202<br />

Emergency Luminaires - Testing Systems<br />

<strong>INTELLEM</strong><br />

•Provides simple and reliable automatic testing<br />

of emergency lighting<br />

•Tests fully comply with EN50172 & BS5266<br />

• Easy to install, stand alone operation<br />

• No data cable required<br />

• Simple offset feature to stagger testing<br />

• Optional infra-red programmable version<br />

• 28 day test cycle to ensure tests are performed<br />

on same day of the week<br />

Intellem offers a simple and competitive solution to the<br />

mandatory requirements for the regular testing of<br />

emergency luminaires. The basic product, Intellem Self<br />

Check, requires no setting up. Converted luminaires are<br />

simply installed, providing instant monitoring of the<br />

emergency circuit and automatic testing at intervals<br />

compliant with legislation. System status is clearly<br />

indicated via the LED flash sequence and on-board<br />

audible alarm, which can be disabled if required by the<br />

user. Infra-Red offers enhanced flexibility. A hand held<br />

infra-red programmer is used to set up convenient test<br />

times, read luminaire and fault status, initiate manual<br />

tests or change testing intervals. Intellem is particularly<br />

beneficial in refurbishment projects, as no additional<br />

cabling is required.<br />

WHERE TO USE <strong>INTELLEM</strong><br />

• Offices • Public houses<br />

• Universities, schools and colleges • Hotels and guest houses<br />

• Retail outlets • Medical centres<br />

• Restaurants • Industrial facilities


SYSTEM OPERATION<br />

• Intellem is available as a simple and basic automatic testing<br />

system - Intellem Self Check, or with enhanced infra-red<br />

programming and 2 way communication - Intellem Infra Red.<br />

System operation for Self Check and Infra-Red is the same,<br />

except where enhancements for Infra-Red are detailed below<br />

• An Intellem diagnostic unit is fitted into all suitable self-contained<br />

dedicated emergency luminaires and mains luminaires<br />

converted for emergency operation. Infra-Red versions also<br />

have the addition of an infra-red transmitter and receiver<br />

• Upon initial power up the unit self calibrates, determining the<br />

correct values for the parameters to be checked during<br />

monitoring and testing<br />

• Test intervals are determined from the moment of initial power<br />

up, with a built in automatic 12 hour offset to ensure that<br />

luminaires installed during the day are tested at night.<br />

• Intellem Infra-Red testing schedules can be reconfigured using<br />

a hand held programmer. The time and day counter can be<br />

programmed and read via the hand held unit<br />

• A full duration test is initiated 36 hours after initial power up,<br />

to commission the unit<br />

• Luminaire status is continuously monitored and information<br />

provided via the luminaire LED and on-board audible alarm.<br />

In the event of a fault, the alarm sounds and the precise nature<br />

of the fault indicated by the LED flashing sequence<br />

• Intellem Infra-Red units can be interrogated, with details of the<br />

luminaire status downloaded to the programmer display<br />

• Testing is automatically carried out as per the Intellem testing<br />

schedule, to meet and exceed the requirements of EN50172.<br />

Intellem Infra-Red has an optional test set-up to meet BS5266,<br />

or can be programmed for customised test schedules<br />

• The first function test occurs 28 days after the initial<br />

commissioning test, or as programmed with Intellem Infra-Red<br />

units.<br />

• Any faults identified during testing are indicated as above<br />

• Manual short (10 second) or full duration tests can be<br />

initiated with Intellem Infra-Red, via the hand held programmer<br />

LUMINAIRE DIAGNOSTIC UNIT<br />

Compact unit, factory fitted into all compatible self-contained<br />

emergency luminaires. Self calibrates upon power up for charger<br />

and battery characteristics. Has a built in day and time counter<br />

and carries out all testing automatically. Removable link disables<br />

the on-board audible alarm, as required. Removable offset link<br />

fitted to Self Check versions, which advances testing cycle by one<br />

day if removed, thereby staggering testing in adjacent luminaires<br />

if required. Infra-Red units have socket to accept plug in<br />

LED/transmitter/receiver module, which is fitted integral to host<br />

luminaire or in a remote ceiling mounted plate.<br />

Diagnostic unit dims: L54 x W38 x D24mm.<br />

Luminaire diagnostic unit & LED/transmitter/receivers<br />

LUMINAIRES<br />

Intellem Self Check and Infra-Red can be integrated into the<br />

majority of Menvier and JSB self contained emergency luminaires<br />

or exit signs and most Crompton Lighting emergency converted<br />

fluorescent luminaires. See the individual product entries for details<br />

of compatibility. Intellem can also be used with Convertalite and<br />

ADV conversion kits, when fitted by Cooper Lighting and Security.<br />

For further information please contact our Technical Support and<br />

Application department. Tel: 01302 303350<br />

<strong>INTELLEM</strong><br />

203<br />

Emergency Luminaires - Testing Systems


204<br />

Emergency Luminaires - Testing Systems<br />

<strong>INTELLEM</strong><br />

