53,478<br />

Net Project Cost: $121,484<br />

Net Simple Payback Period (yrs): 6.2<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

222,825<br />

0<br />

$19,609<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Retrofit kitchen fixtures from F40T12 lamps with magnetic ballasts to<br />

F32T8 (28-watt) lamps with RLO electronic ballasts<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FACULTY CTR<br />

Building Key: 04C4261<br />

Basic Gross Area (sf): 30,573<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3194<br />

<strong>UC</strong>LA Faculty <strong>Center</strong> SEP Custom Calc.NAM.xls<br />

Project Description Reference(s): Lighting Project 1. Interior Linear Fluorescent Lighting.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

7,425<br />

Equipment Description Qty<br />

2.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

7,425<br />

0<br />

$1,782<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

2L 2F32T8 (28-watt) retrofit 50 $17.80 $912 $25.00 $1,401<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$912 $1,401<br />

$75<br />

$119<br />

$1,106<br />

$111<br />

$441<br />

$147<br />

$177<br />

N/A<br />

$168<br />

$1,569<br />

$157<br />

Totals: $1,217 $1,726<br />

Total Project Cost: $3,708<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $3,708<br />

Rebate/Incentive*:<br />

$1,782<br />

Net Project Cost: $1,926<br />

Net Simple Payback Period (yrs): 2.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

7,425<br />

0<br />

$653<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG ST CHS<br />

Building Key: 04C4211<br />

Basic Gross Area (sf): 652,811<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3195<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

195,795<br />

22.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 217<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

195,795<br />

0<br />

$46,991<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$79,357<br />

$7,936<br />

$16,841<br />

$5,614<br />

$6,736<br />

N/A<br />

$22,709<br />

$2,271<br />

Totals: $87,293 $24,980<br />

Total Project Cost: $141,463<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $141,463<br />

Rebate/Incentive*:<br />

$46,991<br />

Net Project Cost: $94,472<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

195,795<br />

0<br />

$17,230<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR DD<br />

Building Key: 04C4490<br />

Basic Gross Area (sf): 98,834<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3196<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

44,212<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 49<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

5.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

44,212<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$10,611<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$17,919<br />

$1,792<br />

$3,803<br />

$1,268<br />

$1,521<br />

N/A<br />

$5,128<br />

$513<br />

Totals: $19,711 $5,641<br />

Total Project Cost: $31,943<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $31,943<br />

Rebate/Incentive*:<br />

$10,611<br />

Net Project Cost: $21,332<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

44,212<br />

0<br />

$3,891


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR RC<br />

Building Key: 04C4301<br />

Basic Gross Area (sf): 55,861<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3197<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

26,166<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 29<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

3.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

26,166<br />

0<br />

$6,280<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$10,605<br />

$1,061<br />

$2,251<br />

$750<br />

$900<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$3,035<br />

$303<br />

Totals: $11,666 $3,338<br />

Total Project Cost: $18,905<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $18,905<br />

Rebate/Incentive*:<br />

$6,280<br />

Net Project Cost: $12,625<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

26,166<br />

0<br />

$2,303<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: COURTSIDE/PK<br />

Building Key: 04C4302C<br />

Basic Gross Area (sf): 364,888<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3198<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

175,042<br />

20.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 194<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

175,042<br />

0<br />

$42,010<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$70,946<br />

$7,095<br />

$15,056<br />

$5,019<br />

$6,022<br />

N/A<br />

$20,302<br />

$2,030<br />

Totals: $78,040 $22,332<br />

Total Project Cost: $126,470<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $126,470<br />

Rebate/Incentive*:<br />

$42,010<br />

Net Project Cost: $84,460<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

175,042<br />

0<br />

$15,404<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 32<br />

Building Key: 04C4263<br />

Basic Gross Area (sf): 308,410<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3199<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

154,290<br />

18.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 171<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

154,290<br />

0<br />

$37,030<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$62,535<br />

$6,253<br />

$13,271<br />

$4,424<br />

$5,308<br />

N/A<br />

$17,895<br />

$1,790<br />

Totals: $68,788 $19,685<br />

Total Project Cost: $111,476<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $111,476<br />

Rebate/Incentive*:<br />

$37,030<br />

Net Project Cost: $74,446<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

154,290<br />

0<br />

$13,578<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 1<br />

Building Key: 04C4342<br />

Basic Gross Area (sf): 1,008,954<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3200<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

632,498<br />

72.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 701<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

632,498<br />

0<br />

$151,800<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$256,356<br />

$25,636<br />

$54,403<br />

$18,134<br />

$21,761<br />

N/A<br />

$73,360<br />

$7,336<br />

Totals: $281,991 $80,696<br />

Total Project Cost: $456,985<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $456,985<br />

Rebate/Incentive*:<br />

$151,800<br />

Net Project Cost: $305,185<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

632,498<br />

0<br />

$55,660<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 2<br />

Building Key: 04C4210<br />

Basic Gross Area (sf): 771,328<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3201<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

468,283<br />

53.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 519<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

468,283<br />

0<br />

$112,388<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$189,798<br />

$18,980<br />

$40,278<br />

$13,426<br />

$16,111<br />

N/A<br />

$54,313<br />

$5,431<br />

Totals: $208,778 $59,745<br />

Total Project Cost: $338,339<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $338,339<br />

Rebate/Incentive*:<br />

$112,388<br />

Net Project Cost: $225,951<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

468,283<br />

0<br />

$41,209<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 3<br />

Building Key: 04C4207<br />

Basic Gross Area (sf): 412,864<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3202<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

247,225<br />

28.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 274<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

247,225<br />

0<br />

$59,334<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$100,202<br />

$10,020<br />

$21,265<br />

$7,088<br />

$8,506<br />

N/A<br />

$28,674<br />

$2,867<br />

Totals: $110,222 $31,542<br />

Total Project Cost: $178,622<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $178,622<br />

Rebate/Incentive*:<br />

$59,334<br />

Net Project Cost: $119,288<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

247,225<br />

0<br />

$21,756<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WOODEN/PS4<br />

Building Key: 04C4235<br />

Basic Gross Area (sf): 707,839<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3203<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

397,003<br />

45.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 440<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

397,003<br />

0<br />

$95,281<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$160,908<br />

$16,091<br />

$34,147<br />

$11,382<br />

$13,659<br />

N/A<br />

$46,046<br />

$4,605<br />

Totals: $176,999 $50,651<br />

Total Project Cost: $286,838<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $286,838<br />

Rebate/Incentive*:<br />

$95,281<br />

Net Project Cost: $191,557<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

397,003<br />

0<br />

$34,936<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 5<br />

Building Key: 04C4587<br />

Basic Gross Area (sf): 339,631<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3204<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

115,041<br />

13.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 128<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

115,041<br />

0<br />

$27,610<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$46,810<br />

$4,681<br />

$9,934<br />

$3,311<br />

$3,974<br />

N/A<br />

$13,395<br />

$1,340<br />

Totals: $51,491 $14,735<br />

Total Project Cost: $83,444<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $83,444<br />

Rebate/Incentive*:<br />

$27,610<br />

Net Project Cost: $55,834<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

115,041<br />

0<br />

$10,124<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 6<br />

Building Key: 04C4219<br />

Basic Gross Area (sf): 282,212<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3205<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

165,117<br />

19.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 183<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

165,117<br />

0<br />

$39,628<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$66,923<br />

$6,692<br />

$14,202<br />

$4,734<br />

$5,681<br />

N/A<br />

$19,151<br />

$1,915<br />

Totals: $73,615 $21,066<br />

Total Project Cost: $119,299<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $119,299<br />

Rebate/Incentive*:<br />

$39,628<br />

Net Project Cost: $79,671<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

165,117<br />

0<br />

$14,530<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 7<br />

Building Key: 04C4322<br />

Basic Gross Area (sf): 508,306<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3206<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

369,935<br />

42.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 410<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

369,935<br />

0<br />

$88,784<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$149,937<br />

$14,994<br />

$31,819<br />

$10,606<br />

$12,728<br />

N/A<br />

$42,907<br />

$4,291<br />

Totals: $164,931 $47,197<br />

Total Project Cost: $267,281<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $267,281<br />

Rebate/Incentive*:<br />

$88,784<br />

Net Project Cost: $178,497<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

369,935<br />

0<br />

$32,554<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 8<br />

Building Key: 04C4209<br />

Basic Gross Area (sf): 990,564<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3207<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

642,423<br />

73.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 712<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

642,423<br />

0<br />

$154,182<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$260,378<br />

$26,038<br />

$55,257<br />

$18,419<br />

$22,103<br />

N/A<br />

$74,511<br />

$7,451<br />

Totals: $286,416 $81,962<br />

Total Project Cost: $464,156<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $464,156<br />

Rebate/Incentive*:<br />

$154,182<br />

Net Project Cost: $309,974<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

642,423<br />

0<br />

$56,533<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PARKG STR 9<br />

Building Key: 04C4208<br />

Basic Gross Area (sf): 678,618<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3208<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

382,567<br />

44.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 424<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

382,567<br />

0<br />

$91,816<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$155,057<br />

$15,506<br />

$32,906<br />

$10,969<br />

$13,162<br />

N/A<br />

$44,372<br />

$4,437<br />

Totals: $170,562 $48,809<br />

Total Project Cost: $276,408<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $276,408<br />

Rebate/Incentive*:<br />

$91,816<br />

Net Project Cost: $184,592<br />

Net Simple Payback Period (yrs): 5.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

382,567<br />

0<br />

$33,666<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace high pressure sodium fixtures with induction fixtures and<br />

install photocell control where appropriate<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: PARKG STR E<br />

Building Key: 04C4332H<br />

Basic Gross Area (sf): 95,116<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3209<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

38,798<br />

Equipment Description Qty<br />

<strong>UC</strong>LA Parking Structures SEP Custom Calc NAM 051208.xls<br />

Project Description Reference(s): Lighting Project 5. Parking Garage and Outdoor Pole Lighting.<br />

85-watt Induction Fixture 43<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

4.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

38,798<br />

0<br />

$9,312<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$15,725<br />

$3,931<br />

$3,792<br />

$1,264<br />

$1,517<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$4,500<br />

$1,125<br />

Totals: $19,656 $5,625<br />

Total Project Cost: $31,854<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $31,854<br />

Rebate/Incentive*:<br />

$9,312<br />

Net Project Cost: $22,542<br />

Net Simple Payback Period (yrs): 6.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

38,798<br />

0<br />

$3,414<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Retrofit gym HID fixtures with Pulse Start Metal Halide lamps<br />

w/electronic ballasts<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PAULEY<br />

Building Key: 04C4204<br />

Basic Gross Area (sf): 204,465<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3210<br />

<strong>UC</strong>LA Pauley Arena SEP Custom Calc.NAM.xls<br />

Project Description Reference(s): Lighting Project 4. Interior High Bay Lighting .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

54,600<br />

Equipment Description Qty<br />

8.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

54,600<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$13,104<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

875-watt PSMH retrofit kit 60 $175.00 $10,763 $250.00 $16,815<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$10,763 $16,815<br />

$888<br />

$1,398<br />

$13,048<br />

$1,305<br />

$5,260<br />

$1,753<br />

$2,104<br />

N/A<br />

$2,018<br />

$18,833<br />

$1,883<br />

Totals: $14,353 $20,716<br />

Total Project Cost: $44,187<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $44,187<br />

Rebate/Incentive*:<br />

$13,104<br />

Net Project Cost: $31,083<br />

Net Simple Payback Period (yrs): 6.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

54,600<br />

0<br />

$4,805


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SAC Pool: Variable Speed Circulation Pumps<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3211<br />

<strong>UC</strong>LA Pools 051208 AML.xls<br />

Project Description Reference(s): Pool Project 1. Variable Speed Drives and High Efficiency Motors for Filter Pumps.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

36,809<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

36,809<br />

0<br />

$8,834<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

VSD and Controls 1 $9,600.00 $9,840 $1,391.25 $1,560<br />

Premium Efficiency Motor 1 $1,225.00 $1,256 $80.00<br />

$90<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$11,096 $1,649<br />

$915<br />

$1,441<br />

$13,452<br />

$1,345<br />

$2,524<br />

$841<br />

$1,010<br />

N/A<br />

$198<br />

$1,847<br />

$185<br />

Totals: $14,798 $2,032<br />

Total Project Cost: $21,205<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $21,205<br />

Rebate/Incentive*:<br />

$8,834<br />

Net Project Cost: $12,371<br />

Net Simple Payback Period (yrs): 3.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

36,809<br />

0<br />

$3,239<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: SAC Pool: Solar Pool Water Heater<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3212<br />

<strong>UC</strong>LA Pools 051208 AML.xls<br />

Project Description Reference(s): Pool Project 3. Solar Water Heating .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

12,614<br />

Equipment Description Qty<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

12,614<br />

Extended Bare<br />

Labor Cost ($)<br />

$12,614<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Solar Water Heating System 1 $28,569.57 $29,284 $37,183.63 $41,683<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$29,284 $41,683<br />

$2,416<br />

$3,804<br />

$35,504<br />

$3,550<br />

$13,561<br />

$4,520<br />

$5,424<br />

N/A<br />

$5,002<br />

$46,685<br />

$4,668<br />

Totals: $39,054 $51,353<br />

Total Project Cost: $113,913<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $113,913<br />

Rebate/Incentive*:<br />

$12,614<br />

Net Project Cost: $101,299<br />

Net Simple Payback Period (yrs): 14.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

78,711<br />

0<br />

$6,927


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: North Pool: Variable Speed Circulation Pumps<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3213<br />

<strong>UC</strong>LA Pools 051208 AML.xls<br />

Project Description Reference(s): Pool Project 1. Variable Speed Drives and High Efficiency Motors for Filter Pumps.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

54,089<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

54,089<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$12,981<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

VSD and Controls 1 $7,680.00 $7,872 $1,113.00 $1,248<br />

Premium Efficiency Motor 1 $1,000.00 $1,025 $84.00<br />

$94<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$8,897 $1,342<br />

$734<br />

$1,156<br />

$10,787<br />

$1,079<br />

$2,028<br />

$676<br />

$811<br />

N/A<br />

$161<br />

$1,503<br />

$150<br />

Totals: $11,865 $1,653<br />

Total Project Cost: $17,033<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $17,033<br />

Rebate/Incentive*:<br />

$12,981<br />

Net Project Cost: $4,052<br />

Net Simple Payback Period (yrs): 0.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

54,089<br />

0<br />

$4,760


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Sunset Canyon Park Pool: Variable Speed Circulation Pumps<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3214<br />

<strong>UC</strong>LA Pools 051208 AML.xls<br />

Project Description Reference(s): Pool Project 1. Variable Speed Drives and High Efficiency Motors for Filter Pumps.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

132,655<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

132,655<br />

0<br />

$31,837<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Premium Efficiency Motor 1 $4,350.00 $4,459 $84.00<br />

$94<br />

VSD and Controls 1 $28,800.00 $29,520 $4,173.75 $4,679<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$33,979 $4,773<br />

$2,803<br />

$4,414<br />

$41,196<br />

$4,120<br />

$7,679<br />

$2,560<br />

$3,072<br />

N/A<br />

$573<br />

$5,346<br />

$535<br />

Totals: $45,315 $5,880<br />

Total Project Cost: $64,507<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $64,507<br />

Rebate/Incentive*:<br />

$31,837<br />

Net Project Cost: $32,670<br />

Net Simple Payback Period (yrs): 2.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

132,655<br />

0<br />

$11,674<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Sunset Canyon Diving & Family Pools: Variable Speed Circulation<br />

Pumps<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3215<br />

<strong>UC</strong>LA Pools 051208 AML.xls<br />

Project Description Reference(s): Pool Project 1. Variable Speed Drives and High Efficiency Motors for Filter Pumps.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

71,539<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

71,539<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$17,169<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Premium Efficiency Motor 1 $1,425.00 $1,461 $74.50<br />

$84<br />

VSD and Controls 1 $11,520.00 $11,808 $1,669.50 $1,872<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$13,269 $1,955<br />

$1,095<br />

$1,724<br />

$16,087<br />

$1,609<br />

$3,016<br />

$1,005<br />

$1,206<br />

N/A<br />

$235<br />

$2,190<br />

$219<br />

Totals: $17,696 $2,409<br />

Total Project Cost: $25,331<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $25,331<br />

