CONVERSIONS WITH LOW BRIGHTNESS LOUVRE<br />

Lux level<br />

mtg Ht (M) ELDL directly under<br />

65°-200cd/m2 100 4.0 2.5 5.5 5.2 2.4 1.9 5.9 6.4 1.8 3.1 6.5 7.6 3.7<br />

2.5<br />

4<br />

200 8.1 2.7 5.9 7.0 2.9 2.0 6.1 6.6 2.4 3.6 7.0 7.7 3.8<br />

600 24.4 3.3 6.6 7.6 3.7 2.2 6.6 7.2 2.6 3.8 7.2 7.8 3.8<br />

2000 81.1 3.6 7.0 7.7 3.8 * * * * * * * *<br />

4000 163.2 * * * * * * * * * * * *<br />

100 1.6 2.9 7.2 6.4 1.9 2.5 8.6 8.8 2.2 4.5 9.8 10.4 4.6<br />

200 3.2 3.6 8.6 8.8 3.2 3.0 9.1 9.9 3.0 4.9 10.2 10.6 5.1<br />

600 9.6 4.6 9.8 11.0 4.7 3.4 10.4 11.0 3.8 5.3 11.4 12.1 5.6<br />

2000 32.0 5.1 10.9 11.7 5.6 3.5 11.0 11.6 3.9 5.7 11.6 12.4 5.9<br />

4000 64.0 5.3 11.6 12.2 5.7 * * * * * * * *<br />

General 100 4.4 2.5 5.4 5.9 2.5 1.8 6.2 6.8 2.0 3.3 7.6 8.0 3.6<br />

Purpose<br />

200 8.8 2.7 6.4 7.0 2.9 2.2 6.5 7.6 2.4 3.8 7.8 8.6 4.0<br />

2.5<br />

4<br />

1 LUX MINIMUM ON CENTRE LINE 0.5 LUX MINIMUM IN CORE AREA 0.2 LUX MINIMUM ON CENTRE LINE<br />

ESCAPE ROUTES - ALL RISKS OPEN AREAS UNOBSTRUCTED ROUTES ONLY<br />

600 26.4 3.4 7.6 8.2 3.7 2.5 7.2 8.6 2.6 3.9 8.3 9.2 4.2<br />

2000 88.0 3.8 7.8 8.6 4.0 * * * * * * * *<br />

4000 176 * * * * * * * * * * * *<br />

100 1.7 2.2 6.8 6.80 2.0 2.3 8.6 8.9 2.3 4.4 9.8 11.6 4.8<br />

200 3.4 3.4 8.6 9.2 3.4 3.0 9.5 10.5 3.2 4.9 10.8 12.4 5.8<br />

600 10.2 4.5 10.1 11.8 5.0 3.5 11.2 12.6 4.1 5.7 12.6 13.9 6.4<br />

2000 34.0 5.4 12.0 13.2 6.1 3.7 12.0 13.4 4.2 6.1 12.9 14.8 6.7<br />

4000 64.0 5.7 12.6 14.0 6.4 * * * * * * * *<br />

CONVERSIONS WITH INDUSTRIAL WEATHERPROOF 120°<br />

cd/1000lm<br />

120° Nadir intensity 129cd/1000lm<br />

Lux level<br />

mtg Ht (M) ELDL directly under<br />

2.5<br />

4<br />

6<br />

10<br />

100 1.9 1.6 5.8 4.6 1.5 2.0 8.0 6.5 1.6 4.5 11.6 8.7 3.4<br />

200 3.8 2.9 8.2 6.4 2.3 2.8 10.7 8.0 2.2 5.8 15.0 10.6 4.6<br />

600 11.4 4.9 12.5 9.4 3.6 4.3 16.0 11.0 3.2 8.6 22.0 14.8 6.0<br />

2000 28.0 7.5 19.0 13.0 5.2 5.2 19.0 13.0 3.6 9.8 25.1 16.0 6.7<br />

4000 47.0 8.6 22.0 14.8 6.0 * * * * * * * *<br />

100 0.7 – – – – 2.2 8.0 6.6 1.1 4.6 13.0 10.0 3.8<br />

200 1.5 2.2 8.0 7.0 1.7 2.8 11.6 9.4 2.4 6.5 17.0 12.6 5.0<br />

600 4.5 5.1 13.9 10.6 4.1 4.8 18.0 13.5 3.7 9.8 25.4 17.8 7.3<br />

2000 15.2 8.5 22.0 15.8 6.2 7.7 28.0 19.5 5.5 15.0 38.0 25.0 10.3<br />

4000 30.4 11.0 27.0 19.6 7.9 * * * * * * * *<br />

100 0.3 – – – – – – – – 3.8 13.0 10.4 3.0<br />

200 0.6 – – – – 1.7 11.2 9.1 1.6 6.5 17.8 14.4 5.2<br />

600 2.0 4.5 14.2 11.1 3.8 4.9 19.6 15.2 3.8 10.8 28.0 21.0 8.2<br />

2000 6.8 8.9 24.2 18.4 7.2 8.4 32.0 23.5 6.3 17.0 44.0 30.0 12.4<br />

4000 13.6 12.1 31.6 23.7 9.2 10.8 40.0 28.0 8.0 22.0 54.0 36.0 15.0<br />

100 0.1 – – – – – – – – – – – –<br />

200 0.2 – – – – – – – – – – – –<br />

600 0.7 – – – – 3.5 19.6 16.0 2.8 11.3 31.5 25.0 9.0<br />

2000 2.4 8.6 20.6 20.6 7.1 9.1 36.0 28.0 7.0 19.5 52.0 38.0 15.0<br />

4000 4.8 13.0 27.6 27.6 10.3 12.2 48.0 36.0 9.6 26.0 63.0 46.0 19.0<br />

90°<br />

60°<br />

30°<br />

0.5L<br />

90°<br />

60°<br />

0.5L<br />

0.5L<br />

1 LUX MINIMUM ON CENTRE LINE 0.5 LUX MINIMUM IN CORE AREA 0.2 LUX MINIMUM ON CENTRE LINE<br />

ESCAPE ROUTES - ALL RISKS OPEN AREAS UNOBSTRUCTED ROUTES ONLY<br />

0.5L<br />

cd/1000lm<br />

100<br />

200<br />

300<br />

40<br />

80<br />

120<br />

0.5L<br />

30° 30°<br />

0.5L<br />

90°<br />

60°<br />

30°<br />

0.5L<br />

90°<br />

60°<br />

0.5L<br />

Nadir intensity 320cd/1000lm<br />

ULOR 0.00<br />

DLOR 0.61<br />

LOR 0.61<br />

ULOR 0.15<br />

DLOR 0.57<br />

LOR 0.72<br />

461<br />