Battery Management System for Telecom Applications ... - Ericom
Battery Management System for Telecom Applications ... - Ericom
Battery Management System for Telecom Applications ... - Ericom
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Why a BMS is Needed?<br />
<strong>Battery</strong> <strong>Management</strong> <strong>System</strong> <strong>for</strong> <strong>Telecom</strong> <strong>Applications</strong><br />
GSM operators prefer 12V VRLA batteries by 4<br />
serial in group to use in 48V DC backup<br />
systems . 4 x 12V batteries <strong>for</strong>ms a ‘’group’’ and<br />
3-4 groups are parallel connected to reach<br />
required Ah capacity<br />
Parallel connections between battery groups<br />
can cause ‘asymmetric’’ charge current<br />
distribution<br />
Telco rectifier systems are designed to charge<br />
one battery group with one current control. It<br />
does not care current distribution between<br />
parallel battery groups. It only controls current<br />
and voltage limitation <strong>for</strong> total Ah capacity.<br />
In real life VRLA batteries cannot be produced<br />
identically. Production differences can effect<br />
battery aging rate and serial / parallel connected<br />
batteries show asymmetrical characteristics <strong>for</strong><br />
a while.<br />
Beatrice Telco-BMS Structure<br />
Small capacity differences between 12V<br />
batteries cause asymmetric internal resistance<br />
behavior during charge and discharge.<br />
Difference increase with cycling and aging. This<br />
situation creates asymmetrical distribution of<br />
charge current and cause exceeding of charge<br />
current limit of battery group (mostly 0,15C).<br />
Charge current out of limits cause faster aging<br />
of battery.<br />
Asymmetrical capacity aging of batteries cause<br />
‘’inter group charging’’ during discharge stage.<br />
Higher voltage (higher SoC) group feeds the<br />
load and ‘’charge’’ other groups. This overloads<br />
the battery group.<br />
All of these problems affects aging parameters<br />
of VRLA batteries and shorten their operation<br />
life<br />
<strong>Ericom</strong> Beatrice has been designed to solve<br />
all of these problems<br />
<strong>Ericom</strong> <strong>Telecom</strong>munication & Energy Technologies Inc.<br />
Adr: Buyukdere Cd. No: 15/A Hur Han B Blok Kat:3 34381 - Sisli / Istanbul / Turkey<br />
Tel: 0212-330-05-40 Fax: 0212-330-05-43 Web: www.ericom.com.tr
BBC x (<strong>Battery</strong> Bank Controller)<br />
Features:<br />
• ‘’Buck’’ topology <strong>for</strong> DC-DC conversion<br />
• 8 Bit PIC microcontroller<br />
• Hall Effect current sensor<br />
• 1-20 A charge current limitation (CC - Constant<br />
Current) 42-54V battery group charge voltage<br />
(default 53.5V) CV (Constant Voltage)<br />
• Temperature compensation parameter <strong>for</strong> each<br />
battery group<br />
• MODBUS derivated text protocol between BBCx<br />
and MPC<br />
• Overcharge and overdischarge protection by<br />
using voltage and temperature measurement of<br />
each 12V VRLA battery.<br />
• <strong>Battery</strong> group isolation in case of fatal failure of a<br />
battery<br />
MPC (Main Process Controller)<br />
Features :<br />
• 8 Bit PIC microcontroller<br />
• Data logging into onboard SD Flash card (8GB)<br />
• Maintenance PC interface via DB9 - RS232<br />
• Proprietary VRLA battery charge algorithms and<br />
SoC / SoH determination methods<br />
• 4 x 4 LED matrix <strong>for</strong> battery state display to<br />
maintenance technician<br />
• GSM/GPRS modem connection via secondary<br />
RS232 port on board<br />
• Remote monitoring and management server<br />
support<br />
Environmental:<br />
Working Temperatures : 0 .. 50 0 C<br />
Relative Humidity: %90 RH<br />
Electrical:<br />
Input Voltage : -42…-56V DC<br />
Output Voltage : -42…-55V DC<br />
Output Current : 0 … 20 A<br />
Physical Dimensions:<br />
9 x 44 x 42 cm (Hx W x D)<br />
19 inch rack compatible, 2U<br />
Weight: 3.5 Kg<br />
<strong>Ericom</strong> <strong>Telecom</strong>munication & Energy Technologies Inc.<br />
Adr: Buyukdere Cd. No: 15/A Hur Han B Blok Kat:3 34381 - Sisli / Istanbul / Turkey<br />