Rebate/Incentive*:<br />

$17,169<br />

Net Project Cost: $8,162<br />

Net Simple Payback Period (yrs): 1.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

71,539<br />

0<br />

$6,295


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Future Million-Gallon Pool at Sunset Canyon: Variable Speed<br />

Circulation Pumps<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3216<br />

<strong>UC</strong>LA Pools 051208 AML.xls<br />

Project Description Reference(s): Pool Project 1. Variable Speed Drives and High Efficiency Motors for Filter Pumps.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

156,488<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

156,488<br />

0<br />

$37,557<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

VSD and Controls 1 $38,400.00 $39,360 $5,565.00 $6,238<br />

Premium Efficiency Motor 1 $0.00 $0 $74.50<br />

$84<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$39,360 $6,322<br />

$3,247<br />

$5,113<br />

$47,720<br />

$4,772<br />

$9,042<br />

$3,014<br />

$3,617<br />

N/A<br />

$759<br />

$7,081<br />

$708<br />

Totals: $52,492 $7,789<br />

Total Project Cost: $75,954<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $75,954<br />

Rebate/Incentive*:<br />

$37,557<br />

Net Project Cost: $38,397<br />

Net Simple Payback Period (yrs): 2.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

156,488<br />

0<br />

$13,771<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace existing GYM HID fixtures with new fluorescent fixtures<br />

highbays w/sensors<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SAC<br />

Building Key: 04C4360<br />

Basic Gross Area (sf): 113,383<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3217<br />

<strong>UC</strong>LA SAC Gym <strong>UC</strong> SEP Custom Calculation.NAM.xls<br />

Project Description Reference(s): Lighting Project 4. Interior High Bay Lighting .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

113,896<br />

13.0<br />

Equipment Description Qty<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

113,896<br />

0<br />

$27,335<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

4L F54T5HO High Bay (or 6-32T8 HLO) w/sensor 56 $250.00 $14,350 $150.00 $9,416<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$14,350 $9,416<br />

$1,184<br />

$1,864<br />

$17,398<br />

$1,740<br />

$4,611<br />

$1,537<br />

$1,844<br />

N/A<br />

$1,130<br />

$10,546<br />

$1,055<br />

Totals: $19,138 $11,601<br />

Total Project Cost: $38,731<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $38,731<br />

Rebate/Incentive*:<br />

$27,335<br />

Net Project Cost: $11,396<br />

Net Simple Payback Period (yrs): 1.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

113,896<br />

0<br />

$10,023<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace gym HID and strength & conditioning fixtures with new<br />

fluorescent fixtures highbays (sensors in gyms only)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SAC<br />

Building Key: 04C4360<br />

Basic Gross Area (sf): 113,383<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3218<br />

<strong>UC</strong>LA Wooden Gym <strong>UC</strong> SEP Custom Calc.NAM.xls<br />

Project Description Reference(s): Lighting Project 4. Interior High Bay Lighting .<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

229,211<br />

30.0<br />

Equipment Description Qty<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

229,211<br />

0<br />

$55,011<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

4L F54T5HO High Bay (or 6-32T8 HLO) no sensor 47 $150.00 $7,226 $150.00 $7,903<br />

4L F54T5HO High Bay (or 6-32T8 HLO) w/sensor 85 $250.00 $21,781 $150.00 $14,293<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$29,008 $22,196<br />

$2,393<br />

$3,768<br />

$35,169<br />

$3,517<br />

$9,905<br />

$3,302<br />

$3,962<br />

N/A<br />

$2,663<br />

$24,859<br />

$2,486<br />

Totals: $38,686 $27,345<br />

Total Project Cost: $83,199<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $83,199<br />

Rebate/Incentive*:<br />

$55,011<br />

Net Project Cost: $28,188<br />

Net Simple Payback Period (yrs): 1.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

229,211<br />

0<br />

$20,171<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Retrofit all F32T8 fixtures with 28W F32 T8 lamps and RLO ballasts,<br />

and install additional occupancy sensors<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3219<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

15,977,250<br />

4,590.0<br />

Equipment Description Qty<br />

<strong>UC</strong>LA T8 to 28W T8 Lighting Custom Calc checked JCR.xls<br />

Project Description Reference(s): Lighting Project 1. Interior Linear Fluorescent Lighting & Lighting Project 2. Interior Lighting Controls.<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

15,977,250<br />

0<br />

$3,834,540<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

2L 2F32T8 (28-watt) retrofit 270,000 $18.00 $4,981,500 $25.00 $7,566,750<br />

Occupancy Sensor 22,500 $43.00 $991,688 $53.00 $1,336,793<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$5,973,188 $8,903,543<br />

$492,788<br />

$775,917<br />

$7,241,893<br />

$724,189<br />

$2,840,287<br />

$946,762<br />

$1,136,115<br />

N/A<br />

$1,068,425<br />

$9,971,968<br />

$997,197<br />

Totals: $7,966,082 $10,969,164<br />

Total Project Cost: $23,858,410<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $23,858,410<br />

Rebate/Incentive*:<br />

$3,834,540<br />

Net Project Cost: $20,023,870<br />

Net Simple Payback Period (yrs): 14.2<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

15,977,250<br />

0<br />

$1,405,998<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SCHOENBERG<br />

Building Key: 04C4335<br />

Basic Gross Area (sf): 122,552<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3220<br />

<strong>UC</strong>LA VAV scoping study report 04-17-2008.xlsx<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Savings from Cogent<br />

Analysis, Costs from SEP Results<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

316,831<br />

0.0<br />

0<br />

198,917<br />

3,537<br />

Equipment Description Qty<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 475,965<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

44,213<br />

Extended Bare<br />

Labor Cost ($)<br />

$158,444<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$114,167<br />

$11,417<br />

$31,396<br />

$10,465<br />

$12,558<br />

N/A<br />

$76,111<br />

$7,611<br />

Totals: $125,584 $83,723<br />

Total Project Cost: $263,726<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $263,726<br />

Rebate/Incentive*:<br />

$158,444<br />

Net Project Cost: $105,282<br />

Net Simple Payback Period (yrs): 1.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

680,760<br />

0<br />

$59,907<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: PUBLIC AFFAIRS<br />

Building Key: 04C4579<br />

Basic Gross Area (sf): 201,667<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3221<br />

<strong>UC</strong>LA VAV scoping study report 04-17-2008.xlsx<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Savings from Cogent<br />

Analysis, Costs from SEP Results<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

206,642<br />

0.0<br />

0<br />

69,336<br />

1,507<br />

Equipment Description Qty<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 262,111<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

18,838<br />

Extended Bare<br />

Labor Cost ($)<br />

$81,744<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$146,786<br />

$14,679<br />

$40,366<br />

$13,455<br />

$16,146<br />

N/A<br />

$97,858<br />

$9,786<br />

Totals: $161,465 $107,643<br />

Total Project Cost: $339,076<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $339,076<br />

Rebate/Incentive*:<br />

$81,744<br />

Net Project Cost: $257,332<br />

Net Simple Payback Period (yrs): 8.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

350,601<br />

0<br />

$30,853<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MACGOWAN<br />

Building Key: 04C4578<br />

Basic Gross Area (sf): 129,542<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3222<br />

<strong>UC</strong>LA VAV scoping study report 04-17-2008.xlsx<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Savings from Cogent<br />

Analysis, Costs from SEP Results<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

196,395<br />

0.0<br />

0<br />

41,057<br />

1,731<br />

Equipment Description Qty<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 229,241<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

21,638<br />

Extended Bare<br />

Labor Cost ($)<br />

$76,655<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$130,477<br />

$13,048<br />

$35,881<br />

$11,960<br />

$14,352<br />

N/A<br />

$86,984<br />

$8,698<br />

Totals: $143,524 $95,683<br />

Total Project Cost: $301,401<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $301,401<br />

Rebate/Incentive*:<br />

$76,655<br />

Net Project Cost: $224,746<br />

Net Simple Payback Period (yrs): 7.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

333,970<br />

0<br />

$29,389<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FRANZ HALL<br />

Building Key: 04C4319<br />

Basic Gross Area (sf): 238,054<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3223<br />

<strong>UC</strong>LA VAV scoping study report 04-17-2008.xlsx<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Savings from Cogent<br />

Analysis, Costs from SEP Results<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

303,182<br />

0.0<br />

0<br />

62,461<br />

1,704<br />

Equipment Description Qty<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 353,151<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

21,300<br />

Extended Bare<br />

Labor Cost ($)<br />

$106,056<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$130,477<br />

$13,048<br />

$35,881<br />

$11,960<br />

$14,352<br />

N/A<br />

$86,984<br />

$8,698<br />

Totals: $143,524 $95,683<br />

Total Project Cost: $301,401<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $301,401<br />

Rebate/Incentive*:<br />

$106,056<br />

Net Project Cost: $195,345<br />

Net Simple Payback Period (yrs): 4.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

454,484<br />

0<br />

$39,995<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MELNITZ HALL<br />

Building Key: 04C4577A<br />

Basic Gross Area (sf): 61,827<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3224<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

56,857<br />

1.0<br />

0<br />

38,536<br />

353<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 87,686<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

4,413<br />

Extended Bare<br />

Labor Cost ($)<br />

$25,457<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$32,619<br />

$3,262<br />

$8,970<br />

$2,990<br />

$3,588<br />

N/A<br />

$21,746<br />

$2,175<br />

Totals: $35,881 $23,921<br />

Total Project Cost: $75,350<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $75,350<br />

Rebate/Incentive*:<br />

$25,457<br />

Net Project Cost: $49,893<br />

Net Simple Payback Period (yrs): 5.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

106,630<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

0<br />

$9,383


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MURPHY HALL<br />

Building Key: 04C4200<br />

Basic Gross Area (sf): 220,188<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3225<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

85,286<br />

2.0<br />

0<br />

57,805<br />

529<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 131,530<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

6,613<br />

Extended Bare<br />

Labor Cost ($)<br />

$38,180<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,929<br />

$4,893<br />

$13,455<br />

$4,485<br />

$5,382<br />

N/A<br />

$32,619<br />

$3,262<br />

Totals: $53,822 $35,881<br />

Total Project Cost: $113,025<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $113,025<br />

Rebate/Incentive*:<br />

$38,180<br />

Net Project Cost: $74,845<br />

Net Simple Payback Period (yrs): 5.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

159,915<br />

0<br />

$14,073<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: REHAB CENTER<br />

Building Key: 04C4594<br />

Basic Gross Area (sf): 142,566<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3226<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

933,037<br />

23.0<br />

0<br />

360,343<br />

7,320<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 1,221,311<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

91,500<br />

Extended Bare<br />

Labor Cost ($)<br />

$384,615<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$163,096<br />

$16,310<br />

$44,851<br />

$14,950<br />

$17,941<br />

N/A<br />

$108,731<br />

$10,873<br />

Totals: $179,406 $119,604<br />

Total Project Cost: $376,752<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $376,752<br />

Rebate/Incentive*:<br />

$301,401<br />

Net Project Cost: $75,350<br />

Net Simple Payback Period (yrs): 0.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,649,252<br />

0<br />

$145,134<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BOYER HALL<br />

Building Key: 04C4403<br />

Basic Gross Area (sf): 133,042<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3227<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

272,885<br />

7.0<br />

0<br />

123,664<br />

3,642<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 371,816<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

45,525<br />

Extended Bare<br />

Labor Cost ($)<br />

$134,761<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$114,167<br />

$11,417<br />

$31,396<br />

$10,465<br />

$12,558<br />

N/A<br />

$76,111<br />

$7,611<br />

Totals: $125,584 $83,723<br />

Total Project Cost: $263,726<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $263,726<br />

Rebate/Incentive*:<br />

$134,761<br />

Net Project Cost: $128,965<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

589,184<br />

0<br />

$51,848<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BRAIN RSCH<br />

Building Key: 04C4332B<br />

Basic Gross Area (sf): 86,578<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3228<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

467,804<br />

13.0<br />

0<br />

211,996<br />

6,244<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 637,401<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

78,050<br />

Extended Bare<br />

Labor Cost ($)<br />

$231,026<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$195,715<br />

$19,572<br />

$53,822<br />

$17,941<br />

$21,529<br />

N/A<br />

$130,477<br />

$13,048<br />

Totals: $215,287 $143,524<br />

Total Project Cost: $452,102<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $452,102<br />

Rebate/Incentive*:<br />

$231,026<br />

Net Project Cost: $221,076<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,010,067<br />

0<br />

$88,886<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: DENTISTRY<br />

Building Key: 04C4334<br />

Basic Gross Area (sf): 204,369<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3229<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

350,853<br />

10.0<br />

0<br />

158,997<br />

4,683<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 478,051<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

58,538<br />

Extended Bare<br />

Labor Cost ($)<br />

$173,270<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$146,786<br />

$14,679<br />

$40,366<br />

$13,455<br />

$16,146<br />

N/A<br />

$97,858<br />

$9,786<br />

Totals: $161,465 $107,643<br />

Total Project Cost: $339,076<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $339,076<br />

Rebate/Incentive*:<br />

$173,270<br />

Net Project Cost: $165,806<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

757,550<br />

0<br />

$66,664<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: FACTOR<br />

Building Key: 04C4336<br />

Basic Gross Area (sf): 199,857<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3230<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

272,885<br />

7.0<br />

0<br />

123,664<br />

3,642<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 371,816<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

45,525<br />

Extended Bare<br />

Labor Cost ($)<br />

$134,761<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$114,167<br />

$11,417<br />

$31,396<br />

$10,465<br />

$12,558<br />

N/A<br />

$76,111<br />

$7,611<br />

Totals: $125,584 $83,723<br />

Total Project Cost: $263,726<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $263,726<br />

Rebate/Incentive*:<br />

$134,761<br />

Net Project Cost: $128,965<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

589,184<br />

0<br />

$51,848<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: KNUDSEN HALL<br />

Building Key: 04C4363<br />

Basic Gross Area (sf): 164,702<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3231<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

428,820<br />

12.0<br />

0<br />

194,329<br />

5,724<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 584,283<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

71,550<br />

Extended Bare<br />

Labor Cost ($)<br />

$211,778<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$179,406<br />

$17,941<br />

$49,337<br />

$16,446<br />

$19,735<br />

N/A<br />

$119,604<br />

$11,960<br />

Totals: $197,346 $131,564<br />

Total Project Cost: $414,427<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $414,427<br />

Rebate/Incentive*:<br />

$211,778<br />

Net Project Cost: $202,649<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

925,914<br />

0<br />

$81,480<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MATH SCIENCE<br />

Building Key: 04C4359<br />

Basic Gross Area (sf): 224,078<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3232<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

272,885<br />

7.0<br />

0<br />

123,664<br />

3,642<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 371,816<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

45,525<br />

Extended Bare<br />

Labor Cost ($)<br />

$134,761<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$114,167<br />

$11,417<br />

$31,396<br />

$10,465<br />

$12,558<br />

N/A<br />

$76,111<br />

$7,611<br />

Totals: $125,584 $83,723<br />

Total Project Cost: $263,726<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $263,726<br />

Rebate/Incentive*:<br />

$134,761<br />

Net Project Cost: $128,965<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

589,184<br />

0<br />

$51,848<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: HEALTH SCI<br />

Building Key: 04C4332D<br />

Basic Gross Area (sf): 1,265,387<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3233<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

584,755<br />

16.0<br />

0<br />

264,995<br />

7,805<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 796,751<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

97,563<br />

Extended Bare<br />

Labor Cost ($)<br />

$288,783<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$244,644<br />

$24,464<br />

$67,277<br />

$22,426<br />

$26,911<br />

N/A<br />

$163,096<br />

$16,310<br />

Totals: $269,108 $179,406<br />

Total Project Cost: $565,127<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $565,127<br />

Rebate/Incentive*:<br />

$288,783<br />

Net Project Cost: $276,344<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

1,262,583<br />

0<br />

$111,107<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: REED RESRCH<br />

Building Key: 04C4329<br />

Basic Gross Area (sf): 69,176<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3234<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

116,951<br />

3.0<br />

0<br />

52,999<br />

1,561<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 159,350<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

