Drive. CT series<br />
2.<br />
CT<br />
Ref.1109<br />
20<br />
Starts per hour<br />
By electronic control: unlimited.<br />
By interrupting the AC supply: ≤ 20<br />
Start up time<br />
This is the time taken from the moment of applying power to the drive, to the drive being ready to<br />
run the motor: Its value is 4 s.<br />
Output frequency / speed range ratio<br />
Open-loop frequency range: 0 to 3.000Hz<br />
Closed-loop speed range: From 0 to 40.000 rpm.<br />
Closed-loop frequency range: 0 to 1250 Hz Limited to 600 Hz for best performance.<br />
Acoustic noise<br />
Maximum pressure level at 1m (dBA)<br />
Max. speed Max. speed<br />
SPMD1403 75 43<br />
SPMC1402 53 43<br />
Overall dimensions<br />
H Height including surface mounting brackets<br />
W Width<br />
D Forward panel projection when surface mounted<br />
F Forward panel projection when through-panel mounted<br />
R Rear panel projection when through-panel mounted<br />
SPMD1403<br />
SPMC1402<br />
Approx. mass<br />
H W D F R<br />
795.5 mm<br />
(31.319 in)<br />
399.1 mm<br />
(15.731 in)<br />
310 mm<br />
(12.205 in)<br />
310 mm<br />
(12.205 in)<br />
kg lb<br />
SPMD1403 42 92.6<br />
SPMC1402 20 44<br />
298 mm<br />
(11.732 in)<br />
298 mm<br />
(11.732 in)<br />
202 mm<br />
(7.953 in)<br />
202 mm<br />
(7.953 in)<br />
≤ 95 mm<br />
(3.740 in)<br />
≤ 95 mm<br />
(3.740 in)<br />
Input current, fuse and cable size ratings<br />
The input current is affected by the supply voltage and impedance.<br />
Typical input current. The values of typical input current are given to aid calculations for power<br />
flow and power loss. These values are stated for a balanced supply.<br />
Maximum continuous input current The values of maximum continuous input current are given<br />
to aid the selection of cables and fuses. These values are stated for the worst case condition with<br />
the unusual combination of stiff supply with bad balance. The value stated for the maximum<br />
continuous input current would only be seen in one of the input phases whereas the current in the<br />
other two phases would be significantly lower. The values of maximum input current are stated for<br />
a supply with a 2% negative phase-sequence imbalance and rated at the maximum supply fault<br />
current given in the table.<br />
Supply fault current used to calculate maximum input currents<br />
Symmetrical fault level<br />
SPMD1403 100 kA<br />
SPMC1402 100 kA<br />
Warning. Fuse protection must be provided at the power input.