Specifications Section 1-2<br />

Output terminal (service<br />

supply)<br />

RUN output<br />

(See note 2.)<br />

Item Specification<br />

Provided only on the PA204S. (See note 4.)<br />

0.3 A or less current consumption by 24-V DC<br />

load: 24 V DC is +17% to −11%<br />

0.3 A current consumption by 24 V DC load:<br />

24 V DC is +10% to −11% (lot No. 0197 or later)<br />

Provided only on the PA204S. (See note 5.)<br />

Contact form: SPST-NO<br />

Switching capacity:<br />

250 V AC, 2 A (resistive load)<br />

250 V AC, 0.5 A (induction load: 24 V DC, 2 A)<br />

None<br />

Contact configuration: SPST-NO<br />

Switch capacity: 240 V AC, 2A (resistive load),<br />

120 V AC, 0.5 A (induction load)<br />

24 V DC, 2A (resistive load)<br />

24 V DC, 2 A (induction load)<br />

Insulation resistance 20 MW min. (at 500 V DC) between AC external and GR terminals (See note 1.)<br />

Dielectric strength 2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals (See note 1.)<br />

Leakage current: 10 mA max.<br />

1,000 V AC 50/60 Hz for 1 min between DC external and GR terminals (See note 1.)<br />

Leakage current: 10 mA max.<br />

Noise immunity 2 kV on power supply line (conforming to IEC61000-4-4)<br />

Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for<br />

80 minutes (Time coefficient: 8 minutes × coefficient factor 10 = total time 80 min.) CPU Unit<br />

mounted to a DIN track: 2 to 55 Hz, 2.94 m/s2 in X, Y, and Z directions for 20 minutes<br />

Shock resistance 147 m/s 2 3 times each in X, Y, and Z directions (according to JIS C0041)<br />

Ambient operating 0 to 55°C<br />

temperature<br />

Ambient operating 10% to 90% (with no condensation)<br />

humidity<br />

Atmosphere Must be free from corrosive gases.<br />

Ambient storage −20 to 75°C (excluding battery)<br />

temperature<br />

Grounding Less than 100 Ω<br />

Enclosure Mounted in a panel.<br />

Weight Refer to Section 3.<br />

CPU Rack dimen- 2-slot Rack: 198.5 ×157×123 mm (W×H×D) (See note 3.)<br />

sions (mm)<br />

3-slot Rack: 260 × 130 × 123 mm (W×H×D) (See note 3.)<br />

5-slot Rack: 330 × 130 × 123 mm (W×H×D) (See note 3.)<br />

8-slot Rack: 435 × 130 × 123 mm (W×H×D) (See note 3.)<br />

10-slot Rack: 505 × 130 × 123 mm (W×H×D) (See note 3.)<br />

Safety standards Conforms to cULus and EC Directives.<br />

Note (1) Disconnect the Power Supply Unit's LG terminal from the GR terminal<br />

when testing insulation and dielectric strength. Testing the insulation and<br />

dielectric strength with the LG terminal and the GR terminals connected<br />

will damage internal circuits in the CPU Unit.<br />

(2) Supported only when mounted to CPU Backplane.<br />

(3) The depth is 153 mm for the C200HW-PA209R Power Supply Unit.<br />

(4) The C200HW-PA204 and C200HW-PA204R do not have an output terminal.<br />

(5) The C200HW-PA204 and C200HW-PA204S do not have a RUN output.<br />