HAND HELD PROGRAMMER<br />

Used for the programming and interrogation of Intellem Infra-Red<br />

units, with infra-red communication protocol. Simple to use with 2<br />

lines x 16 character LCD display and 2 pushbuttons. Buttons<br />

provide access to and scroll through programming menus,<br />

increment numeric commands, accept settings and upload or<br />

download information to unit. Programming features and<br />

commands accessed via the programmer are:<br />

• Set days counter and real time clock on programmer<br />

• Set and read the diagnostic unit clock and days counter<br />

• Read the operational status of the luminaire<br />

• Set and read the time and day when the next test will occur<br />

• Read the test number, time and day when last test was<br />

conducted<br />

• Read the precise nature of fault condition status<br />

• Instigate manual short functional or full duration tests<br />

• Change the test sequence and frequency (advanced setting)<br />

• Temporarily silence audible alarm or reinstate<br />

TEST PROGRAMMES<br />

Intellem provides automatic testing that conforms and exceeds the<br />

current British Standard BS5266 Part 1 (1999) and the European<br />

Standard EN50172. Other test regimes can also be programmed<br />

as required when Intellem Infra-Red is specified. Testing and<br />

monitoring is undertaken as follows:<br />

BS 5266 TEST REQUIREMENTS<br />

Daily<br />

Check for correct operation<br />

Monthly<br />

Functionality test not exceeding 25% of rated<br />

duration<br />

Six Monthly<br />

Test of at least 1 hour for a 3 hour rated system<br />

Three Yearly<br />

Full duration discharge test<br />

Subsequently<br />

Annual duration discharge test after 3 years<br />

<strong>INTELLEM</strong> DEFAULT TEST SCHEDULE<br />

Continual<br />

Monitoring of battery and charger status<br />

Every 28 days (4 weeks)<br />

Test emergency luminaire for 5 minutes<br />

12th Test in Cycle (48 weeks)<br />

Full duration discharge test<br />

INFRA-RED OPTIONAL TEST SCHEDULE<br />

Continual<br />

Monitoring of battery and charger status<br />

Every 28 days (4 weeks)<br />

Test emergency luminaire for 5 minutes<br />

6th Test in Cycle (24 weeks)<br />

1 hour duration discharge test<br />

12th Test in Cycle (48 weeks)<br />

Full duration discharge test<br />

Notes:<br />

1. Intellem operates on a test cycle of 12 test events, performed every 28 days<br />

2. The Fire Precautions (Workplace) Regulations 1997 and EN50172 omit the six monthly 1 hour test, replacing it with an annual full duration discharge test after the first year and every year thereafter<br />

To overcome difficulties in permanently occupied premises, Intellem<br />

Self Check units are provided with an offset key which advances<br />

the test program by 1 day. Every second luminaire, when<br />

adjacent, would be fitted with the key in order to provide full<br />

duration emergency lighting coverage at all times. this would be<br />

overcome by programming with Intellem Infra-Red luminaires.<br />

Hand held programmer<br />

Testing is carried out on a 28 day (4 week) test cycle, to ensure<br />

that testing is always performed on the same day of the week for<br />

convenience.<br />

Following a genuine mains failure of 15 minutes or more in the<br />

previous 24 hours, the next scheduled test is automatically delayed<br />

for a further 24 hours, to allow sufficient time for the batteries to<br />

recharge. Manual full duration tests are also inhibited for 24 hours<br />

following a genuine mains failure or scheduled test.


LED STATUS INDICATION<br />

If the diagnostic unit detects a battery or charger fault during<br />

monitoring or additionally a lamp fault during a test, an audible<br />

alarm will sound. The LED flashing sequence detailed below<br />

indicates the precise nature of the fault.<br />

Lamp Test Failure<br />

Duration Test Failure<br />

Low Charge Current<br />

Low Battery Voltage<br />

Reset Alarm<br />

Power Save Mode<br />

1 second 1 second 1 second 1 second 1 second<br />

1 minute<br />

SYSTEM DESIGN & INSTALLATION<br />

• Determine the number and type of emergency luminaires to be<br />

used, using the spacing charts at the rear of this catalogue<br />

• Specify the luminaires to be complete with Intellem Self Check<br />

or Infra-Red diagnostic units, after confirming compatibility<br />

• If using Intellem Self Check luminaires, install, removing offset<br />

link as appropriate<br />

• If using Intellem Infra-Red luminaires, install and set up test day<br />

and time as required, using hand held programmer<br />

• No additional data cable is required. Luminaires are installed<br />

as normal<br />

CATALOGUE NUMBERS<br />

Description Cat. No. Weight<br />

Intellem Infra-Red Hand Held Programmer IRHHP 0.25<br />

See individual product entries for catalogue numbers of emergency luminaires fitted with<br />

Intellem Self Check or Intellem Infra-Red<br />

For full details of combined mains/emergency luminaires fitted with Intellem Self Check or<br />

Intellem Infra-Red, see appropriate product entry or contact our Technical Support and<br />

Application department. Tel: 01302 303350<br />

Intellem functionality can be specified for the majority of dedicated and emergency converted luminaires in this catalogue<br />

<strong>INTELLEM</strong><br />

205<br />

Emergency Luminaires - Testing Systems