24.07.2013 Views

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

8.8.3 <strong>UC</strong>LA Custom Project 3. TOD Controls on Exhaust Fans<br />

This project considers installing Time of Day Controls (TOD) on Toilet Exhaust Fans. Existing<br />

toilet fans run continuously and are not controlled through building energy management system.<br />

Fan with higher horsepower impose significant operating costs, both electric energy use and<br />

demand charges. Therefore with the time of day controls, fan operating hours will be matched<br />

with building occupancy schedule and controlled through building energy management system.<br />

This will allow fan to run only when building is occupied and turn off automatically when building<br />

is unoccupied.<br />

If required occupancy sensors can be also integrated with fan so that whenever occupancy<br />

detected, fan will be turn on. Time of day control on fan will significantly reduce electric energy<br />

usage charges.<br />

8.8.4 <strong>UC</strong>LA Custom Project 4. Condenser Water Reset<br />

This project considers implementing condenser water reset control strategy for water cooled<br />

chillers through use of existing building direct digital controls (DDC). In condenser water reset<br />

control, water supplied to chiller condenser is varied according to outside air wet bulb<br />

temperature. With condenser water reset methodology, variable set point is used to control<br />

condenser water entering temperature. Every cooling tower can cool water up to certain limits<br />

depending on tower design and ambient wet bulb temperature. Since tower size is fixed, only<br />

driving factor is ambient wet bulb temperature. Cooling tower can cool water to temperatures<br />

equal to “wet bulb temperature + cooling tower approach”. Approach is defined as the difference<br />

between cooling tower leaving water temperature and ambient wet bulb temperature. In other<br />

words if ambient wet bulb temperature is 50°F with cooling tower design approach of 14°F,<br />

cooling tower can cool water to temperature of 64°F. Most of the Chiller Manufacturer’s<br />

literature indicates that a one-degree drop in condenser entering water temperature will reduce<br />

chiller energy consumption by two percent. Due to location of the building, ambient conditions<br />

favor use of condenser water reset and fan power usage due to condenser water reset will be<br />

comparatively less than the energy used for the chiller. An algorithm will set upper and lower<br />

limits on condenser water temperature to protect chiller from damage and by restricting set point<br />

to minimum approach, fan speed will not be increased in vain to achieve impossibly low<br />

temperatures. Without condenser water reset strategy, Cooling tower will run at fixed low<br />

temperature wasting fan energy during conditions when cooling tower cannot achieve the setpoint<br />

due to higher outside air wet-bulb temperature/ or due to high cooling loads on chiller.<br />

Condenser water reset strategy calculates overall system load, chiller characteristics (kW/ton),<br />

outside air wet bulb (enthalpy) and determines the best possible condenser water set-point<br />

under given circumstances for an efficient plant operation.<br />

To implement condenser water reset strategy, a wet bulb temperature sensor and humidity<br />

sensor will be installed in cooling tower yard. The existing DDC panel will be programmed to<br />

add an algorithm to reset (lower) condenser water entering temperature based on ambient wet<br />

bulb temperature. This algorithm will be used to control cooling tower fan VFD to maintain preset<br />

temperature at existing temperature sensors.<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-19 December 31, 2008<br />

Newcomb | Anderson | McCormick

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!