Instrumentation Cable<br />
RE-2Y(St)Y/H PimF nx(2+1)x0.5 mm²<br />
BS 5308 type<br />
PE-insulated instrumentation cable, pair shielding, overall<br />
shielded, PVC or halogen free outer sheath<br />
According to EN 50288-7; based on BS 5308: Part 1: table 7:<br />
1986<br />
Application<br />
LINKING THE FUTURE<br />
www.prysmiangroup.com<br />
© 2008<br />
Changes reserved<br />
according<br />
to technical progress<br />
Used as instrumentation cables, especially in petrochemical industry, not suitable for outdoor laying. Optional available<br />
with light blue outer sheath for intrinsically safe use in explosive areas.<br />
Colour Coding<br />
Pair colouring a-wire: black b-wire: blue<br />
Pair identification each shielded pair is identified by a number foil, numbers starting from 1 to (final number of<br />
pairs)<br />
Principle drawing<br />
Instrumentation Cable<br />
RE-2Y(St)Y PimF<br />
15x2x0.5 mm²<br />
2008_51e<br />
Version 1 | 04.11.2008<br />
Page 1 of 3
Instrumentation Cable<br />
RE-2Y(St)Y/H PimF nx(2+1)x0.5 mm²<br />
BS 5308 type<br />
Construction<br />
RE-2Y(St)Y PimF PimF = pairs in metal foil<br />
Conductor copper, stranded, 7x0.29 mm = 0.5 mm², soft annealed<br />
Insulation PE (2Y), colours see colour coding above<br />
Twisting cores twisted to pairs (SZ-stranding)<br />
Pair shielding each pair shielded with stranded drain wire 0.5 mm² tinned (7x0.29 mm), Al-PETP foil (metal<br />
LINKING THE FUTURE<br />
side inward), number foil, self adhesive foil<br />
Stranding n shielded pairs twisted to group (SZ-stranding), groups twisted to cable core (SZ-stranding),<br />
Cable core wrapping at least one plastic tape<br />
see table additional properties for grouping details<br />
Drain wire copper, stranded, tinned, 0.5 mm² (7x0.29 mm), soft annealed<br />
Shielding Al-PETP foil, metal side facing inward, with overlap, longitudinally applied, fixed with two helixes<br />
Outer sheath PVC (Y) or halogen free material (H), black (or light blue for intrinsically safe),<br />
with inkjet marking: DRAKA EN 50288-7 m<br />
Mechanical and Thermal Properties<br />
Temperature range during operation - 30°C to + 60°C<br />
during installation - 5°C to + 60°C<br />
Electrical Properties at 20°C ± 5°C<br />
Conductor size mm 7x0.29<br />
Conductor cross section mm² 0.5<br />
Conductor resistance at 20°C Ω/km ≤ 36.7<br />
Insulation resistance GΩxkm ≥ 5<br />
Mutual capacitance at 1 kHz pF/m ≤ 115<br />
Capacitance unbalance at 1 kHz pair-to-<br />
pair<br />
AC test voltage for 1 minute<br />
pF/250 m<br />
≤ 250<br />
conductor/conductor V 1000<br />
conductor/screen V 1000<br />
www.prysmiangroup.com<br />
2008_51e<br />
Version 1 | 04.11.2008<br />
Page 2 of 3
Instrumentation Cable<br />
RE-2Y(St)Y/H PimF nx(2+1)x0.5 mm²<br />
BS 5308 type<br />
Additional Properties<br />
Dimensi<br />
on<br />
Outer<br />
diameter<br />
nominal<br />
Cable<br />
weight<br />
net<br />
LINKING THE FUTURE<br />
Standar<br />
d<br />
supply<br />
length<br />
Drum<br />
size<br />
flange-Ø<br />
Transport<br />
weight<br />
gross,<br />
lagged<br />
www.prysmiangroup.com<br />
Copper<br />
content<br />
mm kg/km m mm kg/drum kg/km<br />
<strong>Group</strong>ing of pairs<br />
Instrumentation Cable n x 2 x 0.5 mm²<br />
1 x 3.5 40 1000 500 45 19 (1pr)<br />
2 x 8.5 80 1000 600 85 33 (2pr)<br />
4 x 9.5 120 1000 700 130 61 (4pr)<br />
8 x 14 215 1000 1000 300 116 (2pr)(2pr)(2pr)(2pr)<br />
10 x 15.5 260 1000 1200 390 144 (4pr)(3pr)(3pr)<br />
12 x 16 300 1000 1200 430 172 (4pr)(4pr)(4pr)<br />
15 x 18.5 380 1000 1200 510 214 (4pr)(4pr)(4pr)(3pr)<br />
16 x 19 400 1000 1200 530 227 (4pr)(4pr)(4pr)(4pr)<br />
20 x 20.5 490 1000 1400 680 283 (4pr)(4pr)(4pr)(4pr)(4pr)<br />
24 x 22 560 1000 1400 760 339 (4pr)(4pr)(4pr)(4pr)(4pr)(4pr)<br />
[PRODUCT CODE TABLE]<br />
© PRYSMIAN GROUP 2008, All Rights Reserved<br />
All sizes and values without tolerances are reference values. Specifications are for product as supplied by <strong>Prysmian</strong> <strong>Group</strong>: any<br />
modification or alteration afterwards of product may give different result.<br />
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without<br />
the written consent of <strong>Prysmian</strong> <strong>Group</strong>. The information is believed to be correct at the time of issue. <strong>Prysmian</strong> <strong>Group</strong> reserves the right to<br />
amend this specification without prior notice. This specification is not contractually valid unless specifically authorised by <strong>Prysmian</strong> <strong>Group</strong>.<br />
2008_51e<br />