ASHRAE STANDARD - 55R
ASHRAE STANDARD - 55R
ASHRAE STANDARD - 55R
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
BSR/<strong>ASHRAE</strong> Standard 55P, Thermal Environmental Conditions for Human Occupancy 2/24/03<br />
Third Public Review Draft (Independent Substantive Changes to the Second Public Review)<br />
for people not wearing shoes. Nor does itThis standard does not address acceptable floor temperatures<br />
when people sit on the floor.<br />
Figure 5.2.4.4-1. Local discomfort caused by warm and cool floors.<br />
The limits for floor temperature are specified in Table 5.2.4.4-1. Alternatively, Figure 5.2.4.4-1 may be<br />
used in conjunction with the PD limits from Table 5.2.4-1 to determine the allowable floor temperature<br />
range.<br />
TABLE 5.2.4.4-1. Allowable range of the floor temperature for the three classes of the thermal<br />
environment.<br />
Class<br />
A<br />
B<br />
C<br />
Range of surface temperature of the floor °C ( o F)<br />
19 – 29 (66.2 - 84.2)<br />
19 - 29 (66.2 – 84.2)<br />
17 - 31 (62.6 - 87.8)<br />
19