19,513<br />

Extended Bare<br />

Labor Cost ($)<br />

$57,757<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$48,929<br />

$4,893<br />

$13,455<br />

$4,485<br />

$5,382<br />

N/A<br />

$32,619<br />

$3,262<br />

Totals: $53,822 $35,881<br />

Total Project Cost: $113,025<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $113,025<br />

Rebate/Incentive*:<br />

$57,757<br />

Net Project Cost: $55,268<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

252,517<br />

0<br />

$22,221<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SLICHTER<br />

Building Key: 04C4227<br />

Basic Gross Area (sf): 62,557<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3235<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

155,935<br />

4.0<br />

0<br />

70,665<br />

2,081<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 212,467<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

26,013<br />

Extended Bare<br />

Labor Cost ($)<br />

$77,005<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$65,238<br />

$6,524<br />

$17,941<br />

$5,980<br />

$7,176<br />

N/A<br />

$43,492<br />

$4,349<br />

Totals: $71,762 $47,841<br />

Total Project Cost: $150,701<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $150,701<br />

Rebate/Incentive*:<br />

$77,005<br />

Net Project Cost: $73,696<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

336,668<br />

0<br />

$29,627<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WARREN HALL<br />

Building Key: 04C4581<br />

Basic Gross Area (sf): 102,205<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3236<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

194,918<br />

5.0<br />

0<br />

88,332<br />

2,602<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 265,584<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

32,525<br />

Extended Bare<br />

Labor Cost ($)<br />

$96,265<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$81,548<br />

$8,155<br />

$22,426<br />

$7,475<br />

$8,970<br />

N/A<br />

$54,365<br />

$5,437<br />

Totals: $89,703 $59,802<br />

Total Project Cost: $188,376<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $188,376<br />

Rebate/Incentive*:<br />

$96,265<br />

Net Project Cost: $92,111<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

420,882<br />

0<br />

$37,038<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Dual Duct Conversion to VAV (Cogent Report)<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: YOUNG HALL<br />

Building Key: 04C4228B<br />

Basic Gross Area (sf): 297,589<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3237<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

233,902<br />

6.0<br />

0<br />

105,998<br />

3,122<br />

Equipment Description Qty<br />

<strong>UC</strong> SEP Custom Calculation - <strong>UC</strong>LA Extrapolated Savings.xls<br />

Project Description Reference(s): Air Handler Project 2. Convert Constant Volume Air Handlers to Variable Air Volume. Extrapolated from SEP<br />

Results of Similar Buildings<br />

Estimated Cosntruction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr): 318,700<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

39,025<br />

Extended Bare<br />

Labor Cost ($)<br />

$115,513<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$97,858<br />

$9,786<br />

$26,911<br />

$8,970<br />

$10,764<br />

N/A<br />

$65,238<br />

$6,524<br />

Totals: $107,643 $71,762<br />

Total Project Cost: $226,051<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $226,051<br />

Rebate/Incentive*:<br />

$115,513<br />

Net Project Cost: $110,538<br />

Net Simple Payback Period (yrs): 2.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

505,033<br />

0<br />

$44,443<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - WESTWOO<br />

Building: MED PLZA 100<br />

Building Key: 04C4006<br />

Basic Gross Area (sf): 50,679<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3501<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

95,783<br />

11.0<br />

10,288<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

95,783<br />

10,288<br />

Extended Bare<br />

Labor Cost ($)<br />

$33,276<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$15,457<br />

$3,864<br />

$11,593<br />

$3,864<br />

$4,637<br />

N/A<br />

$46,371<br />

$11,593<br />

Totals: $19,321 $57,964<br />

Total Project Cost: $97,379<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $97,379<br />

Rebate/Incentive*:<br />

$33,276<br />

Net Project Cost: $64,103<br />

Net Simple Payback Period (yrs): 4.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

159,980<br />

0<br />

$14,078<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - SANTA MO<br />

Building: SMH EMERGCY<br />

Building Key: 04C510B<br />

Basic Gross Area (sf): 18,059<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3503<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

34,132<br />

4.0<br />

3,666<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

34,132<br />

3,666<br />

Extended Bare<br />

Labor Cost ($)<br />

$11,858<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$5,508<br />

$1,377<br />

$4,131<br />

$1,377<br />

$1,652<br />

N/A<br />

$16,524<br />

$4,131<br />

Totals: $6,885 $20,655<br />

Total Project Cost: $34,700<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $34,700<br />

Rebate/Incentive*:<br />

$11,858<br />

Net Project Cost: $22,842<br />

Net Simple Payback Period (yrs): 3.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

34,132<br />

4,583<br />

$6,074


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - SANTA MO<br />

Building: SMH PAVILION<br />

Building Key: 04C510D<br />

Basic Gross Area (sf): 194,181<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3505<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

367,002<br />

42.0<br />

39,419<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

367,002<br />

39,419<br />

$127,499<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$59,225<br />

$14,806<br />

$44,419<br />

$14,806<br />

$17,768<br />

N/A<br />

$177,676<br />

$44,419<br />

Totals: $74,031 $222,095<br />

Total Project Cost: $373,119<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $373,119<br />

Rebate/Incentive*:<br />

$127,499<br />

Net Project Cost: $245,620<br />

Net Simple Payback Period (yrs): 3.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

367,002<br />

49,274<br />

$65,310<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - SANTA MO<br />

Building: SMH WST TOWR<br />

Building Key: 04C510F<br />

Basic Gross Area (sf): 202,568<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3507<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

382,854<br />

44.0<br />

41,121<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

382,854<br />

41,121<br />

$133,006<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$61,783<br />

$15,446<br />

$46,337<br />

$15,446<br />

$18,535<br />

N/A<br />

$185,350<br />

$46,338<br />

Totals: $77,229 $231,688<br />

Total Project Cost: $389,234<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $389,234<br />

Rebate/Incentive*:<br />

$133,006<br />

Net Project Cost: $256,228<br />

Net Simple Payback Period (yrs): 3.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

382,854<br />

51,401<br />

$68,130<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Monitoring Based Commissioning<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - SANTA MO<br />

Building: SMH CENT PLT<br />

Building Key: 04C510H<br />

Basic Gross Area (sf): 21,427<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3509<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

16,499<br />

2.0<br />

2,250<br />

Equipment Description Qty<br />

SEP MBCx Analysis MZ 080326 Final.Checked by LCK.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

16,499<br />

2,250<br />

$6,210<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$3,268<br />

$817<br />

$2,451<br />

$817<br />

$980<br />

Extended Bare<br />

Labor Cost ($)<br />

N/A<br />

$9,803<br />

$2,451<br />

Totals: $4,085 $12,254<br />

Total Project Cost: $20,587<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $20,587<br />

Rebate/Incentive*:<br />

$6,210<br />

Net Project Cost: $14,377<br />

Net Simple Payback Period (yrs): 4.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

16,499<br />

2,813<br />

$3,336<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: MBCx Central <strong>Plan</strong>t<br />

<strong>Campus</strong>: LOS ANGELES MC<br />

Location: LOS ANGELES MED CTR - SANTA MO<br />

Building: SMH CENT PLT<br />

Building Key: 04C510H<br />

Basic Gross Area (sf): 21,427<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D3510<br />

<strong>UC</strong> SEP Central <strong>Plan</strong>t MBCx - Checked MZ 032808.xls<br />

Project Description Reference(s): Monitoring Based Commission for All SEP Buildings.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

75,000<br />

9.0<br />

6,000<br />

Equipment Description Qty<br />

Estimated Construction Cost 1<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

Raw Costs:<br />

25.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

75,000<br />

6,000<br />

Extended Bare<br />

Labor Cost ($)<br />

$24,000<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

$10,000<br />

$2,500<br />

$9,375<br />

$3,125<br />

$3,750<br />

N/A<br />

$40,000<br />

$10,000<br />

Totals: $12,500 $50,000<br />

Total Project Cost: $78,750<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $78,750<br />

Rebate/Incentive*:<br />

$24,000<br />

Net Project Cost: $54,750<br />

Net Simple Payback Period (yrs): 4.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

75,000<br />

7,500<br />

$11,625<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace Boiler<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CANYON POINT<br />

Building Key: 04C4302A<br />

Basic Gross Area (sf): 107,419<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6001<br />

<strong>UC</strong>LA Boiler Replace Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 1. Boiler Replacement.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

2,494<br />

Equipment Description Qty<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

2,494<br />

$2,494<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Boiler 1 $28,000.00 $28,700 $16,000.00 $17,936<br />

Programming 1 $500.00 $513 $800.00<br />

$897<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$29,213 $18,833<br />

$2,410<br />

$3,795<br />

$35,417<br />

$3,542<br />

$9,324<br />

$3,108<br />

$3,730<br />

N/A<br />

$2,260<br />

$21,093<br />

$2,109<br />

Totals: $38,959 $23,202<br />

Total Project Cost: $78,323<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $78,323<br />

Rebate/Incentive*:<br />

$2,494<br />

Net Project Cost: $75,829<br />

Net Simple Payback Period (yrs): 55.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

15,563<br />

0<br />

$1,370<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace Boiler<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: COVEL COMMON<br />

Building Key: 04C4302D<br />

Basic Gross Area (sf): 144,067<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6002<br />

<strong>UC</strong>LA Boiler Replace Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 1. Boiler Replacement.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

4,987<br />

Equipment Description Qty<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

4,987<br />

$4,987<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Boiler 2 $28,000.00 $57,400 $16,000.00 $35,872<br />

Programming 2 $500.00 $1,025 $800.00 $1,794<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$58,425 $37,666<br />

$4,820<br />

$7,589<br />

$70,834<br />

$7,083<br />

$18,648<br />

$6,216<br />

$7,459<br />

N/A<br />

$4,520<br />

$42,185<br />

$4,219<br />

Totals: $77,918 $46,404<br />

Total Project Cost: $156,646<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $156,646<br />

Rebate/Incentive*:<br />

$4,987<br />

Net Project Cost: $151,659<br />

Net Simple Payback Period (yrs): 55.4<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

31,119<br />

0<br />

$2,738<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace Boiler<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: UNEX<br />

Building Key: 04C4415<br />

Basic Gross Area (sf): 95,065<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6003<br />

<strong>UC</strong>LA Boiler Replace Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 1. Boiler Replacement.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

0<br />

0.0<br />

5,938<br />

Equipment Description Qty<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

0<br />

5,938<br />

$5,938<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Programming 2 $500.00 $1,025 $800.00 $1,794<br />

Boiler 2 $28,000.00 $57,400 $16,000.00 $35,872<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$58,425 $37,666<br />

$4,820<br />

$7,589<br />

$70,834<br />

$7,083<br />

$18,648<br />

$6,216<br />

$7,459<br />

N/A<br />

$4,520<br />

$42,185<br />

$4,219<br />

Totals: $77,918 $46,404<br />

Total Project Cost: $156,646<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $156,646<br />

Rebate/Incentive*:<br />

$5,938<br />

Net Project Cost: $150,708<br />

Net Simple Payback Period (yrs): 46.2<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

37,053<br />

0<br />

$3,261<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace Chiller<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SOUTHERN REGIONAL LIBRARY FACI<br />

Building Key: 04C4562<br />

Basic Gross Area (sf): 228,306<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6004<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

264,354<br />

80.0<br />

Equipment Description Qty<br />

/26. Sourthern Regional Library FAC/<strong>UC</strong> SEP Custom Calculation - SRLF Chiller Replacement.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 2. Chiller Replacement.<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

264,354<br />

0<br />

$63,445<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

140 ton Chiller 2 $67,200.00 $137,760 $44,800.00 $100,442<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$137,760 $100,442<br />

$11,365<br />

$17,895<br />

$167,020<br />

$16,702<br />

$46,120<br />

$15,373<br />

$18,448<br />

N/A<br />

$12,053<br />

$112,495<br />

$11,249<br />

Totals: $183,722 $123,744<br />

Total Project Cost: $387,408<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $387,408<br />

Rebate/Incentive*:<br />

$63,445<br />

Net Project Cost: $323,963<br />

Net Simple Payback Period (yrs): 13.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

264,354<br />

0<br />

$23,263<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace Chiller<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: UNEX<br />

Building Key: 04C4415<br />

Basic Gross Area (sf): 95,065<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6005<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

212,201<br />

72.0<br />

Equipment Description Qty<br />

/29. UNEX/<strong>UC</strong> SEP Custom Calculation - UNEX Chiller Replacement.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 2. Chiller Replacement.<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

212,201<br />

0<br />

$50,928<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

150 ton Chiller 2 $60,000.00 $123,000 $42,000.00 $94,164<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$123,000 $94,164<br />

$10,148<br />

$15,978<br />

$149,125<br />

$14,913<br />

$42,007<br />

$14,002<br />

$16,803<br />

N/A<br />

$11,300<br />

$105,464<br />

$10,546<br />

Totals: $164,038 $116,010<br />

Total Project Cost: $352,860<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $352,860<br />

Rebate/Incentive*:<br />

$50,928<br />

Net Project Cost: $301,932<br />

Net Simple Payback Period (yrs): 16.2<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

212,201<br />

0<br />

$18,674<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Replace Chiller<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: WILSHIRE CTR<br />

Building Key: 04C4270<br />

Basic Gross Area (sf): 455,912<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6006<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

304,707<br />

98.0<br />

Equipment Description Qty<br />

/27. Wilshire CTR/<strong>UC</strong> SEP Custom Calculation - Willshire Chiller Replacement.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 2. Chiller Replacement.<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

304,707<br />

0<br />

$73,130<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

350 ton chiller 2 $147,000.00 $301,350 $98,000.00 $219,716<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$301,350 $219,716<br />

$24,861<br />

$39,145<br />

$365,357<br />

$36,536<br />

$100,887<br />

$33,629<br />

$40,355<br />

N/A<br />

$26,366<br />

$246,082<br />

$24,608<br />

Totals: $401,892 $270,690<br />

Total Project Cost: $847,454<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $847,454<br />

Rebate/Incentive*:<br />

$73,130<br />

Net Project Cost: $774,324<br />

Net Simple Payback Period (yrs): 28.9<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

304,707<br />

0<br />

$26,814<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CW Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CORNELL HALL<br />

Building Key: 04C515D<br />

Basic Gross Area (sf): 71,737<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6007<br />

<strong>UC</strong>LA Condenser Water Reset Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 4. Condenser Water Reset.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

68,040<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

68,040<br />

0<br />

Extended Bare<br />

Labor Cost ($)<br />

$16,330<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Programming 4 $500.00 $2,050 $800.00 $3,587<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$2,050 $3,587<br />

$169<br />

$266<br />

$2,485<br />

$249<br />

$1,073<br />

$358<br />

$429<br />

N/A<br />

$430<br />

$4,018<br />

$402<br />

Totals: $2,734 $4,419<br />

Total Project Cost: $9,013<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $9,013<br />

Rebate/Incentive*:<br />

$7,211<br />

Net Project Cost: $1,803<br />

Net Simple Payback Period (yrs): 0.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

68,040<br />

0<br />

$5,988


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CW Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: MED PLZA 300<br />

Building Key: 04C4345<br />

Basic Gross Area (sf): 101,095<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6008<br />

<strong>UC</strong>LA Condenser Water Reset Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 4. Condenser Water Reset.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

170,100<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

170,100<br />

0<br />

$40,824<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Programming 4 $500.00 $2,050 $800.00 $3,587<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$2,050 $3,587<br />

$169<br />

$266<br />

$2,485<br />

$249<br />

$1,073<br />

$358<br />

$429<br />

N/A<br />

$430<br />

$4,018<br />

$402<br />

Totals: $2,734 $4,419<br />

Total Project Cost: $9,013<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $9,013<br />

Rebate/Incentive*:<br />

$7,211<br />

Net Project Cost: $1,803<br />

Net Simple Payback Period (yrs): 0.1<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

170,100<br />

0<br />

$14,969<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CW Reset<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: SOUTHERN REGIONAL LIBRARY FACI<br />

Building Key: 04C4562<br />

Basic Gross Area (sf): 228,306<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6009<br />

<strong>UC</strong>LA Condenser Water Reset Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 4. Condenser Water Reset.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

