24.07.2013 Views

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

The project involves installing DDC dampers on outside air intake, return air and exhaust air to<br />

control percentage of outside air and return air in supply air to vary according to the load and<br />

outside conditions. In addition, a retrofit kit (damper actuator, flow measuring station, outside air<br />

temperature and humidity monitoring station, mixed air temperature sensor) is installed on each<br />

of the air handler. This kit includes direct digital controls, which increases the cost but greatly<br />

increases the functionality. Enthalpy changeover control strategy will be adapted to use outside<br />

air in the most economical way without use of energy required to dehumidify additional outside<br />

air. Enthalpy is a measure of the total heat in the air, which is calculated by measuring both the<br />

dry bulb temperature and the relative humidity. Outside air will be used for cooling when the<br />

enthalpy of outside air is lower than the enthalpy of return air. Outside air and return air<br />

dampers are modulated to admit enough outside air to minimize cooling energy use. When<br />

outside air enthalpy is greater than the return air enthalpy, minimum outside air required for<br />

ventilation is brought into the space.<br />

8.2.10 Laboratory Air Handler Project 1. Convert Laboratory Air Handlers and Fume Hoods to<br />

Variable Air Volume<br />

The intention of this project is to convert laboratories to variable air volume systems and reduce<br />

the large outside air heating, cooling and fan power loads. Many existing labs are constant<br />

volume reheat systems, with a fixed air flow coming from the air handlers being reheated at the<br />

laboratory and exhausted through the constant volume hoods or room general exhaust. Most<br />

new laboratories utilize VAV air handlers and fume hoods. The intention of this project is to<br />

update the configuration of the existing labs so that they can operate as efficiently as the new<br />

labs. The <strong>UC</strong> EH&S Laboratory Safety Design Guide Second Edition September 2007 states<br />

“All laboratories should contain a fully integrated laboratory variable air volume (VAV)<br />

airflow/pressure control system to control room temperature, ventilation rate and room<br />

pressurization.”<br />

This project starts with a review of the air balance requirements of the facility. The air flow<br />

needs of each room are determined according to the function of the room, the number of hoods<br />

and the internal and external heat loads. This air balance may be significantly reduced from the<br />

existing design because of better understanding of actual loads or better design parameters.<br />

The minimum air changes typically needed in a laboratory are 6 air changes per hour for a room<br />

with a 10 foot ceiling, per the EH&S Design Guide. A given lab may need higher minimums,<br />

depending upon the density of hoods.<br />

The mechanical work includes converting the air handlers to VAV with the addition of VFDs to<br />

the supply fans. This may be appropriate for the exhaust fans as well, depending upon how<br />

they are ducted together. The hoods are converted to variable flow through the addition of an<br />

exhaust flow control valve and the sealing off of the sash bypass. If there are a small number of<br />

hoods in a larger room, these do not need to be converted to VAV, where the general exhaust<br />

requirements for the room are great enough that it makes no difference whether the air leaves<br />

through the hood or the general exhaust duct. The room supply air and general exhaust<br />

typically require new flow control valves or dampers as well to allow pressure control of each<br />

room. The exhaust fans may need stepping control and/or VFDs to maintain proper exhaust<br />

pressure in the duct and proper discharge velocity on the roof. The control systems should<br />

include supply temperature reset, utilizing either a DDC sequence or a controller such as DART,<br />

described above.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-10 December 31, 2008<br />

Newcomb | Anderson | McCormick

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!