Technical data<br />
Rectifier units<br />
AFE rectifier/regenerative units<br />
<strong>Siemens</strong> DA 65.11 · 2003/2004<br />
Compact<br />
PLUS units<br />
Compact and chassis units<br />
Rated voltage<br />
Line voltage 3-ph. 380 V AC (–20 %) to 460 V AC (+5 %)<br />
Output voltage<br />
Operating range of the DC link voltage control<br />
Factory setting:<br />
600 V DC for compact units<br />
632 V DC for chassis units<br />
Minimum: 1.5-fold of the rms value of the applied voltage<br />
Maximum: 740 V<br />
Rated frequency<br />
Line frequency 50/60 Hz (±10 %)<br />
Rectifier/regenerative output<br />
Load class II to EN 60 146-1-1<br />
6.8 to 250 kW<br />
Base load current 0.91 x rated input current (from/to the line supply)<br />
Short-time current 1.36 x rated input current for 60 s<br />
1.6 x rated input current for 30 s for units up to enclosure size G<br />
Cycle time 300 s<br />
Supply power factor<br />
fundamental<br />
overall<br />
Efficiency > 0.98<br />
1 (factory setting)<br />
> 0.99<br />
1) With a V D = 2 % commutating reactor. 2) Where there is a fast changeover from<br />
motoring mode to generating mode,<br />
a deadtime of 15 ms is to be taken into<br />
account.<br />
Compact and<br />
chassis units<br />
Rated voltage<br />
Compact PLUS units Compact and chassis units<br />
Line voltage 3-ph. 380 V AC (–15 %) to 480 V AC (+10 %) 3-ph. 380 V AC (–15 %) to 480 V AC (+10 %)<br />
Output voltage<br />
Rated frequency<br />
510 V DC (–15 %) to 650 V DC (+10 %) 510 V DC (–15 %) to 650 V DC (+10 %)<br />
Line frequency 50/60 Hz (±6 %) 50/60 Hz (±6 %)<br />
Rated motor output<br />
Load class II to EN 60 146-1-1<br />
15 kW, 50 kW, 100 kW 15 kW to 250 kW<br />
Base load current 0.91 x rated output current 0.91 x rated output current<br />
Short-time current 3 x rated output current –<br />
Short-time duration 250 ms –<br />
Short-time cycle 1 s at 15 kW, 12 s at 50 kW and 100 kW –<br />
Overload current 1.6 x rated output current for max. 30 s 1.36 x rated output current<br />
Overload duration 30 s 60 s (20 % of the cycle time)<br />
Overload cycle time<br />
Power factor<br />
300 s 300 s<br />
1 )<br />
fundamental<br />
0.98<br />
0.98<br />
overall<br />
0.93 to 0.96<br />
0.93 to 0.96<br />
Efficiency 0.995 0.99 to 0.995<br />
Rectifier/regenerative units 2)<br />
Compact and chassis units<br />
Rated voltage<br />
Line voltage<br />
3-ph. 380 V AC (–15 %) to 480 V AC (+10 %)<br />
motoring<br />
Line voltage<br />
3-ph. 455 V AC (–15 %) to 576 V AC (+10 %)<br />
regenerating<br />
Output voltage 510 V DC (–15 %) to 650 V DC (+10 %)<br />
Rated frequency<br />
Line frequency 50/60 Hz (±6 %)<br />
Rated motor output 7.5 kW to 250 kW<br />
Load class II to EN 60 146-1-1<br />
Base load current 0.91 x rated output current<br />
Short-time current 1.36 x rated output current<br />
Cycle time 300 s<br />
Overload duration 60 s (20 % of the cycle time)<br />
Power factor, motoring<br />
fundamental<br />
overall<br />
0.98<br />
0.93 to 0.96<br />
Efficiency 0.99 to 0.995