NGTS 2.1<br />

Page 22 Issue 2<br />

May 1995<br />

B4 SINGLE SWITCH STATIONS<br />

Current transformers for feeder protection and for feeder instrumentation purposes shall be installed in the<br />

line current transformer housings.<br />

Current transformers for system back-up protection shall be installed in the line current transformer housings<br />

and in the bushings or housings on the higher numbered side of the bus section circuit-breaker; the current<br />

transformer for system back-up protection shall also be used for circuit-breaker fail protection.<br />

Current transformers for bus section instrumentation purposes shall be installed in the bushing or housings<br />

on the lower numbered zone side of the bus section circuit-breaker.<br />

Current transformers for mesh corner protection shall be installed in the line current transformer housings,<br />

the HV bushing turrets of the associated transformer(s) and in the bushings or housings on both sides of<br />

the bus section circuit-breaker, the current transformer for a particular zone or protection being located on<br />

the side of the circuit-breaker remote from that zone.