19.08.2013 Views

SIMOVERT MASTERDRIVES Motion Control - Siemens

SIMOVERT MASTERDRIVES Motion Control - Siemens

SIMOVERT MASTERDRIVES Motion Control - Siemens

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2<br />

2/4<br />

<strong>SIMOVERT</strong> <strong>MASTERDRIVES</strong> <strong>Motion</strong> <strong>Control</strong><br />

Technical data<br />

Rectifier units<br />

AFE rectifier/regenerative units<br />

<strong>Siemens</strong> DA 65.11 · 2003/2004<br />

Compact<br />

PLUS units<br />

Compact and chassis units<br />

Rated voltage<br />

Line voltage 3-ph. 380 V AC (–20 %) to 460 V AC (+5 %)<br />

Output voltage<br />

Operating range of the DC link voltage control<br />

Factory setting:<br />

600 V DC for compact units<br />

632 V DC for chassis units<br />

Minimum: 1.5-fold of the rms value of the applied voltage<br />

Maximum: 740 V<br />

Rated frequency<br />

Line frequency 50/60 Hz (±10 %)<br />

Rectifier/regenerative output<br />

Load class II to EN 60 146-1-1<br />

6.8 to 250 kW<br />

Base load current 0.91 x rated input current (from/to the line supply)<br />

Short-time current 1.36 x rated input current for 60 s<br />

1.6 x rated input current for 30 s for units up to enclosure size G<br />

Cycle time 300 s<br />

Supply power factor<br />

fundamental<br />

overall<br />

Efficiency > 0.98<br />

1 (factory setting)<br />

> 0.99<br />

1) With a V D = 2 % commutating reactor. 2) Where there is a fast changeover from<br />

motoring mode to generating mode,<br />

a deadtime of 15 ms is to be taken into<br />

account.<br />

Compact and<br />

chassis units<br />

Rated voltage<br />

Compact PLUS units Compact and chassis units<br />

Line voltage 3-ph. 380 V AC (–15 %) to 480 V AC (+10 %) 3-ph. 380 V AC (–15 %) to 480 V AC (+10 %)<br />

Output voltage<br />

Rated frequency<br />

510 V DC (–15 %) to 650 V DC (+10 %) 510 V DC (–15 %) to 650 V DC (+10 %)<br />

Line frequency 50/60 Hz (±6 %) 50/60 Hz (±6 %)<br />

Rated motor output<br />

Load class II to EN 60 146-1-1<br />

15 kW, 50 kW, 100 kW 15 kW to 250 kW<br />

Base load current 0.91 x rated output current 0.91 x rated output current<br />

Short-time current 3 x rated output current –<br />

Short-time duration 250 ms –<br />

Short-time cycle 1 s at 15 kW, 12 s at 50 kW and 100 kW –<br />

Overload current 1.6 x rated output current for max. 30 s 1.36 x rated output current<br />

Overload duration 30 s 60 s (20 % of the cycle time)<br />

Overload cycle time<br />

Power factor<br />

300 s 300 s<br />

1 )<br />

fundamental<br />

0.98<br />

0.98<br />

overall<br />

0.93 to 0.96<br />

0.93 to 0.96<br />

Efficiency 0.995 0.99 to 0.995<br />

Rectifier/regenerative units 2)<br />

Compact and chassis units<br />

Rated voltage<br />

Line voltage<br />

3-ph. 380 V AC (–15 %) to 480 V AC (+10 %)<br />

motoring<br />

Line voltage<br />

3-ph. 455 V AC (–15 %) to 576 V AC (+10 %)<br />

regenerating<br />

Output voltage 510 V DC (–15 %) to 650 V DC (+10 %)<br />

Rated frequency<br />

Line frequency 50/60 Hz (±6 %)<br />

Rated motor output 7.5 kW to 250 kW<br />

Load class II to EN 60 146-1-1<br />

Base load current 0.91 x rated output current<br />

Short-time current 1.36 x rated output current<br />

Cycle time 300 s<br />

Overload duration 60 s (20 % of the cycle time)<br />

Power factor, motoring<br />

fundamental<br />

overall<br />

0.98<br />

0.93 to 0.96<br />

Efficiency 0.99 to 0.995