40,032<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

40,032<br />

0<br />

$9,608<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Programming 4 $500.00 $2,050 $800.00 $3,587<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$2,050 $3,587<br />

$169<br />

$266<br />

$2,485<br />

$249<br />

$1,073<br />

$358<br />

$429<br />

N/A<br />

$430<br />

$4,018<br />

$402<br />

Totals: $2,734 $4,419<br />

Total Project Cost: $9,013<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $9,013<br />

Rebate/Incentive*:<br />

$7,211<br />

Net Project Cost: $1,803<br />

Net Simple Payback Period (yrs): 0.5<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

40,032<br />

0<br />

$3,523<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CT VFDs<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: TIVERTON HSE<br />

Building Key: 04C4265<br />

Basic Gross Area (sf): 121,634<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6010<br />

<strong>UC</strong>LA CT VFD Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 5. Install VFDs on Cooling Towers.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

24,661<br />

Equipment Description Qty<br />

4.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

24,661<br />

0<br />

$5,919<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Programming 1 $500.00 $513 $800.00<br />

$897<br />

25 hp VFD 1 $3,925.00 $4,023 $1,100.00 $1,233<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$4,536 $2,130<br />

$374<br />

$589<br />

$5,499<br />

$550<br />

$1,301<br />

$434<br />

$520<br />

N/A<br />

$256<br />

$2,385<br />

$239<br />

Totals: $6,049 $2,624<br />

Total Project Cost: $10,928<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $10,928<br />

Rebate/Incentive*:<br />

$5,919<br />

Net Project Cost: $5,009<br />

Net Simple Payback Period (yrs): 2.3<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

24,661<br />

0<br />

$2,170<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: CT VFDs<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: UNEX<br />

Building Key: 04C4415<br />

Basic Gross Area (sf): 95,065<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6011<br />

<strong>UC</strong>LA CT VFD Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 5. Install VFDs on Cooling Towers.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

11,650<br />

Equipment Description Qty<br />

2.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

11,650<br />

0<br />

$2,796<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Programming 1 $500.00 $513 $800.00<br />

$897<br />

15 hp VFD 1 $2,275.00 $2,332 $820.00<br />

$919<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$2,844 $1,816<br />

$235<br />

$369<br />

$3,449<br />

$345<br />

$905<br />

$302<br />

$362<br />

N/A<br />

$218<br />

$2,034<br />

$203<br />

Totals: $3,793 $2,237<br />

Total Project Cost: $7,599<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $7,599<br />

Rebate/Incentive*:<br />

$2,796<br />

Net Project Cost: $4,803<br />

Net Simple Payback Period (yrs): 4.7<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

11,650<br />

0<br />

$1,025<br />

Backup


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: Pump VFDs<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: CAMPUSWIDE<br />

Building Key: 04CWIDE<br />

Basic Gross Area (sf):<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6012<br />

<strong>UC</strong>LA Pump VFD Calculation-Multiple.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 6. Variable Speed Drives on Pumps.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

201,511<br />

34.0<br />

Equipment Description Qty<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

Extended Bare<br />

Labor Cost ($)<br />

201,511<br />

0<br />

$48,363<br />

Backup<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

7.5 hp 3 $1,975.00 $6,073 $545.00 $1,833<br />

10 hp 3 $1,975.00 $6,073 $545.00 $1,833<br />

15 hp 5 $2,275.00 $11,659 $820.00 $4,596<br />

20 hp 4 $3,375.00 $13,838 $820.00 $3,677<br />

Programming 15 $500.00 $7,688 $800.00 $13,452<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$45,331 $25,391<br />

$3,740<br />

$5,888<br />

$54,959<br />

$5,496<br />

$13,760<br />

$4,587<br />

$5,504<br />

N/A<br />

$3,047<br />

$28,438<br />

$2,844<br />

Totals: $60,455 $31,281<br />

Total Project Cost: $115,587<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $115,587<br />

Rebate/Incentive*:<br />

$48,363<br />

Net Project Cost: $67,224<br />

Net Simple Payback Period (yrs): 3.8<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

201,511<br />

0<br />

$17,733<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.


PROJECT DETAIL REPORT<br />

SEP Project ID Number:<br />

Project: TOD EF<br />

<strong>Campus</strong>: LOS ANGELES<br />

Location: LOS ANGELES<br />

Building: BUNCHE HALL<br />

Building Key: 04C4580<br />

Basic Gross Area (sf): 229,248<br />

Calculation File:<br />

Project <strong>Energy</strong> Savings Summary<br />

Electric (kWh/yr):<br />

Peak Demand (kW):<br />

Gas (th/yr):<br />

Chilled Water (ton-hr/yr):<br />

HW/Steam (MMBTu/yr):<br />

Project Cost Summary<br />

D6013<br />

<strong>UC</strong>LA TOD on EF Calculation.xls<br />

Project Description Reference(s): <strong>UC</strong>LA Custom Project 3. TOD Controls on Exhaust Fans.<br />

Building <strong>Energy</strong> Savings Incentive Calculation Basis<br />

8,081<br />

Equipment Description Qty<br />

0.0<br />

0<br />

0<br />

0<br />

Assumed Incentive Rates: Central <strong>Plan</strong>t Efficiencies:<br />

Electricity $0.24 per annual kWh th/MMBTU: 12.5<br />

Natural Gas $1 per annual therm kWh/ton-hr: 0.8<br />

th/ton-hr: 0.0<br />

Equivalent Electric Savings (kWh/yr):<br />

Equivalent Gas Savings (th/yr):<br />

Anticipated Gross Incentive:<br />

Bare Material Extended Bare<br />

Cost per Unit ($) Material Cost ($)<br />

<strong>Campus</strong> Prioritization and Schedule<br />

Project Tier:<br />

Start Preliminary Engineering:<br />

Scheduled Completion:<br />

Bare Labor Cost<br />

per Unit ($)<br />

8,081<br />

0<br />

$1,939<br />

Note: Where the anticipated gross incentive exceeds 80% of the total project<br />

cost, the incentive is capped. The net incentive amount is shown below in the<br />

Project Cost Summary.<br />

Extended Bare<br />

Labor Cost ($)<br />

Programming 1 $500.00 $513 $800.00<br />

$897<br />

City: <strong>Los</strong> <strong>Angeles</strong><br />

City Index Material Multiplier:<br />

City Index Labor Multiplier:<br />

102.5%<br />

112.1%<br />

Raw Costs:<br />

Sales Tax: 8.25%<br />

Contractor O&P: 12.00%<br />

Subtotals:<br />

Contingency:<br />

Engineering:<br />

Construction Phase:<br />

Project Management:<br />

10.00%<br />

15.00%<br />

5.00%<br />

6.00%<br />

$513 $897<br />

$42<br />

$67<br />

$621<br />

$62<br />

$268<br />

$89<br />

$107<br />

N/A<br />

$108<br />

$1,004<br />

$100<br />

Totals: $683 $1,105<br />

Total Project Cost: $2,253<br />

Project Economic Summary, Including Cogeneration and Purchased Utility Impacts<br />

Total Project Cost: $2,253<br />

Rebate/Incentive*:<br />

$1,803<br />

Net Project Cost: $451<br />

Net Simple Payback Period (yrs): 0.6<br />

Total Purchased Electricity Savings (kWh/yr):<br />

Total Purchased Gas Savings (th/yr):<br />

Total Purchased Annual Cost Savings ($/yr):<br />

*Highlighted incentives have been capped at 80% of the total project cost. It is recommended that these projects be bundled together with other projects to maximize<br />

incentive funding.<br />

8,081<br />

0<br />

$711<br />

Backup


11. PROJECT LISTS & SUMMARY OF PROJECTS<br />

The following table is a complete list of all projects identified through the SEP effort, organized<br />

by funding source and project types. Subtotals are provided for savings and costs by project<br />

type and fund source. It is anticipated that the campus may wish to sort and view the list in a<br />

number of different manners. A complete project list is also provided electronically with this<br />

report for this purpose. See Appendix C.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 11-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


Table 11.1: SEP Projects by Funding Source and Project Type<br />

Net<br />

Simple<br />

Payback<br />

(yrs)<br />

Net Project<br />

Cost ($)<br />

Gross<br />

Estimated<br />

Utility<br />

Incentive ($)<br />

Estimated<br />

Project Cost ($)<br />

Total Cost<br />

Savings ($/yr)<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

Demand<br />

Savings (kW)<br />

Total<br />

Purchased<br />

Electricity<br />

Savings<br />

(kWh/yr)<br />

Building<br />

Key Building Name Project Name<br />

SEP<br />

Project<br />

ID<br />

State Funded Buildings<br />

MBCx Projects<br />

D3124 04C4200 MURPHY HALL Monitoring Based Commissioning 313,814<br />

19.0<br />

- $ 27,616 $ 186,161 $ 63,811 $ 122,350 4.4<br />

D3003 04C4202 PERLOFF HALL Monitoring Based Commissioning 93,931<br />

6.0<br />

- $ 8,266 $ 55,723 $ 19,100 $ 36,623 4.4<br />

D3004 04C4203 YOUNG LIBRY Monitoring Based Commissioning 435,993<br />

27.0<br />

- $ 38,367 $ 258,643 $ 88,655 $ 169,988 4.4<br />

D3128 04C4227 SLICHTER Monitoring Based Commissioning 89,153<br />

6.0<br />

- $ 7,845 $ 52,890 $ 18,129 $ 34,761 4.4<br />

D3008 04C4228A GEOLOGY Monitoring Based Commissioning 574,992<br />

39.0<br />

- $ 50,599 $ 307,998 $ 119,599 $ 188,399 3.7<br />

D3131 04C4228B YOUNG HALL Monitoring Based Commissioning 939,408<br />

64.0<br />

- $ 82,668 $ 503,200 $ 195,397 $ 307,803 3.7<br />

D3009 04C4228C MOLECULR SCI Monitoring Based Commissioning 563,998<br />

38.0<br />

- $ 49,632 $ 302,109 $ 117,312 $ 184,797 3.7<br />

D3011 04C4235 WOODEN/PS4 Monitoring Based Commissioning 296,046<br />

18.0<br />

- $ 26,052 $ 175,619 $ 60,198 $ 115,421 4.4<br />

D3013 04C4256A ENGR BLDG 4 Monitoring Based Commissioning 928,466<br />

64.0<br />

- $ 81,705 $ 497,340 $ 193,122 $ 304,218 3.7<br />

D3014 04C4260 FACMGMT BLDG Monitoring Based Commissioning 269,646<br />

17.0<br />

- $ 23,729 $ 159,960 $ 54,830 $ 105,130 4.4<br />

D3022 04C4315 GONDA CENTER Monitoring Based Commissioning 395,228<br />

27.0<br />

- $ 34,780 $ 211,707 $ 82,208 $ 129,499 3.7<br />

D3023 04C4317 LAW Monitoring Based Commissioning 392,555<br />

24.0<br />

- $ 34,545 $ 232,872 $ 79,822 $ 153,050 4.4<br />

D3024 04C4318A POWELL LIB Monitoring Based Commissioning 237,790<br />

15.0<br />

- $ 20,925 $ 141,062 $ 48,352 $ 92,710 4.4<br />

D3143 04C4319 FRANZ HALL Monitoring Based Commissioning 751,470<br />

51.0<br />

- $ 66,129 $ 402,529 $ 156,306 $ 246,223 3.7<br />

D3025 04C4320 LIFE SCIENCE Monitoring Based Commissioning 677,471<br />

46.0<br />

- $ 59,617 $ 362,894 $ 140,915 $ 221,979 3.7<br />

D3026 04C4325 DORIS STEIN Monitoring Based Commissioning 297,709<br />

20.0<br />

- $ 26,198 $ 159,469 $ 61,924 $ 97,545 3.7<br />

D3147 04C4329 REED RESRCH Monitoring Based Commissioning 218,371<br />

15.0<br />

- $ 19,217 $ 116,971 $ 45,421 $ 71,550 3.7<br />

D3027 04C4331 PUBLIC HLTH HLTH Monitoring Based Based Commissioning Commissioning 443 443,716 716 30 30.0 0 - $ 39 39,047 047 $ 237 237,681 681 $ 92 92,293 293 $ 145 145,388 388 37 3.7<br />

