202<br />
Emergency Luminaires - Testing Systems<br />
<strong>INTELLEM</strong><br />
•Provides simple and reliable automatic testing<br />
of emergency lighting<br />
•Tests fully comply with EN50172 & BS5266<br />
• Easy to install, stand alone operation<br />
• No data cable required<br />
• Simple offset feature to stagger testing<br />
• Optional infra-red programmable version<br />
• 28 day test cycle to ensure tests are performed<br />
on same day of the week<br />
Intellem offers a simple and competitive solution to the<br />
mandatory requirements for the regular testing of<br />
emergency luminaires. The basic product, Intellem Self<br />
Check, requires no setting up. Converted luminaires are<br />
simply installed, providing instant monitoring of the<br />
emergency circuit and automatic testing at intervals<br />
compliant with legislation. System status is clearly<br />
indicated via the LED flash sequence and on-board<br />
audible alarm, which can be disabled if required by the<br />
user. Infra-Red offers enhanced flexibility. A hand held<br />
infra-red programmer is used to set up convenient test<br />
times, read luminaire and fault status, initiate manual<br />
tests or change testing intervals. Intellem is particularly<br />
beneficial in refurbishment projects, as no additional<br />
cabling is required.<br />
WHERE TO USE <strong>INTELLEM</strong><br />
• Offices • Public houses<br />
• Universities, schools and colleges • Hotels and guest houses<br />
• Retail outlets • Medical centres<br />
• Restaurants • Industrial facilities
SYSTEM OPERATION<br />
• Intellem is available as a simple and basic automatic testing<br />
system - Intellem Self Check, or with enhanced infra-red<br />
programming and 2 way communication - Intellem Infra Red.<br />
System operation for Self Check and Infra-Red is the same,<br />
except where enhancements for Infra-Red are detailed below<br />
• An Intellem diagnostic unit is fitted into all suitable self-contained<br />
dedicated emergency luminaires and mains luminaires<br />
converted for emergency operation. Infra-Red versions also<br />
have the addition of an infra-red transmitter and receiver<br />
• Upon initial power up the unit self calibrates, determining the<br />
correct values for the parameters to be checked during<br />
monitoring and testing<br />
• Test intervals are determined from the moment of initial power<br />
up, with a built in automatic 12 hour offset to ensure that<br />
luminaires installed during the day are tested at night.<br />
• Intellem Infra-Red testing schedules can be reconfigured using<br />
a hand held programmer. The time and day counter can be<br />
programmed and read via the hand held unit<br />
• A full duration test is initiated 36 hours after initial power up,<br />
to commission the unit<br />
• Luminaire status is continuously monitored and information<br />
provided via the luminaire LED and on-board audible alarm.<br />
In the event of a fault, the alarm sounds and the precise nature<br />
of the fault indicated by the LED flashing sequence<br />
• Intellem Infra-Red units can be interrogated, with details of the<br />
luminaire status downloaded to the programmer display<br />
• Testing is automatically carried out as per the Intellem testing<br />
schedule, to meet and exceed the requirements of EN50172.<br />
Intellem Infra-Red has an optional test set-up to meet BS5266,<br />
or can be programmed for customised test schedules<br />
• The first function test occurs 28 days after the initial<br />
commissioning test, or as programmed with Intellem Infra-Red<br />
units.<br />
• Any faults identified during testing are indicated as above<br />
• Manual short (10 second) or full duration tests can be<br />
initiated with Intellem Infra-Red, via the hand held programmer<br />
LUMINAIRE DIAGNOSTIC UNIT<br />
Compact unit, factory fitted into all compatible self-contained<br />
emergency luminaires. Self calibrates upon power up for charger<br />
and battery characteristics. Has a built in day and time counter<br />
and carries out all testing automatically. Removable link disables<br />
the on-board audible alarm, as required. Removable offset link<br />
fitted to Self Check versions, which advances testing cycle by one<br />
day if removed, thereby staggering testing in adjacent luminaires<br />
if required. Infra-Red units have socket to accept plug in<br />
LED/transmitter/receiver module, which is fitted integral to host<br />
luminaire or in a remote ceiling mounted plate.<br />
Diagnostic unit dims: L54 x W38 x D24mm.<br />
Luminaire diagnostic unit & LED/transmitter/receivers<br />
LUMINAIRES<br />
Intellem Self Check and Infra-Red can be integrated into the<br />
majority of Menvier and JSB self contained emergency luminaires<br />
or exit signs and most Crompton Lighting emergency converted<br />
fluorescent luminaires. See the individual product entries for details<br />
of compatibility. Intellem can also be used with Convertalite and<br />
ADV conversion kits, when fitted by Cooper Lighting and Security.<br />
For further information please contact our Technical Support and<br />
Application department. Tel: 01302 303350<br />
<strong>INTELLEM</strong><br />
203<br />
Emergency Luminaires - Testing Systems
204<br />
Emergency Luminaires - Testing Systems<br />
