• Saves time and cost on testing & maintenance<br />
•Tests fully comply with BS5266 & EN50172<br />
• Easy to use control panel<br />
• 250 address capacity per panel<br />
• Stand alone or network up to 63 panels<br />
• Events log and test reports can be printed<br />
• Colour graphics software package available<br />
EASICHECK<br />
EasiCheck offers an advanced, versatile and flexible<br />
solution to automatic testing, which is easy to use and<br />
provides a high level of integrity. Each panel can monitor<br />
up to 250 luminaires, continuously checking battery<br />
voltage and charge current. Functionality and duration<br />
tests are performed automatically at frequencies that<br />
exceed the requirements of the current codes of practice.<br />
All faults are displayed on the panel, providing location<br />
text and the nature of the fault, to aid maintenance.<br />
EasiCheck is suitable for all size of projects, but<br />
particularly medium to large installations, where panels<br />
can be networked or where optional site monitoring or<br />
colour graphics software is required, providing central<br />
PC control.<br />
WHERE TO USE EASICHECK<br />
• Hospitals • Shopping centres<br />
• Universities, schools and colleges • Retail outlets<br />
• Museums • Offices<br />
• Airports • Industrial facilities<br />
195<br />
Emergency Luminaires - Testing Systems
196<br />
Emergency Luminaires - Testing Systems<br />
EASICHECK<br />
SYSTEM OPERATION<br />
• An EasiCheck interface module is fitted into all suitable<br />
dedicated emergency luminaires and mains luminaires<br />
converted for emergency operation<br />
• Each module is given a unique address number, using a hand<br />
held programmer<br />
• Every luminaire is then connected to a 2 core data BUS cable,<br />
which is linked back to the control panel. A single panel can<br />
accommodate up to 250 luminaires (self contained systems) or<br />
255 luminaires and addressable devices (central power<br />
systems)<br />
• When switched on, the panel will self learn the number of<br />
luminaires connected to it<br />
• Text information can be allocated to each system component,<br />
including central battery units and changeover devices etc for<br />
central power system versions, during commissioning by a<br />
Cooper Lighting and Security service engineer<br />
• The panel can then be programmed to carry out automatic test<br />
sequences according to BS5266 or EN50172. Testing can<br />
also be initiated manually. All test data is sent back and stored<br />
at the control panel. Additionally, the system carries out<br />
continuous real time monitoring of all connected devices<br />
• Central battery unit status is constantly monitored on central<br />
power systems version. Multiple CBU's can be controlled by a<br />
single panel<br />
• In the event of a fault, the precise location of the device is<br />
displayed at the control panel along with accurate details of<br />
the nature of the fault and an alarm is raised<br />
• Luminaire status is provided locally via a 2 colour LED built into<br />
each fitting<br />
• A printer can be connected, which automatically prints details<br />
of any system events as soon as they occur<br />
• The system can be enhanced by networking up to 63 panels.<br />
Central PC monitoring and a global network printer can also<br />
be incorporated. An advanced colour graphics software<br />
package is available to provide central and remote system<br />
control and monitoring<br />
PANEL<br />
Constructed from flame retardant polycarbonate. 2 line x 40<br />
character LCD display and soft touch 5 button keypad. A single<br />
panel can accommodate up to 250 luminaires or interfaces.<br />
If a greater number are required, up to 63 panels can be linked<br />
using a networking card. Access to panel functions is by means<br />
of a secure password. All functions controlled by the keypad,<br />
via a series of user friendly menus with context sensitive help<br />
information. System and luminaire faults can be viewed without<br />
input of password. Panel has printer connection facility and battery<br />
back-up. An on-board alarm is fitted, which is activated when<br />
faults are identified. Alarm can be muted using keypad.<br />
Panel is used to facilitate following functions:<br />
- Set up test types and times<br />
- Set up testing groups<br />
- Initiate manual tests<br />
- Display real time current/voltage of single luminaire<br />
- Print test results (remote printer)<br />
In addition, LED indicators display the following status:<br />
- Power on<br />
- Emergency mode<br />