D3150 04C4332B BRAIN RSCH Monitoring Based Commissioning 273,300<br />

19.0<br />

- $ 24,050 $ 146,396 $ 56,847 $ 89,549 3.7<br />

D3028 04C4332E M DAVIES CC Monitoring Based Commissioning 221,688<br />

15.0<br />

- $ 19,509 $ 118,751 $ 46,111 $ 72,640 3.7<br />

D3030 04C4333 JULES STEIN Monitoring Based Commissioning 277,493<br />

19.0<br />

- $ 24,419 $ 148,640 $ 57,719 $ 90,921 3.7<br />

D3154 04C4334 DENTISTRY Monitoring Based Commissioning 645,136<br />

44.0<br />

- $ 56,772 $ 345,573 $ 134,189 $ 211,384 3.7<br />

D3156 04C4335 SCHOENBERG Monitoring Based Commissioning 174,661<br />

11.0<br />

- $ 15,370 $ 103,613 $ 35,516 $ 68,097 4.4<br />

D3158 04C4336 FACTOR Monitoring Based Commissioning 630,893<br />

43.0<br />

- $ 55,519 $ 337,941 $ 131,226 $ 206,715 3.7<br />

D3032 04C4343 BOELTER HALL Monitoring Based Commissioning 1,180,314<br />

81.0<br />

- $ 103,868 $ 632,242 $ 245,506 $ 386,736 3.7<br />

D3033 04C4344 MORTON MED Monitoring Based Commissioning 1,157,990<br />

79.0<br />

- $ 101,903 $ 620,286 $ 240,863 $ 379,423 3.7<br />

D3034 04C4345 MED PLZA 300 Monitoring Based Commissioning 319,127<br />

22.0<br />

- $ 28,083 $ 170,944 $ 66,379 $ 104,565 3.7<br />

D3035 04C4348 MACDONALDLAB Monitoring Based Commissioning 456,496<br />

31.0<br />

- $ 40,172 $ 244,525 $ 94,952 $ 149,573 3.7<br />

D3164 04C4359 MATH SCIENCE Monitoring Based Commissioning 707,352<br />

48.0<br />

- $ 62,247 $ 378,898 $ 147,130 $ 231,768 3.7<br />

D3168 04C4363 KNUDSEN HALL Monitoring Based Commissioning 519,921<br />

36.0<br />

- $ 45,753 $ 278,497 $ 108,144 $ 170,353 3.7<br />

D3038 04C4374 FOWLER MUSM Monitoring Based Commissioning 321,970<br />

22.0<br />

- $ 28,333 $ 172,464 $ 66,970 $ 105,494 3.7<br />

D3039 04C4375 ROYCE HALL Monitoring Based Commissioning 263,198<br />

16.0<br />

- $ 23,161 $ 156,134 $ 53,519 $ 102,615 4.4<br />

D3172 04C4403 BOYER HALL Monitoring Based Commissioning 419,979<br />

29.0<br />

- $ 36,958 $ 224,963 $ 87,356 $ 137,607 3.7<br />

D3040 04C4415 UNEX Monitoring Based Commissioning 135,488<br />

8.0<br />

- $ 11,923 $ 80,373 $ 27,550 $ 52,823 4.4<br />

SOUTHERN REGIONAL<br />

D3042 04C4562 LIBRARY FACILITY Monitoring Based Commissioning 325,381<br />

20.0<br />

- $ 28,634 $ 193,024 $ 66,163 $ 126,861 4.4<br />

D3176 04C4577A MELNITZ HALL Monitoring Based Commissioning 88,117<br />

5.0<br />

- $ 7,754 $ 52,273 $ 17,918 $ 34,355 4.4<br />

D3178 04C4578 MACGOWAN Monitoring Based Commissioning 184,623<br />

11.0<br />

- $ 16,247 $ 109,522 $ 37,541 $ 71,981 4.4<br />

D3180 04C4579 PUBLIC AFFAIRS Monitoring Based Commissioning 287,416<br />

18.0<br />

- $ 25,293 $ 170,502 $ 58,443 $ 112,059 4.4<br />

D3043 04C4580 BUNCHE HALL Monitoring Based Commissioning 326,724<br />

20.0<br />

- $ 28,752 $ 193,820 $ 66,436 $ 127,384 4.4<br />

D3183 04C4581 WARREN HALL Monitoring Based Commissioning 322,635<br />

22.0<br />

- $ 28,392 $ 172,822 $ 67,108 $ 105,714 3.7<br />

D3185 04C4594 REHAB CENTER Monitoring Based Commissioning 450,042<br />

31.0<br />

- $ 39,604 $ 241,068 $ 93,609 $ 147,459 3.7<br />

D3045 04C515A COLLINS CTR Monitoring Based Commissioning 44,626<br />

3.0<br />

- $ 3,927 $ 26,473 $ 9,074 $ 17,399 4.4<br />

D3046 04C515B GOLD HALL Monitoring Based Commissioning 78,876<br />

5.0<br />

- $ 6,941 $ 46,791 $ 16,039 $ 30,752 4.4<br />

D3047 04C515C ENTREP HALL Monitoring Based Commissioning 103,456<br />

6.0<br />

- $ 9,104 $ 61,372 $ 21,037 $ 40,335 4.4<br />

D3048 04C515D CORNELL HALL Monitoring Based Commissioning 102,237<br />

6.0<br />

- $ 8,997 $ 60,651 $ 20,789 $ 39,862 4.4<br />

D3049 04C515E ROSNFLD LIBR Monitoring Based Commissioning 72,751<br />

4.0<br />

- $ 6,402 $ 43,159 $ 14,793 $ 28,366 4.4<br />

D3050 04C515F MULLIN CMNS Monitoring Based Commissioning 48,393<br />

3.0<br />

- $ 4,259 $ 28,708 $ 9,840 $ 18,868 4.4<br />

D3084 04CWIDE CAMPUSWIDE MBCx Central <strong>Plan</strong>t 1,124,400<br />

86.0<br />

- $ 98,947 $ 693,000 $ 240,000 $ 453,000 4.6<br />

Subtotal, State Funded, MBCx Projects 19,184,439 1,289.0<br />

- $ 1,688,231 $ 10,618,251 $ 3,976,161 $ 6,642,090 3.9


Table 11.1: SEP Projects by Funding Source and Project Type (Continued)<br />

Net<br />

Simple<br />

Payback<br />

(yrs)<br />

Net Project<br />

Cost ($)<br />

Gross<br />

Estimated<br />

Utility<br />

Incentive ($)<br />

Estimated<br />

Project Cost ($)<br />

Total Cost<br />

Savings ($/yr)<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

Demand<br />

Savings (kW)<br />

Total<br />

Purchased<br />

Electricity<br />

Savings<br />

(kWh/yr)<br />

SEP<br />

Project Building<br />

ID Key Building Name Project Name<br />

New Construction Projects<br />

$ 42,141 $ 442,353 $ 100,842 $ 341,511 8.1<br />

-<br />

34.0<br />

D3005 04C4203 YOUNG LIBRY SBD, New/Renov - Young Research Library Renovation 478,877<br />

$ 109,358 $ 1,147,921 $ 261,688 $ 886,233 8.1<br />

$ 10,360 $ 108,750 $ 24,792 $ 83,958 8.1<br />

$ 170,545 $ 2,034,322 $ 408,105 $ 1,626,217 9.5<br />

$ 76,198 $ 777,227 $ 191,988 $ 585,239 7.7<br />

$ 8,637 $ 90,665 $ 20,668 $ 69,997 8.1<br />

$ 9,194 $ 93,780 $ 23,165 $ 70,615 7.7<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

90.0<br />

8.0<br />

140.0<br />

76.0<br />

7.0<br />

9.0<br />

$ 43,693 $ 445,671 $ 110,088 $ 335,583 7.7<br />

-<br />

44.0<br />

$ 48,758 $ 511,810 $ 116,676 $ 395,134 8.1<br />

-<br />

40.0<br />

D3006 04C4204 PAULEY SBD, New/Renov - Pauley Pavilion Renovation and Expansion 1,242,705<br />

D3010 04C4230 POLICE STN SBD, New/Renov - Police Station Replacement Building 117,733<br />

D3029 04C4332F SEMEL INST SBD, New/Renov - CHS South Tower Seismic Renovation 1,938,015<br />

D3031 04C4333 JULES STEIN SBD, New/Renov - Jules Stein Eye Institute Seismic Repair 865,891<br />

D3041 04C4451 CLARK LIB SBD, New/Renov - Clark Library Seismic Correction 98,149<br />

D3051 04CTBD1 CNSI - BSL 3 LABORATORY SBD, New/Renov - CNSI-BSL3 Laboratory 104,475<br />

TELEMEDICINE AND PRIME<br />

D3055 04CTBD5 FACILITIES SBD, New/Renov - Telemedicine and Prime Facilities Phase 2 496,511<br />

LETTERS AND SCIENCE<br />

D3056 04CTBD6 EXPANSION SBD, New/Renov - Letters and Science Expansion 554,072<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3083 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3082 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3081 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3080 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3079 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3078 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3077 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

$ 550,316 $ 5,982,444 $ 1,333,220 $ 4,649,224 8.4<br />

-<br />

-<br />

3.0<br />

472.0<br />

D3076 04CWIDE CAMPUSWIDE SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

Subtotal, State Funded, New Construction Projects 6,253,593<br />

$ 14,073 $ 113,025 $ 38,180 $ 74,845 5.3<br />

$ 20,070 $ 231,886 $ 56,783 $ 175,103 8.7<br />

$ 8,912 $ 33,239 $ 24,071 $ 9,168 1.0<br />

$ 82,063 $ 260,501 $ 216,698 $ 52,100 0.6<br />

$ 32,145 $ 61,824 $ 82,093 $ 12,365 0.4<br />

$ 29,627 $ 150,701 $ 77,005 $ 73,696 2.5<br />

$ 634 $ 48,656 $ 1,730 $ 46,926 74.0<br />

$ 19,735 $ 45,741 $ 50,373 $ 9,148 0.5<br />

$ 32,167 $ 176,117 $ 84,253 $ 91,864 2.9<br />

$ 44,443 $ 226,051 $ 115,513 $ 110,538 2.5<br />

$ 313,196 $ 1,155,824 $ 822,292 $ 333,532 1.1<br />

$ 1,111 $ 35,195 $ 3,027 $ 32,168 28.9<br />

$ 17,134 $ 62,008 $ 47,476 $ 14,532 0.8<br />

$ 4,359 $ 2,784 $ 11,303 $ 557 0.1<br />

$ 3,847 $ 2,784 $ 10,012 $ 557 0.1<br />

$ 5,922 $ 47,848 $ 15,355 $ 32,493 5.5<br />

$ 20,419 $ 125,784 $ 56,290 $ 69,494 3.4<br />

$ 9,066 $ 65,921 $ 24,120 $ 41,801 4.6<br />

$ 3,667 $ 36,733 $ 9,748 $ 26,985 7.4<br />

$ 9,208 $ 32,243 $ 23,860 $ 8,383 0.9<br />

$ 103,530 $ 755,712 $ 293,908 $ 461,804 4.5<br />

$ 49,169 $ 1,551,693 $ 129,310 $ 1,422,383 28.9<br />

$ 51,915 $ 126,983 $ 136,824 $ 25,397 0.5<br />

$ 8,811 $ 46,233 $ 22,944 $ 23,289 2.6<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

2.0<br />

4.0<br />

2.0<br />

63.0<br />

1.0<br />

4.0<br />

1.0<br />

2.0<br />

5.0<br />

6.0<br />

68.0<br />

-<br />

50.0<br />

-<br />

-<br />

-<br />

57.0<br />

1.0<br />

-<br />

4.0<br />

143.0<br />

22.0<br />

3.0<br />

-<br />

HVAC Projects<br />

D3225 04C4200 MURPHY HALL Dual Duct Conversion to VAV (Cogent Report) 159,915<br />

D1051 04C4202 PERLOFF HALL CAV to VAV - AHU 1, 2, 5W and 5E & Add Economizer 228,070<br />

D1050 04C4203 YOUNG LIBRY SAF 9 CAV to VAV 101,270<br />

D1049 04C4203 YOUNG LIBRY SAF-3 to 8 CAV to VAV 932,532<br />

D1048 04C4203 YOUNG LIBRY SAF-1 & 2 SP Reset 365,279<br />

D3235 04C4227 SLICHTER Dual Duct Conversion to VAV (Cogent Report) 336,668<br />

D1056 04C4228A GEOLOGY Aircuity 7,207<br />

D1055 04C4228A GEOLOGY S-1(Geophysics) 224,261<br />

D1054 04C4228A GEOLOGY S-1, 5, 9, 10 to 12 365,538<br />

D3237 04C4228B YOUNG HALL Dual Duct Conversion to VAV (Cogent Report) 505,033<br />

D1016 04C4228C MOLECULR SCI AHU 1, 2, 3, 4 & 6 Aircuity 3,559,048<br />

D1015 04C4228C MOLECULR SCI AHU - 5 VIV to VAV & SP Reset 12,629<br />

D1034 04C4235 WOODEN/PS4 AHU 4 CAV to VAV & DCV 194,701<br />

D1033 04C4235 WOODEN/PS4 AHU 2 Pace) SP reset 49,533<br />

D1032 04C4235 WOODEN/PS4 AHU 1 Pace) SP reset 43,721<br />

D1031 04C4235 WOODEN/PS4 AHU 1 (Mcquay) SP reset 67,300<br />

D1030 04C4235 WOODEN/PS4 CAV to VAV 232,032<br />

D1029 04C4235 WOODEN/PS4 AHU 3 VIV to VAV & SP Reset 103,025<br />

D1028 04C4235 WOODEN/PS4 AHU 1 VIV to VAV 41,673<br />

D1065 04C4256A ENGR BLDG 4 ACS 9 - CAV to VAV 104,641<br />

D1064 04C4256A ENGR BLDG 4 CF - 1 to 22 - VIV to VAV 1,176,481<br />

D1063 04C4256A ENGR BLDG 4 ACS 8 (AHU-3) - Aircruity 558,742<br />

D1062 04C4256A ENGR BLDG 4 ACS - 1 to 5 - SP Reset 589,949<br />

D1002 04C4260 FACMGMT BLDG AHU 1 & 2 - SP Reset 100,125<br />

(0)<br />

-<br />

-<br />

-<br />

(0)<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-


Table 11.1: SEP Projects by Funding Source and Project Type (Continued)<br />

Gross<br />

Net<br />

Estimated<br />

Simple<br />

Total Cost Estimated Utility Net Project Payback<br />

Savings ($/yr) Project Cost ($) Incentive ($) Cost ($) (yrs)<br />

$ 28,923 $ 86,096 $ 77,061 $ 17,219 0.6<br />

$ 4,319 $ 30,759 $ 11,515 $ 19,244 4.5<br />

$ 19,439 $ 81,053 $ 52,371 $ 28,682 1.5<br />

$ 6,302 $ 30,085 $ 16,811 $ 13,274 2.1<br />

$ 16,922 $ 96,194 $ 45,384 $ 50,810 3.0<br />

$ 6,787 $ 46,817 $ 17,665 $ 29,152 4.3<br />

$ 8,211 $ 44,343 $ 22,043 $ 22,300 2.7<br />

$ 2,206 $ 19,798 $ 6,071 $ 13,727 6.2<br />

$ 12,425 $ 46,563 $ 33,317 $ 13,246 1.1<br />

$ 4,057 $ 48,385 $ 11,206 $ 37,179 9.2<br />

$ 1,933 $ 36,901 $ 5,057 $ 31,844 16.5<br />

$ 39,995 $ 301,401 $ 106,056 $ 195,345 4.9<br />

$ 82,105 $ 2,503,946 $ 215,086 $ 2,288,860 27.9<br />

$ 6,739 $ 58,784 $ 17,420 $ 41,364 6.1<br />

$ 22,569 $ 117,329 $ 60,590 $ 56,739 2.5<br />

$ 22,221 $ 113,025 $ 57,757 $ 55,268 2.5<br />

$ 8,190 $ 26,664 $ 21,169 $ 5,495 0.7<br />

$ 23,358 $ 219,224 $ 61,921 $ 157,303 6.7<br />

$ 88,886 $ 452,102 $ 231,026 $ 221,076 2.5<br />

$ 111,107 $ 565,127 $ 288,783 $ 276,344 2.5<br />

$ 3,548 $ 26,360 $ 9,331 $ 17,029 4.8<br />

$ 20,571 $ 317,011 $ 53,987 $ 263,024 12.8<br />

$ 43,540 $ 121,465 $ 115,384 $ 24,293 0.6<br />

$ 66,664 $ 339,076 $ 173,270 $ 165,806 2.5<br />

$ 59,907 $ 263,726 $ 158,444 $ 105,282 1.8<br />

$ 51,848 $ 263,726 $ 134,761 $ 128,965 2.5<br />

$ 64,659 $ 161,132 $ 166,693 $ 32,226 0.5<br />

$ 125,633 $ 358,186 $ 323,388 $ 71,637 0.6<br />

$ 14,969 $ 9,013 $ 40,824 $ 1,803 0.1<br />

$ 205,550 $ 4,023,619 $ 545,095 $ 3,478,524 16.9<br />

$ 16,408 $ 495,153 $ 43,975 $ 451,178 27.5<br />

$ 1,009 $ 46,015 $ 2,789 $ 43,226 42.8<br />

$ 51,848 $ 263,726 $ 134,761 $ 128,965 2.5<br />

$ 81,480 $ 414,427 $ 211,778 $ 202,649 2.5<br />

$ 32,396 $ 49,351 $ 84,100 $ 9,870 0.3<br />

$ 10,057 $ 185,171 $ 27,553 $ 157,618 15.7<br />

$ 9,720 $ 45,550 $ 25,178 $ 20,372 2.1<br />

$ 51,848 $ 263,726 $ 134,761 $ 128,965 2.5<br />

$ 1,025 $ 7,599 $ 2,796 $ 4,803 4.7<br />

$ 18,674 $ 352,860 $ 50,928 $ 301,932 16.2<br />

$ 3,261 $ 156,646 $ 5,938 $ 150,708 46.2<br />

$ 55,187 $ 3,048,573 $ 133,376 $ 2,915,197 52.8<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

(0)<br />

-<br />

(0)<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

Demand<br />

Savings (kW)<br />

24.0<br />

1.0<br />

4.0<br />

1.0<br />

1.0<br />

-<br />

4.0<br />

5.0<br />

7.0<br />

10.0<br />

1.0<br />

-<br />

32.0<br />

-<br />

1.0<br />

3.0<br />

-<br />

12.0<br />

13.0<br />

16.0<br />

1.0<br />

9.0<br />

7.0<br />

10.0<br />

-<br />

7.0<br />

2.0<br />

15.0<br />

-<br />

154.0<br />

14.0<br />

(2.0)<br />

7.0<br />

12.0<br />

1.0<br />

11.0<br />

-<br />

7.0<br />

2.0<br />

72.0<br />

-<br />

21.0<br />

Total<br />

Purchased<br />

SEP<br />

Electricity<br />

Project Building<br />

Savings<br />

ID Key Building Name Project Name<br />

(kWh/yr)<br />

D1005 04C4315 GONDA CENTER CV Rebalance 328,672<br />

D1047 04C4317 LAW S-8 CAV to VAV 49,076<br />

D1046 04C4317 LAW S-5 & 6 CAV to VAV 220,903<br />

D1045 04C4317 LAW S-4 CAV to VAV 71,619<br />

D1044 04C4317 LAW SF 3 & 7 VIV to VAV & SP Reset 192,296<br />

D1043 04C4317 LAW SF 1 & 2 SP Reset 77,125<br />

D1021 04C4318A POWELL LIB AH 20 CAV to VAV 93,311<br />

D1020 04C4318A POWELL LIB AH 18, 38 & 39 CAV to VAV 25,070<br />

D1019 04C4318A POWELL LIB AH-19 CAV to VAV 141,194<br />

D1018 04C4318A POWELL LIB AH 1 to 4, 17 & 37 CAV to VAV with DCV 46,108<br />

D1017 04C4318A POWELL LIB S-1 CAV to VAV 21,971<br />

D3223 04C4319 FRANZ HALL Dual Duct Conversion to VAV (Cogent Report) 454,484<br />