<strong>INTELLEM</strong><br />
HAND HELD PROGRAMMER<br />
Used for the programming and interrogation of Intellem Infra-Red<br />
units, with infra-red communication protocol. Simple to use with 2<br />
lines x 16 character LCD display and 2 pushbuttons. Buttons<br />
provide access to and scroll through programming menus,<br />
increment numeric commands, accept settings and upload or<br />
download information to unit. Programming features and<br />
commands accessed via the programmer are:<br />
• Set days counter and real time clock on programmer<br />
• Set and read the diagnostic unit clock and days counter<br />
• Read the operational status of the luminaire<br />
• Set and read the time and day when the next test will occur<br />
• Read the test number, time and day when last test was<br />
conducted<br />
• Read the precise nature of fault condition status<br />
• Instigate manual short functional or full duration tests<br />
• Change the test sequence and frequency (advanced setting)<br />
• Temporarily silence audible alarm or reinstate<br />
TEST PROGRAMMES<br />
Intellem provides automatic testing that conforms and exceeds the<br />
current British Standard BS5266 Part 1 (1999) and the European<br />
Standard EN50172. Other test regimes can also be programmed<br />
as required when Intellem Infra-Red is specified. Testing and<br />
monitoring is undertaken as follows:<br />
BS 5266 TEST REQUIREMENTS<br />
Daily<br />
Check for correct operation<br />
Monthly<br />
Functionality test not exceeding 25% of rated<br />
duration<br />
Six Monthly<br />
Test of at least 1 hour for a 3 hour rated system<br />
Three Yearly<br />
Full duration discharge test<br />
Subsequently<br />
Annual duration discharge test after 3 years<br />
<strong>INTELLEM</strong> DEFAULT TEST SCHEDULE<br />
Continual<br />
Monitoring of battery and charger status<br />
Every 28 days (4 weeks)<br />
Test emergency luminaire for 5 minutes<br />
12th Test in Cycle (48 weeks)<br />
Full duration discharge test<br />
INFRA-RED OPTIONAL TEST SCHEDULE<br />
Continual<br />
Monitoring of battery and charger status<br />
Every 28 days (4 weeks)<br />
Test emergency luminaire for 5 minutes<br />
6th Test in Cycle (24 weeks)<br />
1 hour duration discharge test<br />
12th Test in Cycle (48 weeks)<br />
Full duration discharge test<br />
Notes:<br />
1. Intellem operates on a test cycle of 12 test events, performed every 28 days<br />
2. The Fire Precautions (Workplace) Regulations 1997 and EN50172 omit the six monthly 1 hour test, replacing it with an annual full duration discharge test after the first year and every year thereafter<br />
To overcome difficulties in permanently occupied premises, Intellem<br />
Self Check units are provided with an offset key which advances<br />
the test program by 1 day. Every second luminaire, when<br />
adjacent, would be fitted with the key in order to provide full<br />
duration emergency lighting coverage at all times. this would be<br />
overcome by programming with Intellem Infra-Red luminaires.<br />
Hand held programmer<br />
Testing is carried out on a 28 day (4 week) test cycle, to ensure<br />
that testing is always performed on the same day of the week for<br />
convenience.<br />
Following a genuine mains failure of 15 minutes or more in the<br />
previous 24 hours, the next scheduled test is automatically delayed<br />
for a further 24 hours, to allow sufficient time for the batteries to<br />
recharge. Manual full duration tests are also inhibited for 24 hours<br />
following a genuine mains failure or scheduled test.
LED STATUS INDICATION<br />
If the diagnostic unit detects a battery or charger fault during<br />
monitoring or additionally a lamp fault during a test, an audible<br />
alarm will sound. The LED flashing sequence detailed below<br />
indicates the precise nature of the fault.<br />
Lamp Test Failure<br />
Duration Test Failure<br />
Low Charge Current<br />
Low Battery Voltage<br />
Reset Alarm<br />
Power Save Mode<br />
1 second 1 second 1 second 1 second 1 second<br />
1 minute<br />
SYSTEM DESIGN & INSTALLATION<br />
• Determine the number and type of emergency luminaires to be<br />
used, using the spacing charts at the rear of this catalogue<br />
• Specify the luminaires to be complete with Intellem Self Check<br />
or Infra-Red diagnostic units, after confirming compatibility<br />
• If using Intellem Self Check luminaires, install, removing offset<br />
link as appropriate<br />
• If using Intellem Infra-Red luminaires, install and set up test day<br />
and time as required, using hand held programmer<br />
• No additional data cable is required. Luminaires are installed<br />
as normal<br />
CATALOGUE NUMBERS<br />
Description Cat. No. Weight<br />
Intellem Infra-Red Hand Held Programmer IRHHP 0.25<br />
See individual product entries for catalogue numbers of emergency luminaires fitted with<br />
Intellem Self Check or Intellem Infra-Red<br />
For full details of combined mains/emergency luminaires fitted with Intellem Self Check or<br />
Intellem Infra-Red, see appropriate product entry or contact our Technical Support and<br />
Application department. Tel: 01302 303350<br />
Intellem functionality can be specified for the majority of dedicated and emergency converted luminaires in this catalogue<br />