- General fault<br />
- System fault<br />
- Test in progress<br />
- Disable luminaire groups<br />
- Fault indication in luminaire groups 1-16<br />
DIMENSIONS<br />
H<br />
D<br />
L<br />
MUTE SCROLL<br />
BUZZER<br />
1 2 3 4 5<br />
H (mm) L (mm) D (mm)<br />
270 332 90
LUMINAIRE INTERFACE<br />
Compact module fitted into all emergency luminaires to be<br />
connected to the system. Self-contained and slave luminaire<br />
versions. Requires allocation of address by hand held programmer,<br />
prior to being connected to data BUS cable.<br />
Dims: L54xW38xD24mm.<br />
HAND HELD PROGRAMMER<br />
Used to program address into all interface devices. Simple to use.<br />
Sprung probes are held against interface contacts and program<br />
button pressed until display confirms successful programming.<br />
Display increments address automatically by 1, ready for next<br />
interface. Address number can be manually allocated, if required,<br />
using “Tens” and “Units” buttons. Can also be used to read back<br />
the address of a programmed interface.<br />
Dims: L152xW82xD35mm.<br />
PRINTER<br />
High speed thermal printer for connection directly to a dedicated<br />
panel, or as a network printer using separate interface. Provides<br />
print out of system status, event log as faults occur, or test results.<br />
Virtually silent operation. Requires adjacent mains power socket<br />
outlet for connection of power supply unit.<br />
Dims: L155xW100xD75mm.<br />
MAINS CHANGEOVER COMBINED MODULE<br />
Used to changeover from normal mains to emergency 230V AC<br />
supply. EasiCheck addressable version of ACM1.<br />
Dims: L215xW37xD30mm.<br />
OTHER INTERFACES & DEVICES<br />
There is a comprehensive range of network interfaces and devices<br />
for self-contained and central power supply installations that are<br />
available to meet project requirements. For information, please<br />
contact our Technical Support and Application department.<br />
Tel: 01302 303350.<br />
LUMINAIRES<br />
EasiCheck can be integrated into the majority of Menvier and<br />
JSB self contained and slave emergency luminaires or exit signs<br />
and most Crompton Lighting emergency converted fluorescent<br />
luminaires. See the individual product entries for details of<br />
compatibility. EasiCheck can also be used with Convertalite and<br />
ADV conversion kits, when fitted by Cooper Lighting and Security.<br />
Suitable mains luminaires that are intended for use with a static<br />
inverter system can usually be fitted with an EasiCheck slave<br />
interface. For further information please contact our Technical<br />
Support and Application department. Tel: 01302 303350.<br />
Luminaire interface<br />
Hand held programmer<br />
EasiCheck printer<br />
EASICHECK<br />
197<br />
Emergency Luminaires - Testing Systems
198<br />
Emergency Luminaires - Testing Systems<br />
EASICHECK<br />
TEST PROGRAMMES<br />
EasiCheck provides automatic testing that conforms and exceeds the current British Standard BS5266 Part 1 (1999) and the European<br />
Standard EN50172. Other test regimes can also be programmed as required.<br />
BS 5266 TEST REQUIREMENTS<br />
Daily<br />
Check for correct operation<br />
Monthly<br />
Functionality test not exceeding 25% of rated duration<br />
Six Monthly<br />
Test of at least 1 hour for a 3 hour rated system<br />
Three Yearly<br />
Full duration discharge test<br />
Subsequently<br />
After first 3 years, an annual duration discharge test is required<br />
EASICHECK TEST SCHEDULE<br />
Continual<br />
Monitoring of battery and charger status<br />
Weekly or Monthly (selectable)<br />
Test emergency circuit for up to 5 minutes<br />
Six Monthly<br />
Full duration discharge test<br />
Yearly<br />
Full duration discharge test<br />
Note: The Fire Precautions (Workplace) Regulations 1997 and EN50172 omit the six monthly 1 hour test, replacing it with an annual full duration discharge test after the first year and every year thereafter<br />
It is recommended that discharge tests are performed at a time of<br />
least risk, such as outside normal working hours, so that following<br />
the test the batteries can be re-charged prior to re-occupation. This<br />
can be difficult in permanently occupied premises. To overcome<br />
this, EasiCheck luminaires can be allocated into 1 of up to 16<br />
test groups and the testing of each group staggered. Adjacent<br />
luminaires would be allocated to different groups in order to<br />
provide full duration emergency lighting coverage at all times.<br />
2<br />
2<br />
1 1<br />
2<br />
Following a genuine mains failure that has occurred in the previous<br />