D1010 04C4320 LIFE SCIENCE SF - 4 & 5 - Aircuity 933,010<br />

D1009 04C4320 LIFE SCIENCE Vivarium - CV Rebalance 76,582<br />

D1061 04C4325 DORIS STEIN AHU - 1, 2 & 3 VIV to VAV SP Reset 256,468<br />

D3234 04C4329 REED RESRCH Dual Duct Conversion to VAV (Cogent Report) 252,517<br />

D1042 04C4331 PUBLIC HLTH CV Rebalance - S-1 93,063<br />

D1041 04C4331 PUBLIC HLTH CAV to VAV - AHU S-2 to S-9 265,427<br />

D3228 04C4332B BRAIN RSCH Dual Duct Conversion to VAV (Cogent Report) 1,010,067<br />

D3233 04C4332D HEALTH SCI Dual Duct Conversion to VAV (Cogent Report) 1,262,583<br />

D1040 04C4332E M DAVIES CC AHU 1 CAV to VAV 40,321<br />

D1039 04C4333 JULES STEIN S2, 3 & 4Aircuity 233,762<br />

D1038 04C4333 JULES STEIN S-1, 5 & 6 CAV to VAV 494,776<br />

D3229 04C4334 DENTISTRY Dual Duct Conversion to VAV (Cogent Report) 757,550<br />

D3220 04C4335 SCHOENBERG Dual Duct Conversion to VAV (Cogent Report) 680,760<br />

D3230 04C4336 FACTOR Dual Duct Conversion to VAV (Cogent Report) 589,184<br />

D1053 04C4343 BOELTER HALL AH 4 to 7, 10 to 12 - SP Reset 734,759<br />

D1052 04C4343 BOELTER HALL S-1 to 11 except 9 - CAV to VAV 1,427,651<br />

D6008 04C4345 MED PLZA 300 CW Reset 170,100<br />

D1013 04C4348 MACDONALDLAB Lab CAV to VAV with Aircuity 2,335,790<br />

D1012 04C4348 MACDONALDLAB AHU 2 Vivarium Aircuity 186,450<br />

D1011 04C4348 MACDONALDLAB AHU 1 VIV to VAV & SP Reset 11,470<br />

D3232 04C4359 MATH SCIENCE Dual Duct Conversion to VAV (Cogent Report) 589,184<br />

D3231 04C4363 KNUDSEN HALL Dual Duct Conversion to VAV (Cogent Report) 925,914<br />

D1003 04C4374 FOWLER MUSM AHU 1 & 2 SP Reset 368,136<br />

D1023 04C4375 ROYCE HALL AC 3, 4, 6 to 8 - CAV to VAV 114,281<br />

D1022 04C4375 ROYCE HALL AC 1 & 2 - SP Reset 110,457<br />

D3227 04C4403 BOYER HALL Dual Duct Conversion to VAV (Cogent Report) 589,184<br />

D6011 04C4415 UNEX CT VFDs 11,650<br />

D6005 04C4415 UNEX Replace Chiller 212,201<br />

D6003 04C4415 UNEX Replace Boiler 37,053<br />

D1035 04C4415 UNEX AHU 1 to 8 T-1 & T-2 CAV to VAV 627,124<br />

SOUTHERN REGIONAL<br />

D6009 04C4562 LIBRARY FACILITY CW Reset 40,032<br />

SOUTHERN REGIONAL<br />

D6004 04C4562 LIBRARY FACILITY Replace Chiller 264,354<br />

SOUTHERN REGIONAL<br />

D1026 04C4562 LIBRARY FACILITY AHU 3 5 & SF-1 CAV to VAV with SP Reset 147,123<br />

SOUTHERN REGIONAL<br />

D1025 04C4562 LIBRARY FACILITY AHU 1, 2 & 4 SP Reset 554,493<br />

D3224 04C4577A MELNITZ HALL Dual Duct Conversion to VAV (Cogent Report) 106,630<br />

D3222 04C4578 MACGOWAN Dual Duct Conversion to VAV (Cogent Report) 333,970<br />

D3221 04C4579 PUBLIC AFFAIRS Dual Duct Conversion to VAV (Cogent Report) 350,601<br />

D6013 04C4580 BUNCHE HALL TOD EF 8,081<br />

D1060 04C4580 BUNCHE HALL Apply DDC controls, convert to VAV 1,861,221<br />

D3236 04C4581 WARREN HALL Dual Duct Conversion to VAV (Cogent Report) 420,882<br />

(0)<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

$ 3,523 $ 9,013 $ 9,608 $ 1,803 0.5<br />

-<br />

-<br />

$ 23,263 $ 387,408 $ 63,445 $ 323,963 13.9<br />

-<br />

80.0<br />

$ 12,947 $ 132,983 $ 33,019 $ 99,964 7.7<br />

-<br />

4.0<br />

$ 48,795 $ 72,370 $ 123,813 $ 14,474 0.3<br />

$ 9,383 $ 75,350 $ 25,457 $ 49,893 5.3<br />

$ 29,389 $ 301,401 $ 76,655 $ 224,746 7.6<br />

$ 30,853 $ 339,076 $ 81,744 $ 257,332 8.3<br />

$ 711 $ 2,253 $ 1,939 $ 451 0.6<br />

$ 163,787 $ 3,634,425 $ 428,856 $ 3,205,569 19.6<br />

$ 37,038 $ 188,376 $ 96,265 $ 92,111 2.5<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

5.0<br />

1.0<br />

-<br />

-<br />

-<br />

67.0<br />

5.0


Table 11.1: SEP Projects by Funding Source and Project Type (Continued)<br />

Gross<br />

Net<br />

Estimated<br />

Simple<br />

Total Cost Estimated Utility Net Project Payback<br />

Savings ($/yr) Project Cost ($) Incentive ($) Cost ($) (yrs)<br />

$ 145,134 $ 376,752 $ 384,615 $ 75,350 0.5<br />

$ 9,332 $ 40,897 $ 24,902 $ 15,995 1.7<br />

$ 20,947 $ 115,534 $ 55,772 $ 59,762 2.9<br />

$ 5,379 $ 10,407 $ 14,441 $ 2,081 0.4<br />

$ 12,432 $ 41,969 $ 33,071 $ 8,898 0.7<br />

$ 5,988 $ 9,013 $ 16,330 $ 1,803 0.3<br />

$ 11,197 $ 45,552 $ 29,767 $ 15,785 1.4<br />

$ 12,122 $ 47,642 $ 32,257 $ 15,385 1.3<br />

$ 12,720 $ 74,077 $ 33,874 $ 40,203 3.2<br />

$ 17,733 $ 115,587 $ 48,363 $ 67,224 3.8<br />

$ 3,004,396 $ 27,552,281 $ 7,904,780 $ 19,647,501 6.5<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

Demand<br />

Savings (kW)<br />

23.0<br />

-<br />

1.0<br />

2.0<br />

1.0<br />

-<br />

-<br />

1.0<br />

1.0<br />

34.0<br />

1,148.0<br />

$ 4,805 $ 44,187 $ 13,104 $ 31,083 6.5<br />

-<br />

8.0<br />

$ 34,936 $ 286,838 $ 95,281 $ 191,557 5.5<br />

Total<br />

Purchased<br />

SEP<br />

Electricity<br />

Project Building<br />

Savings<br />

ID Key Building Name Project Name<br />

(kWh/yr)<br />

D3226 04C4594 REHAB CENTER Dual Duct Conversion to VAV (Cogent Report) 1,649,252<br />

D1001 04C515A COLLINS CTR AHU - 1 VIV to VAV SP Reset 106,041<br />

D1014 04C515B GOLD HALL AHU - 2, 7, 9 VIV to VAV SP Reset 238,032<br />

D1037 04C515C ENTREP HALL VFD + DCV for a CAV system 61,127<br />

D1036 04C515C ENTREP HALL AHU - 3 VIV to VAV SP Reset 141,268<br />

D6007 04C515D CORNELL HALL CW Reset 68,040<br />

D1057 04C515D CORNELL HALL AHU - 4 VIV to VAV SP Reset 127,238<br />

D1058 04C515E ROSNFLD LIBR AHU - 6 VIV to VAV SP Reset 137,755<br />

D1059 04C515F MULLIN CMNS AHU - 5 & 10 VIV to VAV SP Reset 144,543<br />

D6012 04CWIDE CAMPUSWIDE Pump VFDs 201,511<br />

Subtotal, State Funded, HVAC Projects 34,140,869<br />

Lighting Projects<br />

Retrofit gym HID fixtures with Pulse Start Metal Halide lamps<br />

D3210 04C4204 PAULEY<br />

w/electronic ballasts 54,600<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3203 04C4235 WOODEN/PS4<br />

and install photocell control where appropriate 397,003<br />

-<br />

45.0<br />

$ 653 $ 3,708 $ 1,782 $ 1,926 2.9<br />

-<br />

2.0<br />

$ 1,405,998 $ 23,858,410 $ 3,834,540 $ 20,023,870 14.2<br />

-<br />

4,590.0<br />

$ 18,480 $ 233,962 $ 50,400 $ 183,562 9.9<br />

$ 1,464,872 $ 24,427,106 $ 3,995,107 $ 20,431,999 13.9<br />

-<br />

-<br />

-<br />

4,645.0<br />

Retrofit kitchen fixtures from F40T12 lamps with magnetic<br />

D3194 04C4261 FACULTY CTR<br />

ballasts to F32T8 (28-watt) lamps with RLO electronic ballasts 7,425<br />

Retrofit all F32T8 fixtures with 28W F32 T8 lamps and RLO<br />

D3219 04CWIDE CAMPUSWIDE<br />

ballasts, and install additional occupancy sensors 15,977,250<br />

Replace 600 additional stairwell light fixtures with bi-level fixtures<br />

D3192 04CWIDE CAMPUSWIDE with occupancy sensors in campus buildings 210,000<br />

Subtotal, State Funded, Lighting Projects 16,646,278<br />

Other Projects<br />

$ 13,771 $ 75,954 $ 37,557 $ 38,397 2.8<br />

-<br />

-<br />

Future Million-Gallon Pool at Sunset Canyon: Variable Speed<br />

Circulation Pumps 156,488<br />

Sunset Canyon Diving & Family Pools: Variable Speed<br />

Circulation Pumps 71,539<br />

D3216 04CWIDE CAMPUSWIDE<br />

$ 6,295 $ 25,331 $ 17,169 $ 8,162 1.3<br />

-<br />

-<br />

D3215 04CWIDE CAMPUSWIDE<br />

$ 11,674 $ 64,507 $ 31,837 $ 32,670 2.8<br />

$ 4,760 $ 17,033 $ 12,981 $ 4,052 0.9<br />

$ 6,927 $ 113,913 $ 12,614 $ 101,299 14.6<br />

$ 3,239 $ 21,205 $ 8,834 $ 12,371 3.8<br />

$ 12,320 $ 145,530 $ 33,600 $ 111,930 9.1<br />

$ 24,640 $ 291,060 $ 67,200 $ 223,860 9.1<br />

$ 24,640 $ 291,060 $ 67,200 $ 223,860 9.1<br />

$ 24,640 $ 291,060 $ 67,200 $ 223,860 9.1<br />

$ 24,640 $ 291,060 $ 67,200 $ 223,860 9.1<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

18.0<br />

35.0<br />

35.0<br />

35.0<br />

35.0<br />

$ 4,177 $ 27,990 $ 11,391 $ 16,599 4.0<br />

-<br />

6.0<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

-<br />

27.0<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

D3214 04CWIDE CAMPUSWIDE Sunset Canyon Park Pool: Variable Speed Circulation Pumps 132,655<br />

D3213 04CWIDE CAMPUSWIDE North Pool: Variable Speed Circulation Pumps 54,089<br />

D3212 04CWIDE CAMPUSWIDE SAC Pool: Solar Pool Water Heater 78,711<br />

D3211 04CWIDE CAMPUSWIDE SAC Pool: Variable Speed Circulation Pumps 36,809<br />

D3122 04CWIDE CAMPUSWIDE Server Virtualization Phase 5 of 5: 5 VM Installations 140,000<br />

D3121 04CWIDE CAMPUSWIDE Server Virtualization Phase 4 of 5: 10 VM Installations 280,000<br />

D3120 04CWIDE CAMPUSWIDE Server Virtualization Phase 3 of 5: 10 VM Installations 280,000<br />

D3119 04CWIDE CAMPUSWIDE Server Virtualization Phase 2 of 5: 10 VM Installations 280,000<br />

D3118 04CWIDE CAMPUSWIDE Server Virtualization Phase 1 of 5: 10 VM Installations 280,000<br />

LCD Phase 9 of 9: 222 Verdiem (PC Power Management)<br />

D3117 04CWIDE CAMPUSWIDE<br />

Installations and 9 CRT Replacements 47,463<br />

LCD Phase 8 of 9: 1000 Verdiem (PC Power Management)<br />

D3116 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

LCD Phase 7 of 9: 1000 Verdiem (PC Power Management)<br />

D3115 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

LCD Phase 6 of 9: 1000 Verdiem (PC Power Management)<br />

D3114 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

LCD Phase 5 of 9: 1000 Verdiem (PC Power Management)<br />

D3113 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

LCD Phase 4 of 9: 1000 Verdiem (PC Power Management)<br />

D3112 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

LCD Phase 3 of 9: 1000 Verdiem (PC Power Management)<br />

D3111 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

LCD Phase 2 of 9: 1000 Verdiem (PC Power Management)<br />

D3110 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

-<br />

27.0<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

-<br />

27.0<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

-<br />

27.0<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

-<br />

27.0<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

-<br />

27.0<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

-<br />

27.0


Table 11.1: SEP Projects by Funding Source and Project Type (Continued)<br />

Net<br />

Simple<br />

Payback<br />

(yrs)<br />

Net Project<br />

Cost ($)<br />

Gross<br />

Estimated<br />

Utility<br />

Incentive ($)<br />

Estimated<br />

Project Cost ($)<br />

Total Cost<br />

Savings ($/yr)<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

Demand<br />

Savings (kW)<br />

$ 18,814 $ 68,191 $ 51,311 $ 16,880 0.9<br />

-<br />

27.0<br />

$ 13,619 $ 66,753 $ 37,144 $ 29,609 2.2<br />

-<br />

18.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

Total<br />

Purchased<br />

SEP<br />

Electricity<br />

Project Building<br />

Savings<br />

ID Key Building Name Project Name<br />

(kWh/yr)<br />

LCD Phase 1 of 9: 1000 Verdiem (PC Power Management)<br />

D3109 04CWIDE CAMPUSWIDE<br />

Installations and 40 CRT Replacements 213,796<br />

Refrigerators Phase 7 of 7: 69 <strong>Energy</strong> Star Refrigerator<br />

D3108 04CWIDE CAMPUSWIDE<br />

Replacements 154,767<br />

Refrigerators Phase 6 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

D3107 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 5 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

D3106 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 4 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

D3105 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 3 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

D3104 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 2 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

D3103 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 1 of 7: 100 <strong>Energy</strong> Star Refrigerator<br />

D3102 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 5 of 5: 73 <strong>Energy</strong> Star Refrigerator<br />

D3101 04CWIDE CAMPUSWIDE<br />

Replacements 163,739<br />

Refrigerators Phase 4 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

D3100 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 3 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

D3099 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 2 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

D3098 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

Refrigerators Phase 1 of 5: 100 <strong>Energy</strong> Star Refrigerator<br />

D3097 04CWIDE CAMPUSWIDE<br />

Replacements 224,300<br />

D3096 04CWIDE CAMPUSWIDE Lab Freezers Phase 4 of 4: 6 Lab Freezer Replacements 23,184<br />

D3095 04CWIDE CAMPUSWIDE Lab Freezers Phase 3 of 4: 20 Lab Freezer Replacements 77,280<br />

D3094 04CWIDE CAMPUSWIDE Lab Freezers Phase 2 of 4: 20 Lab Freezer Replacements 77,280<br />

D3093 04CWIDE CAMPUSWIDE Lab Freezers Phase 1 of 4: 20 Lab Freezer Replacements 77,280<br />

