EASICHECK™
EASICHECK™
EASICHECK™
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
196<br />
Emergency Luminaires - Testing Systems<br />
EASICHECK<br />
SYSTEM OPERATION<br />
• An EasiCheck interface module is fitted into all suitable<br />
dedicated emergency luminaires and mains luminaires<br />
converted for emergency operation<br />
• Each module is given a unique address number, using a hand<br />
held programmer<br />
• Every luminaire is then connected to a 2 core data BUS cable,<br />
which is linked back to the control panel. A single panel can<br />
accommodate up to 250 luminaires (self contained systems) or<br />
255 luminaires and addressable devices (central power<br />
systems)<br />
• When switched on, the panel will self learn the number of<br />
luminaires connected to it<br />
• Text information can be allocated to each system component,<br />
including central battery units and changeover devices etc for<br />
central power system versions, during commissioning by a<br />
Cooper Lighting and Security service engineer<br />
• The panel can then be programmed to carry out automatic test<br />
sequences according to BS5266 or EN50172. Testing can<br />
also be initiated manually. All test data is sent back and stored<br />
at the control panel. Additionally, the system carries out<br />
continuous real time monitoring of all connected devices<br />
• Central battery unit status is constantly monitored on central<br />
power systems version. Multiple CBU's can be controlled by a<br />
single panel<br />
• In the event of a fault, the precise location of the device is<br />
displayed at the control panel along with accurate details of<br />
the nature of the fault and an alarm is raised<br />
• Luminaire status is provided locally via a 2 colour LED built into<br />
each fitting<br />
• A printer can be connected, which automatically prints details<br />
of any system events as soon as they occur<br />
• The system can be enhanced by networking up to 63 panels.<br />
Central PC monitoring and a global network printer can also<br />
be incorporated. An advanced colour graphics software<br />
package is available to provide central and remote system<br />
control and monitoring<br />
PANEL<br />
Constructed from flame retardant polycarbonate. 2 line x 40<br />
character LCD display and soft touch 5 button keypad. A single<br />
panel can accommodate up to 250 luminaires or interfaces.<br />
If a greater number are required, up to 63 panels can be linked<br />
using a networking card. Access to panel functions is by means<br />
of a secure password. All functions controlled by the keypad,<br />
via a series of user friendly menus with context sensitive help<br />
information. System and luminaire faults can be viewed without<br />
input of password. Panel has printer connection facility and battery<br />
back-up. An on-board alarm is fitted, which is activated when<br />
faults are identified. Alarm can be muted using keypad.<br />
Panel is used to facilitate following functions:<br />
- Set up test types and times<br />
- Set up testing groups<br />
- Initiate manual tests<br />
- Display real time current/voltage of single luminaire<br />
- Print test results (remote printer)<br />
In addition, LED indicators display the following status:<br />
- Power on<br />
- Emergency mode<br />
- General fault<br />
- System fault<br />
- Test in progress<br />
- Disable luminaire groups<br />
- Fault indication in luminaire groups 1-16<br />
DIMENSIONS<br />
H<br />
D<br />
L<br />
MUTE SCROLL<br />
BUZZER<br />
1 2 3 4 5<br />
H (mm) L (mm) D (mm)<br />
270 332 90