24.07.2013 Views

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

UC Los Angeles Campus & Medical Center Strategic Energy Plan ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

8.2.3 Air Handler Project 3. Demand Control Ventilation<br />

This project adds a carbon dioxide sensor to air handlers that serve areas with highly variable<br />

occupancies, such as lecture halls, theaters, gymnasiums. Measurement of the carbon dioxide<br />

level is used to reset the minimum outside air flow function of the outside air economizer<br />

according to occupancy requirements. The project includes a carbon dioxide sensor which is<br />

usually located inside the lecture hall or building space. This will result in the heating and<br />

cooling of less outside air when it is not needed for ventilation.<br />

The minimum flow of outside air into the air handler has typically been designed according to full<br />

occupancy of the space. For example, if there are 200 seats in a lecture hall the minimum<br />

outside air flow may have been determined by multiplying 15 cfm per person (or seat) times 200<br />

seats, or 3,000 cfm. The outside air economizer would be adjusted never to drop below this<br />

level.<br />

In the modified case the minimum outside air flow will be allowed to drop to lower levels as long<br />

as adequate ventilation is maintained for the number of people in the room, as indicated by the<br />

carbon dioxide levels. This is a standard control sequence required by Title 24 for new<br />

construction in high density spaces. Title 24 requires a minimum outside air flow rate of at least<br />

0.15 cfm/sf, regardless of occupancy. This level of ventilation removes contaminants not<br />

related to human occupants. This level of outside air supply is typically found in office areas, so<br />

carbon dioxide sensors do not offer significant energy savings potential for offices and other<br />

areas that are never densely occupied.<br />

The savings are calculated for this project through a bin simulation adjusted for local weather,<br />

operating hours, building load characteristics, air handler flows and configuration, and<br />

temperature control strategies.<br />

The cost for implementing this project includes a carbon dioxide sensor, which can be factory<br />

calibrated with no need for additional calibration during its service life, and integration into the<br />

economizer control sequence. The campus can choose to monitor and log the carbon dioxide<br />

levels.<br />

This project does not apply to air handlers serving office areas or other relatively low density<br />

areas. It does not apply to patient handling or laboratory air handlers where other outside air<br />

requirements exist.<br />

8.2.4 Air Handler Project 4. Static Pressure Reset on Variable Air Volume Air Handlers<br />

This project adds a static pressure reset capability to existing VAV air handlers that do not have<br />

direct digital zone controls. The current design static pressure setpoint may be the appropriate<br />

pressure to operate at during hours of high air conditioning load, but it is not necessarily needed<br />

during other hours of operation. This project automatically resets the static pressure to a level<br />

that maintains comfort conditions but is typically lower than the original setpoint.<br />

There are two technologies commonly used to apply this control strategy. If the VAV system<br />

has direct digital controls at the room thermostats it is possible to use information from these<br />

thermostats to automatically reset the supply static pressure. It can be continuously reset so<br />

that a small portion of the VAV boxes are calling for full cooling. This would be an indicator that<br />

the pressure is operating at as low a point possible. For air handlers with DDC at the zones,<br />

2413.01/Reports/<strong>UC</strong> SEP Final Report – <strong>UC</strong>LA.doc 8-7 December 31, 2008<br />

Newcomb | Anderson | McCormick

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!