NGTS 2.1<br />
Page 19 Issue 2<br />
May 1995<br />
A7 THE NEUTRAL AND NEUTRAL END CONNECTIONS OF TRANSFORMER AND SHUNT<br />
REACTORS<br />
For neutral current transformers associated with double-wound grid transformers and supergrid autotransformers,<br />
and neutral end current transformers associated with supergrid auto-transformers,<br />
accommodation shall be provided as follows:<br />
(i) Neutral current transformer housings shall provide accommodation for at least three current transformer<br />
windings as follows:<br />
Core 1 Protection Type B<br />
Core 2 Measurement/Protection<br />
Core 3 Measurement/Protection<br />
(ii) Neutral end current transformer housings shall provide accommodation for one Protection Type B<br />
current transformer winding per phase.<br />
(iii) Combined neutral and neutral-end current transformer housings shall provide accommodation for at<br />
least two neutral current transformer windings as follows:<br />
Core 1 Protection Type B (one current transformer per phase)<br />
Core 2 Measurement/Protection (one only - on neutral conductor)<br />
Core 3 Measurement/Protection (one only - on neutral conductor)<br />
For neutral and neutral end current transformers associated with supergrid shunt reactors, accommodation<br />
shall be provided as follows:<br />
(i) Neutral end current transformer housings shall provide accommodation for one Protection Type B current<br />
transformer per phase.<br />
(ii) Neutral current transformer housings shall provide accommodation for one Measurement/Protection<br />
current transformer.