Subtotal, State Funded, Other Projects 6,364,652<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 14,409 $ 70,622 $ 39,297 $ 31,325 2.2<br />

-<br />

19.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

-<br />

26.0<br />

$ 19,738 $ 96,743 $ 53,832 $ 42,911 2.2<br />

$ 2,040 $ 116,424 $ 5,564 $ 110,860 54.3<br />

$ 6,801 $ 388,080 $ 18,547 $ 369,533 54.3<br />

$ 6,801 $ 388,080 $ 18,547 $ 369,533 54.3<br />

$ 6,801 $ 388,080 $ 18,547 $ 369,533 54.3<br />

$ 560,089 $ 4,586,700 $ 1,521,237 $ 3,065,463 5.5<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

26.0<br />

3.0<br />

9.0<br />

9.0<br />

9.0<br />

707.0<br />

$ 15,600 $ 346,500 $ 28,409 $ 318,091 20.4<br />

-<br />

-<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

-<br />

52.0<br />

Savings by Design (SBD) - Deferred Maintenance & Capital Renewal Projects<br />

D3075 04CWIDE CAMPUSWIDE Natural Gas Component of DM and CR Projects 2014 177,272<br />

Second Electric Savings Component of DM and CR Projects<br />

D3074 04CWIDE CAMPUSWIDE<br />

2014 454,550<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

$ 15,600 $ 346,500 $ 28,409 $ 318,091 20.4<br />

-<br />

-<br />

52.0<br />

-<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

-<br />

52.0<br />

D3073 04CWIDE CAMPUSWIDE First Electric Savings Component of DM and CR Projects 2014 454,550<br />

D3072 04CWIDE CAMPUSWIDE Natural Gas Component of DM and CR Projects 2013 177,272<br />

Second Electric Savings Component of DM and CR Projects<br />

D3071 04CWIDE CAMPUSWIDE<br />

2013 454,550<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

$ 15,600 $ 346,500 $ 28,409 $ 318,091 20.4<br />

-<br />

-<br />

52.0<br />

-<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

-<br />

52.0<br />

D3070 04CWIDE CAMPUSWIDE First Electric Savings Component of DM and CR Projects 2013 454,550<br />

D3069 04CWIDE CAMPUSWIDE Natural Gas Component of DM and CR Projects 2012 177,272<br />

Second Electric Savings Component of DM and CR Projects<br />

D3068 04CWIDE CAMPUSWIDE<br />

2012 454,550<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

$ 15,600 $ 346,500 $ 28,409 $ 318,091 20.4<br />

-<br />

-<br />

52.0<br />

-<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

-<br />

52.0<br />

D3067 04CWIDE CAMPUSWIDE First Electric Savings Component of DM and CR Projects 2012 454,550<br />

D3066 04CWIDE CAMPUSWIDE Natural Gas Component of DM and CR Projects 2011 177,272<br />

Second Electric Savings Component of DM and CR Projects<br />

D3065 04CWIDE CAMPUSWIDE<br />

2011 454,550<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

$ 15,600 $ 346,500 $ 28,409 $ 318,091 20.4<br />

-<br />

-<br />

52.0<br />

-<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

-<br />

52.0<br />

D3064 04CWIDE CAMPUSWIDE First Electric Savings Component of DM and CR Projects 2011 454,550<br />

D3063 04CWIDE CAMPUSWIDE Natural Gas Component of DM and CR Projects 2010 177,272<br />

Second Electric Savings Component of DM and CR Projects<br />

D3062 04CWIDE CAMPUSWIDE<br />

2010 454,550


Table 11.1: SEP Projects by Funding Source and Project Type (Continued)<br />

Net<br />

Simple<br />

Payback<br />

(yrs)<br />

Net Project<br />

Cost ($)<br />

Gross<br />

Estimated<br />

Utility<br />

Incentive ($)<br />

Estimated<br />

Project Cost ($)<br />

Total Cost<br />

Savings ($/yr)<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

Demand<br />

Savings (kW)<br />

Total<br />

Purchased<br />

Electricity<br />

Savings<br />

(kWh/yr)<br />

Building<br />

Key Building Name Project Name<br />

SEP<br />

Project<br />

ID<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

$ 15,600 $ 346,500 $ 28,409 $ 318,091 20.4<br />

-<br />

-<br />

52.0<br />

-<br />

$ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

-<br />

52.0<br />

D3061 04CWIDE CAMPUSWIDE First Electric Savings Component of DM and CR Projects 2010 454,550<br />

D3060 04CWIDE CAMPUSWIDE Natural Gas Component of DM and CR Projects 2009 177,272<br />

Second Electric Savings Component of DM and CR Projects<br />

D3059 04CWIDE CAMPUSWIDE<br />

2009 454,550<br />

D3058 04CWIDE CAMPUSWIDE First Electric Savings Component of DM and CR Projects 2009 454,550<br />

52.0<br />

- $ 40,000 $ 693,000 $ 109,092 $ 583,908 14.6<br />

Subtotal, State Funded, (SBD) - Deferred Maintenance & Capital Renewal Projects 6,518,233 624.0<br />

- $ 573,605 $ 10,395,000 $ 1,479,558 $ 8,915,442 15.5<br />

Subtotal, State Funded Projects 89,108,065 8,885.0 - $ 7,841,510 $ 83,561,782 $ 20,210,063 $ 63,351,719 8.1<br />

$ 14,078 $ 97,379 $ 33,276 $ 64,103 4.6<br />

$ 6,074 $ 34,700 $ 11,858 $ 22,842 3.8<br />

$ 65,310 $ 373,119 $ 127,499 $ 245,620 3.8<br />

$ 68,130 $ 389,234 $ 133,006 $ 256,228 3.8<br />

$ 11,625 $ 78,750 $ 24,000 $ 54,750 4.7<br />

$ 3,336 $ 20,587 $ 6,210 $ 14,377 4.3<br />

$ 168,553 $ 993,770 $ 335,849 $ 657,921 3.9<br />

-<br />

4,583<br />

49,274<br />

51,401<br />

7,500<br />

2,813<br />

115,570<br />

11.0<br />

4.0<br />

42.0<br />

44.0<br />

9.0<br />

2.0<br />

112.0<br />

Med <strong>Center</strong> Funded Buildings<br />

MBCx Projects<br />

D3501 04C4006 MED PLZA 100 Monitoring Based Commissioning 159,980<br />

D3503 04C510B SMH EMERGCY Monitoring Based Commissioning 34,132<br />

D3505 04C510D SMH PAVILION Monitoring Based Commissioning 367,002<br />

D3507 04C510F SMH WST TOWR Monitoring Based Commissioning 382,854<br />

D3510 04C510H SMH CENT PLT MBCx Central <strong>Plan</strong>t 75,000<br />

D3509 04C510H SMH CENT PLT Monitoring Based Commissioning 16,499<br />

Subtotal, Med <strong>Center</strong> Funded, MBCx Projects 1,035,467<br />

New Construction<br />

D3001 04C4006 MED PLZA 100 100 SBD, New/Renov New/Renov - Outpatient Wing Wing Seismic Renovation Renovation 615,049<br />

44.0<br />

- $ 54,124 $ 645,613 $ 129,516 $ 516,097 9.5<br />

SBD, New/Renov - Santa Monica/Orthopaedic Replacement<br />

D3044 04C510F SMH WST TOWR<br />

Hospital and Parking Structure 2,748,782 314.0 163,728 $ 351,590 $ 3,637,434 $ 790,690 $ 2,846,744 8.1<br />

$ 3,929 $ 46,867 $ 9,401 $ 37,466 9.5<br />

-<br />

3.0<br />

D3088 04CWIDEM CAMPUSWIDE - MED CTR SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 46,867 $ 9,401 $ 37,466 9.5<br />

-<br />

3.0<br />

D3087 04CWIDEM CAMPUSWIDE - MED CTR SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 46,867 $ 9,401 $ 37,466 9.5<br />

-<br />

3.0<br />

D3086 04CWIDEM CAMPUSWIDE - MED CTR SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

D3085 04CWIDEM CAMPUSWIDE - MED CTR SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

3.0<br />

- $ 3,929 $ 46,867 $ 9,401 $ 37,466 9.5<br />

Subtotal, Med <strong>Center</strong> Funded, New Construction 3,542,413 370.0 163,728 $ 421,430 $ 4,470,516 $ 957,810 $ 3,512,706 8.3<br />

Subtotal, Med <strong>Center</strong> Funded Projects 4,577,880 482.0 279,298 $ 589,983 $ 5,464,286 $ 1,293,659 $ 4,170,627 7.1<br />

$ 7,177 $ 48,381 $ 16,584 $ 31,797 4.4<br />

$ 13,472 $ 90,818 $ 31,130 $ 59,688 4.4<br />

$ 18,069 $ 121,803 $ 41,751 $ 80,052 4.4<br />

$ 8,882 $ 59,875 $ 20,523 $ 39,352 4.4<br />

$ 12,410 $ 83,659 $ 28,676 $ 54,983 4.4<br />

$ 60,010 $ 404,536 $ 138,664 $ 265,872 4.4<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

5.0<br />

9.0<br />

13.0<br />

6.0<br />

9.0<br />

42.0<br />

Housing Funded<br />

MBCx<br />

D3015 04C4265 TIVERTON HSE Monitoring Based Commissioning 81,558<br />

D3019 04C4302A CANYON POINT Monitoring Based Commissioning 153,094<br />

D3020 04C4302D COVEL COMMON Monitoring Based Commissioning 205,324<br />

D3021 04C4310 KERCKHOFF Monitoring Based Commissioning 100,932<br />

D3036 04C4352 SYCAMORE CT Monitoring Based Commissioning 141,026<br />

Subtotal, Housing, MBCx 681,934<br />

$ 6,398 $ 67,157 $ 15,310 $ 51,847 8.1<br />

$ 171,648 $ 1,750,813 $ 432,481 $ 1,318,332 7.7<br />

$ 68,403 $ 718,016 $ 163,684 $ 554,332 8.1<br />

$ 63,886 $ 670,602 $ 152,875 $ 517,727 8.1<br />

$ 19,296 $ 202,549 $ 46,174 $ 156,375 8.1<br />

-<br />

-<br />

-<br />

-<br />

-<br />

5.0<br />

172.0<br />

56.0<br />

52.0<br />

16.0<br />

$ 12,190 $ 127,950 $ 29,169 $ 98,781 8.1<br />

-<br />

10.0<br />

$ 294,648 $ 3,092,901 $ 705,077 $ 2,387,824 8.1<br />

$ 636,469 $ 6,629,988 $ 1,544,770 $ 5,085,218 8.0<br />

-<br />

-<br />

241.0<br />

552.0<br />

New Construction<br />

D3002 04C4201 ARWHD LODGE SBD, New/Renov - Lake Arrowhead Facility Improvements 72,707<br />

D3012 04C4246 DYKSTRA HALL SBD, New/Renov - Dykstra Repairs and Refurbishment 1,950,545<br />

D3017 04C4298 RIEBER HALL SBD, New/Renov - Rieber Repairs and Refurbishment 777,303<br />

D3018 04C4299 HEDRICK HALL SBD, New/Renov - Hedrick Repairs and Refurbishment 725,977<br />

D3053 04CTBD3 HILGARD GRAD STUD SBD, New/Renov - Hilgard Graduate Student Housing 219,273<br />

SOUTHWEST CAMPUS SBD, New/Renov - Southwest <strong>Campus</strong> Housing Commons<br />

D3054 04CTBD4 HOUSING COMMONS<br />

Building 138,519<br />

NORTHWEST CAMPUS<br />

D3057 04CTBD7 STUDENT HOUSING BUILDING SBD, New/Renov - Northwest <strong>Campus</strong> Student Housing Unit 3,348,278<br />

Subtotal, Housing, New Construction 7,232,601


Table 11.1: SEP Projects by Funding Source and Project Type (Continued)<br />

Net<br />

Simple<br />

Payback<br />

(yrs)<br />

Net Project<br />

Cost ($)<br />

Gross<br />

Estimated<br />

Utility<br />

Incentive ($)<br />

Estimated<br />

Project Cost ($)<br />

Total Cost<br />

Savings ($/yr)<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

Demand<br />

Savings (kW)<br />

Total<br />

Purchased<br />

Electricity<br />

Savings<br />

(kWh/yr)<br />

Building<br />

Key Building Name Project Name<br />

SEP<br />

Project<br />

ID<br />

$ 2,170 $ 10,928 $ 5,919 $ 5,009 2.3<br />

$ 1,370 $ 78,323 $ 2,494 $ 75,829 55.4<br />

$ 2,738 $ 156,646 $ 4,987 $ 151,659 55.4<br />

$ 34,268 $ 105,987 $ 85,306 $ 21,197 0.6<br />

$ 4,585 $ 28,262 $ 12,180 $ 16,082 3.5<br />

$ 6,409 $ 2,784 $ 16,712 $ 557 0.1<br />

$ 51,541 $ 382,929 $ 127,598 $ 255,331 5.0<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

-<br />

4.0<br />

-<br />

-<br />

2.0<br />

1.0<br />

-<br />

7.0<br />

HVAC Projects<br />

D6010 04C4265 TIVERTON HSE CT VFDs 24,661<br />

D6001 04C4302A CANYON POINT Replace Boiler 15,563<br />

D6002 04C4302D COVEL COMMON Replace Boiler 31,119<br />

D1006 04C4302D COVEL COMMON DAC 1 to 4 & DAHU-1 - VIV to VAV SP Reset 389,410<br />

D1008 04C4310 KERCKHOFF CAV to VAV - AHU 2 52,107<br />

D1007 04C4310 KERCKHOFF AHU 1 SP Reset 72,829<br />

Subtotal, Housing, HVAC Projects 585,688<br />

Lighting Projects<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3198 04C4302C COURTSIDE/PK<br />

and install photocell control where appropriate 175,042<br />

20.0<br />

- $ 15,404 $ 126,470 $ 42,010 $ 84,460 5.5<br />

Subtotal, Housing, Lighting Projects 175,042<br />

20.0<br />

- $ 15,404 $ 126,470 $ 42,010 $ 84,460 5.5<br />

Subtotal, Housing Funded Projects 8,675,264 621.0 - $ 763,423 $ 7,543,922 $ 1,853,042 $ 5,690,880 7.5<br />

$ 39,533 $ 266,496 $ 91,347 $ 175,149 4.4<br />

$ 14,220 $ 95,861 $ 32,858 $ 63,003 4.4<br />

$ 53,753 $ 362,357 $ 124,205 $ 238,152 4.4<br />

-<br />

-<br />

-<br />

28.0<br />

10.0<br />

38.0<br />

Other Fund Source<br />

MBCx<br />

D3016 04C4270 WILSHIRE CTR Monitoring Based Commissioning 449,235<br />

D3037 04C4360 SAC Monitoring Based Commissioning 161,592<br />

Subtotal, Other Fund Source MBCx Proejcts 610,827<br />

$ 18,372 $ 187,394 $ 46,289 $ 141,105 7.7<br />

$ 12,538 $ 131,608 $ 30,002 $ 101,606 8.1<br />

-<br />

-<br />

18.0<br />

10.0<br />

New Construction<br />

SBD, New/Renov - CHS Parking E General Clinical Research<br />

D3007 04C4211 PARKG ST CHS<br />

<strong>Center</strong>/Biomarker Seismic Renovation 208,768<br />

D3052 04CTBD2 SOUTH CAMPUS STUDENT SBD, New/Renov - South <strong>Campus</strong> Student <strong>Center</strong> 142,476<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3092 04CWIDEO CAMPUSWIDE - OTHER SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3091 04CWIDEO CAMPUSWIDE - OTHER SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

-<br />

3.0<br />

D3090 04CWIDEO CAMPUSWIDE - OTHER SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

$ 3,929 $ 41,243 $ 9,401 $ 31,842 8.1<br />

$ 46,625 $ 483,975 $ 113,895 $ 370,080 7.9<br />

-<br />

-<br />

3.0<br />

40.0<br />

D3089 04CWIDEO CAMPUSWIDE - OTHER SBD, New/Renov - <strong>Campus</strong> Approved Projects Under $5 Million 44,646<br />

