Download datasheet - Draka Communications - Prysmian Group
Download datasheet - Draka Communications - Prysmian Group
Download datasheet - Draka Communications - Prysmian Group
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
J-H(St)H Fire alarm cable<br />
n x 2 x 0.8 mm Bd<br />
Halogen-free, flame-retardant, low-smoke internal<br />
telecommunication cable with electrostatic screen, unitstranded<br />
Specification DIN VDE 0815<br />
Fire test DIN EN 50266-2-4 (according to IEC 332-3<br />
test type C)<br />
Application<br />
Used as installations cable in local networks, especially for fixed indoor installations in fire protected areas.<br />
Not admissible as power installation cable and not allowed for laying in ground.<br />
Colour Coding, Marking<br />
LINKING THE FUTURE<br />
www.prysmiangroup.com<br />
© 2009<br />
Changes reserved according<br />
to technical progress.<br />
Quad: Marking of cores of star quads with black rings according to DIN VDE 0815.<br />
Basic unit: 5 main colours of star quad: red, green, grey, yellow, white. Marking units of basic and main units are<br />
marked with a red open helix, all others have a white helix.<br />
Construction<br />
J-H(St)H Fire alarm<br />
cable<br />
Ring marking of quads<br />
Conductor copper, solid, 0.8 mm, soft annealed<br />
Insulation halogen-free, flame-retardant compound (H), ring marking of cores according to DIN VDE 0815<br />
Twisting quads in unit-stranding (SZ-stranding)<br />
Cable core wrapping at least one layer of plastic tape<br />
Screen electrostatic screen; tinned copper drain wire of diameter 0.6 or 0.8 mm galvanically connected<br />
with the laminated aluminium/PETP tape<br />
Principle drawing<br />
J-H(St)H Fire alarm cable<br />
50x2x0.8 Bd<br />
Outer sheath halogen-free, flame-retardant compound (H), colour red and with printing “BRANDMELDEKABEL”<br />
2009_75e<br />
Version 1 | 14.09.2009<br />
Page 1 of 3
J-H(St)H Fire alarm cable<br />
n x 2 x 0.8 mm Bd<br />
Mechanical and Thermal Properties<br />
Admissible bending radius 7.5 x outer cable diameter<br />
Temperature range during operation - 30°C to + 70°C<br />
LINKING THE FUTURE<br />
during installation - 5°C to + 50°C<br />
Electrical Properties at 20°C ± 5°C<br />
Conductor diameter mm 0.8<br />
Conductor loop resistance /km ≤ 73.2<br />
Insulation resistance Mxkm ≥ 100<br />
Mutual capacitance at 800 Hz nF/km ≤ 120*<br />
Capacitance unbalance at 800 Hz<br />
k1 pF/100 m ≤ 300**<br />
k9-12 pF/100 m ≤ 100***<br />
Test voltage at 50 Hz – 1 min<br />
core/core V 800<br />
core/screen V 800<br />
Operating peak voltage V 300<br />
*<br />
For cable with 4 pairs mentioned value may not exceed 20 %.<br />
** 20% of the values , at least however 1 value may amount to 500 pF.<br />
*** 10% of the values, at least however 4 values (relations), may amount to 300 pF.<br />
www.prysmiangroup.com<br />
2009_75e<br />
Version 1 | 14.09.2009<br />
Page 2 of 3
J-H(St)H Fire alarm cable<br />
n x 2 x 0.8 mm Bd<br />
Additional Properties<br />
Product<br />
code Dimension<br />
Outer<br />
diameter<br />
ca.<br />
LINKING THE FUTURE<br />
Cable<br />
weight<br />
net<br />
ca.<br />
Standard<br />
supply<br />
length<br />
www.prysmiangroup.com<br />
Drum<br />
size/<br />
flange-Ø<br />
Transport<br />
weight<br />
gross ca.<br />
Copper<br />
content<br />
ca. mm kg/km m kg/drum kg/km<br />
J-H(St)H Fire alarm cable n x 2 x 0.8 Bd<br />
1019171-*… 2 x 7.0 65 1000 S6** 71 25<br />
1019174-*… 4 x 10.4 112 1000 NG10/ 1000 192 46<br />
1019175-*… 6 x 10.6 135 1000 NG10/ 1000 215 65<br />
1019176-*… 10 x 12.6 197 1000 NG10/ 1000 277 106<br />
on request 20 x 16.3 335 1000 NG12/ 1200 460 206<br />
on request 30 x 19.6 485 1000 NG14/ 1400 615 306<br />
on request 40 x 21.9 616 1000 NG14/ 1400 746 407<br />
on request 50 x 24 743 1000 NG14/ 1400 843 508<br />
on request 60 x 26,2 894 1000 NG16/ 1600 1099 608<br />
on request 80 x 30 1174 1000 NG16/ 1600 1379 809<br />
on request 100 x 33 1428 1000 NG18/ 1800 1808 1010<br />
*... Delivery length and packaging code, for example at 1000m lengths: 01000DX<br />
S6**, S7** ply wood drums, ≥NG10…drum one way (solid wood)<br />
[PRODUCT CODE TABLE]<br />
© PRYSMIAN GROUP 2009, All Rights Reserved<br />
All sizes and values without tolerances are reference values. Specifications are for product as supplied by <strong>Prysmian</strong> <strong>Group</strong>: any<br />
modification or alteration afterwards of product may give different result.<br />
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without<br />
the written consent of <strong>Prysmian</strong> <strong>Group</strong>. The information is believed to be correct at the time of issue. <strong>Prysmian</strong> <strong>Group</strong> reserves the right to<br />
amend this specification without prior notice. This specification is not contractually valid unless specifically authorised by <strong>Prysmian</strong> <strong>Group</strong>.<br />
2009_75e<br />
Version 1 | 14.09.2009<br />