24 hours, the next scheduled test is automatically delayed for a<br />
further 24 hours, to allow sufficient time for the batteries to<br />
recharge. Manual tests are also inhibited for 24 hours following a<br />
genuine mains failure or scheduled test. All test results can be<br />
downloaded to an optional printer.<br />
EasiCheck wiring schematic, demonstrating how allocation of test groups can stagger the testing of adjacent luminaires<br />
3<br />
4<br />
3<br />
3<br />
1<br />
2<br />
4<br />
3<br />
2<br />
1<br />
4
SYSTEM DESIGN & INSTALLATION<br />
• Determine the number and type of EasiCheck compatible<br />
emergency luminaires to be used, using the spacing charts at<br />
the rear of this catalogue<br />
• Specify the luminaires to be complete with EasiCheck<br />
addressable interface modules<br />
• Locate the control panel in a suitable clean, dry environment,<br />
such as a maintenance office<br />
• Address all luminaires and interface devices as applicable<br />
using the hand held programmer<br />
• Connect data BUS cable. Cable must be 2 core screened or<br />
twisted pair, typically 1.0 - 2.5mm2 depending on volt drop<br />
limitations. Contact Technical Support for full details of the<br />
required cable specification. Polarity must be maintained<br />
throughout.<br />
• Circuit configuration for data cable can be a ring, radial or<br />
a preferred combination of a ring with multiple radial spurs<br />
EasiCheck typical schematic diagram<br />
Optional<br />
P.C.<br />
Optional<br />
Printer<br />
Optional<br />
Isolator<br />
Optional<br />
Isolator<br />
Optional<br />
Isolator<br />
• Short circuit isolators are incorporated into the panel as<br />
standard. Further isolators can be added to the circuit,<br />
if required, to minimise loss of communication due to a<br />
short circuit and make fault finding easier. Note: Loss of<br />
communication does NOT affect the integrity of the emergency<br />
luminaire operation<br />
• The panel is set to auto learn the devices connected to it.<br />
The panel can then be commissioned by Cooper Lighting<br />
and Security, using a PC to download address, group, type of<br />
luminaire, number of cells, duration, descriptive address text<br />
and test times<br />
• The panel can be used to adjust test times, initiate manual tests,<br />
display luminaire voltage and current and print out event logs or<br />
test results<br />
Optional P.C. Interface<br />
Optional<br />
Isolator<br />
Optional<br />
Isolator<br />
Optional Printer Interface<br />
Optional EasiCheck Printer<br />
(can also be directly connected to panel)<br />
EASICHECK<br />
199<br />
Emergency Luminaires - Testing Systems
200<br />
Emergency Luminaires - Testing Systems<br />
EASICHECK<br />
ENHANCED OPTIONS<br />
EasiCheck can be used as a stand alone system or can be<br />
networked, with up to 63 panels being linked. The management<br />
of larger installations with multiple panels can be simplified by<br />
interfacing the system with a PC based monitoring or graphical<br />
control system. Cooper Lighting and Security offer two software<br />
systems for use with EasiCheck.<br />
• Site Monitoring Software<br />
- Simple windows based, text driven package<br />
- Monitors the status of all panels and luminaires<br />
- All system events and tests are listed as they happen<br />
- Identifies the address panel/luminaire and location where a<br />
fault has occurred<br />
- Tests can be started or stopped<br />
- Panels can be reset following clearing of faults<br />
- Alarm buzzer can be muted<br />
• Colour Graphics<br />
- Advanced windows based, graphics package<br />
- Site plans can be imported<br />
- Monitors the status of all panels and luminaires<br />
- All system events and tests are listed as they happen<br />
- Identifies the address panel/luminaire and location where a<br />
fault has occurred<br />
- Offers full PC control of panel functionality<br />
- Status, testing and faults can be displayed graphically on site<br />
plans<br />
- Reports can be easily created and printed<br />
CATALOGUE NUMBERS<br />
Description Cat. No.<br />
Control panel - self contained systems EC1001<br />
Control panel - central power systems EC1002<br />
Interface module - self contained luminaires EC110<br />
Interface module - slave luminaires EC125<br />
Addressable mains changeover relay EC140<br />
Network card (fitted inside control panel) EC150/151<br />
Hand held programmer EC160<br />
Printer EC170<br />
Example of site monitoring software<br />
Example of colour graphic software<br />
Example of colour graphic software