Subtotal, Other Fund Source New Construction 529,826<br />

$ 26,814 $ 847,454 $ 73,130 $ 774,324 28.9<br />

$ 64,796 $ 1,729,872 $ 176,717 $ 1,553,155 24.0<br />

$ 23,784 $ 16,705 $ 62,162 $ 3,341 0.1<br />

$ 6,769 $ 22,142 $ 17,524 $ 4,618 0.7<br />

$ 122,162 $ 2,616,173 $ 329,533 $ 2,286,640 18.7<br />

-<br />

-<br />

-<br />

-<br />

-<br />

98.0<br />

171.0<br />

1.0<br />

-<br />

270.0<br />

HVAC Projects<br />

D6006 04C4270 WILSHIRE CTR Replace Chiller 304,707<br />

D1027 04C4270 WILSHIRE CTR AHU 1 & 2 SP Reset 736,319<br />

D1024 04C4360 SAC AHU1 to 6 SP Reset 270,268<br />

D1004 04C4360 SAC AHU 4 SP Reset 76,916<br />

Subtotal, Other Fund Source HVAC 1,388,209<br />

Lighting Projects<br />

$ 21,756 $ 178,622 $ 59,334 $ 119,288 5.5<br />

-<br />

28.0<br />

Replace high pressure sodium fixtures with induction fixtures<br />

and install photocell control where appropriate 247,225<br />

Replace high pressure sodium fixtures with induction fixtures<br />

and install photocell control where appropriate 382,567<br />

Replace high pressure sodium fixtures with induction fixtures<br />

and install photocell control where appropriate 642,423<br />

Replace high pressure sodium fixtures with induction fixtures<br />

and install photocell control where appropriate 468,283<br />

Replace high pressure sodium fixtures with induction fixtures<br />

and install photocell control where appropriate 195,795<br />

Replace high pressure sodium fixtures with induction fixtures<br />

and install photocell control where appropriate 165,117<br />

D3202 04C4207 PARKG STR 3<br />

$ 33,666 $ 276,408 $ 91,816 $ 184,592 5.5<br />

-<br />

44.0<br />

D3208 04C4208 PARKG STR 9<br />

$ 56,533 $ 464,156 $ 154,182 $ 309,974 5.5<br />

-<br />

73.0<br />

D3207 04C4209 PARKG STR 8<br />

$ 41,209 $ 338,339 $ 112,388 $ 225,951 5.5<br />

-<br />

53.0<br />

D3201 04C4210 PARKG STR 2<br />

$ 17,230 $ 141,463 $ 46,991 $ 94,472 5.5<br />

-<br />

22.0<br />

D3195 04C4211 PARKG ST CHS<br />

$ 14,530 $ 119,299 $ 39,628 $ 79,671 5.5<br />

-<br />

19.0<br />

D3205 04C4219 PARKG STR 6


Table 11.1: SEP Projects by Funding Source and Project Type (Continued)<br />

Net<br />

Simple<br />

Payback<br />

(yrs)<br />

Net Project<br />

Cost ($)<br />

Gross<br />

Estimated<br />

Utility<br />

Incentive ($)<br />

Estimated<br />

Project Cost ($)<br />

Total Cost<br />

Savings ($/yr)<br />

Total<br />

Purchased<br />

Gas Savings<br />

(th/yr)<br />

Demand<br />

Savings (kW)<br />

$ 13,578 $ 111,476 $ 37,030 $ 74,446 5.5<br />

-<br />

18.0<br />

$ 2,303 $ 18,905 $ 6,280 $ 12,625 5.5<br />

-<br />

3.0<br />

$ 32,554 $ 267,281 $ 88,784 $ 178,497 5.5<br />

-<br />

42.0<br />

$ 3,414 $ 31,854 $ 9,312 $ 22,542 6.6<br />

-<br />

4.0<br />

$ 55,660 $ 456,985 $ 151,800 $ 305,185 5.5<br />

-<br />

72.0<br />

Total<br />

Purchased<br />

SEP<br />

Electricity<br />

Project Building<br />

Savings<br />

ID Key Building Name Project Name<br />

(kWh/yr)<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3199 04C4263 PARKG STR 32<br />

and install photocell control where appropriate 154,290<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3197 04C4301 PARKG STR RC<br />

and install photocell control where appropriate 26,166<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3206 04C4322 PARKG STR 7<br />

and install photocell control where appropriate 369,935<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3209 04C4332H PARKG STR E<br />

and install photocell control where appropriate 38,798<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3200 04C4342 PARKG STR 1<br />

and install photocell control where appropriate 632,498<br />

Replace gym HID and strength & conditioning fixtures with new<br />

D3218 04C4360 SAC<br />

fluorescent fixtures highbays (sensors in gyms only) 229,211<br />

Replace existing GYM HID fixtures with new fluorescent fixtures<br />

D3217 04C4360 SAC<br />

highbays w/sensors 113,896<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3196 04C4490 PARKG STR DD<br />

and install photocell control where appropriate 44,212<br />

Retrofit existing 175-watt suspended metal halide fixtures with<br />

ceramic metal halide and replace quartz floods with fluorescent<br />

D3193 04C4582 ACKERMAN<br />

T5HO wall washes 222,825<br />

Replace high pressure sodium fixtures with induction fixtures<br />

D3204 04C4587 PARKG STR 5<br />

and install photocell control where appropriate 115,041<br />

Subtotal, Other Fund Source Lighting 4,048,282<br />

Subtotal, Other Fund Source Projects 6,577,145<br />

<strong>UC</strong> <strong>Los</strong> <strong>Angeles</strong> Total 108,938,355<br />

$ 20,171 $ 83,199 $ 55,011 $ 28,188 1.4<br />

-<br />

30.0<br />

$ 10,023 $ 38,731 $ 27,335 $ 11,396 1.1<br />

-<br />

13.0<br />

$ 3,891 $ 31,943 $ 10,611 $ 21,332 5.5<br />

-<br />

5.0<br />

$ 19,609 $ 174,962 $ 53,478 $ 121,484 6.2<br />

-<br />

42.0<br />

$ 10,124 $ 83,444 $ 27,610 $ 55,834 5.5<br />

$ 356,249 $ 2,817,067 $ 971,590 $ 1,845,477 5.2<br />

$ 578,789 $ 6,279,572 $ 1,539,223 $ 4,740,349 8.2<br />

$ 9,773,705 $ 102,849,562 $ 24,895,987 $ 77,953,575 8.0<br />

-<br />

-<br />

-<br />

279,298<br />

13.0<br />

481.0<br />

829.0<br />

10,817.0


12. ENERGY & GHG FORECAST<br />

The University of California 2007 Policy of Sustainable Practices sets the goal of reducing<br />

greenhouse gas emissions to 2000 levels by 2014 and to 1990 levels by 2020. Each campus<br />

will need to develop complete greenhouse gas emissions calculations for the baseline years of<br />

1990 and 2000. In order to determine the potential impact of energy efficiency and renewable<br />

energy projects identified in the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong>, current, past, and future greenhouse gas<br />

emissions from purchased electricity and natural gas have been estimated based on<br />

information provided on energy purchases for fiscal years 1999-2000 and 2006-2007.<br />

Greenhouse gas emissions savings for the projects identified have also been calculated in order<br />

to compare their impact with the greenhouse gas emissions reduction goals. While these<br />

emissions calculations do not include all sources of campus greenhouse gas emissions, they do<br />

provide a way of measuring the impact of the projects identified in the SEP in relation to<br />

electricity and natural gas usage.<br />

12.1 Electricity Emissions Factors<br />

Although some California utilities publish greenhouse gas emissions factors for their delivered<br />

power, a complete record of historical and current factors is not available. Therefore, in<br />

accordance with the California Climate Action Registry (CCAR) General Reporting Protocol,<br />

EPA’s eGRID emissions factor for the CALI – WECC California subregion for 2000 of 0.000366<br />

metric tons of CO2e/kWh was used to calculate greenhouse gas emissions from purchased<br />

electricity. This number includes greenhouse gas emissions of carbon dioxide, methane, and<br />

nitrous oxide and uses global warming potential factors published in the IPCC’s Third<br />

Assessment Report to convert methane and nitrous oxide emissions to carbon dioxide<br />

equivalents. The emissions factor is reported in metric tons of carbon dioxide equivalent per<br />

kWh (CO2e/kWh) of electricity purchased. While the emissions factor does normally vary by<br />

year based on the actual fuel mix used, a constant value was used to isolate the impacts of<br />

energy efficiency and renewable energy projects. Each campus may choose to develop utility<br />

and year specific emissions factors when filing their greenhouse gas emissions with the<br />

California Climate Action Registry.<br />

12.2 Gas Emissions Factors<br />

The emission factors provided in the California Climate Action Registry General Reporting<br />

Protocol, Tables C.5 and C.6 were used to calculate the greenhouse gas emissions associated<br />

with natural gas purchases. This number is 0.005295 metric tons of CO2e per therm.<br />

12.3 Current <strong>Energy</strong> Usage and Emissions<br />

Current emissions from purchased utilities are shown in Table 1.1<br />

12.4 2014 Goals<br />

The University of California has set the goal of meeting 2000 greenhouse gas emission by<br />

2014. In 2000 many campuses were purchasing their energy from Enron which relied on a<br />

different power mix than the state-wide average. This information is not accurately reflected in<br />

the average state-wide emissions factor and therefore actual greenhouse gas emissions for<br />

campuses purchasing Enron power will be much higher than calculated. In addition to the<br />

campus wide greenhouse gas emissions goal, the campus also needs to meet the goal of<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 12-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


educing growth adjusted electricity consumption to 10% below 2000 levels by 2014. The<br />

energy consumption and greenhouse gas emissions associated with the 2014 goals are shown<br />

in Table 1.1. The emissions are based on the statewide average emissions factor.<br />

12.5 2020 Goals<br />

While the goal of achieving a reduction of greenhouse gas emissions to 1990 levels by 2020<br />

has been set, the lack of data on energy consumption and emission factors in 1990 has made it<br />

infeasible to determine an accurate baseline.<br />

12.6 SEP <strong>Energy</strong> Efficiency and Renewable <strong>Energy</strong> Projects<br />

The <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> has identified energy efficiency and renewable energy projects to<br />

help meet the greenhouse gas emissions targets of each campus. The impact of these<br />

proposed projects on greenhouse gas emissions is shown in Table 1.1. If the campus chooses<br />

to install the photovoltaic systems proposed in the SEP, they will need to retain ownership of the<br />

renewable energy credits (RECs) associated with the production of electricity from the PV<br />

panels in order to claim credit for the greenhouse gas emissions reductions from the system.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 12-2 December 31, 2008<br />

Newcomb | Anderson | McCormick


13. CONCLUSIONS<br />

13.1 Next Steps and Recommendations<br />

13.1.1 Action <strong>Plan</strong><br />

The <strong>UC</strong> <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong> was driven by the <strong>UC</strong>’s Policy on Sustainable Practices, Section<br />

II d., which stipulates that the system (1) reduce systemwide growth-adjusted energy<br />

consumption by 10 percent or more by 2014 from the year 2000 base consumption level, and<br />

(2) reduce GHG emissions to 2000 levels by 2014.<br />

To accomplish these goals, the campus must create a strategic action plan for implementing<br />

energy-saving projects through the year 2014. The plan should address both State and Nonstate<br />

funded facilities. The SEP project list should be used as a starting point to guide these<br />

action plans, but the University should continuously evaluate the feasibility of additional energysaving<br />

measures. Every campus has begun to develop an action plan through 2011. For each<br />

year in the six year program, the University should re-evaluate and modify the action plan to<br />

reflect actual progress towards goals and necessary future steps.<br />

13.1.2 College Performance: Measurement and Reporting<br />

To ensure meeting the goals and requirements of the <strong>UC</strong> Policy on Sustainable Practices, the<br />

campus must measure, evaluate, and report energy use and greenhouse gas emissions<br />

regularly.<br />

A Climate Change Working Group at each campus is currently developing a protocol to allow for<br />

growth adjustment and normalization of data and accurate reporting procedures. These<br />

Working Groups will monitor progress toward reaching the stated goals for GHG reduction, and<br />

will evaluate suggestions for programs to reach these goals.<br />

13.2 Funding Sources<br />

Significant financial investment will be required to accomplish the <strong>UC</strong> Policy on Sustainable<br />

Practices goals. A variety of financing programs and funding sources are available to the<br />

Universities. Two major funding sources designed specifically to support energy efficiency<br />

projects are the Utility Incentive Programs and the <strong>UC</strong>OP’s <strong>Energy</strong> Efficiency Financing<br />

program.<br />

13.2.1 Utility Incentive Programs<br />

Most Utilities in California offer incentives to customers to support the implementation of energysaving<br />

projects.<br />

The University of California/California State University/Investor-Owned Utility (<strong>UC</strong>/CSU/IOU)<br />

<strong>Energy</strong> Efficiency Partnership Program provides funding to all campuses served by San Diego<br />

Gas and Electric (SDG&E), Southern California Gas (SCG), Southern California Edison (SCE),<br />

Pacific Gas and Electric (PG&E). Through the Partnership, these IOUs distribute incentives<br />

from Public Purpose Programs (formerly Publics Good Charges) that customers pay on their<br />

utility bills. Since 2004, the IOUs have paid <strong>UC</strong> almost $20 million in incentives through this<br />

Partnership, and the IOUs have offered to increase <strong>UC</strong> funding in future years. As a preliminary<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 13-1 December 31, 2008<br />

Newcomb | Anderson | McCormick


step within the <strong>Strategic</strong> <strong>Energy</strong> <strong>Plan</strong>, commitments were made to the IOUs to coincide with<br />

CP<strong>UC</strong> filing deadlines and it is anticipated that funding levels will be granted for the<br />

commitment. Current <strong>UC</strong>/CSU/IOU Partnership incentive rates are $0.24 per kilowatt-hour<br />

saved in the first year and $1.00 per therm saved in the first year, and the Partnership will pay<br />

up to 80% of the project cost. This incentive structure is anticipated to remain unchanged in the<br />

future program years.<br />

Publicly-Owned Utilities, such as <strong>Los</strong> <strong>Angeles</strong> Department of Public Works (LADWP),<br />

Sacramento Municipal Utility District (SMUD), Riverside Public Utilities (RPU) also manage<br />

energy efficiency incentive programs that have historically paid substantial incentives to<br />

Universities in their territories. There have been discussions with each of these utilities to<br />

negotiate similar incentive rates, and LADWP has agreed to match the $0.24/kWh incentive rate<br />

for project completed by <strong>UC</strong>LA.<br />

13.2.2 <strong>UC</strong>OP <strong>Energy</strong> Efficiency Financing<br />

<strong>UC</strong>OP has designed a program to work in concert with the Utility incentive programs to provide<br />

low-interest loan to cover the cost to the campuses after the incentives. <strong>Campus</strong>es will pay<br />

back the loans to <strong>UC</strong>OP using the energy cost savings. To do so will require Department of<br />

Finance approval to allow for capital debt service to be paid with energy cost savings. In order<br />

to be eligible for the <strong>UC</strong>OP borrowed funds, a portfolio of projects must meet minimum,<br />

although liberal, project cost return requirement. The anticipated criteria include a 85% ratio of<br />

loan payment to energy savings, which equates to approximately 15 year simple payback on the<br />

portfolio of projects.<br />

<strong>UC</strong>OP is prepared to lend up to $500 million to campuses through 2014 to support energysaving<br />

projects.<br />

To learn more about <strong>UC</strong>OP <strong>Energy</strong> Efficiency Project Financing, contact<br />

Dirk van Ulden<br />

Associate Director<br />

<strong>Energy</strong> & Utilities Services<br />

University of California Office of the President<br />

510-987-9392<br />

Dirk.vanulden@ucop.edu<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 13-2 December 31, 2008<br />

Newcomb | Anderson | McCormick


APPENDICES


Appendix A<br />

Field Data Forms<br />

(Electronic copies only – see folder “Appendix A - Field Data Forms” on disk)


Appendix B<br />

Savings Calculations<br />

(Electronic copies only – see folder “Appendix B- Savings Calculations” on disk)


Appendix C<br />

Other Calculations and Data<br />

(Electronic copies only – see folder “Appendix C- Other Calculations and Data” on disk)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!