106<br />
L <strong>Multicore</strong> <strong>Armoured</strong> <strong>LSZH</strong> (<strong>Copper</strong>)<br />
XLPE/<strong>LSZH</strong>/SWA/<strong>LSZH</strong> (COPPER) BS6724 & IEC60502<br />
<strong>Multicore</strong> plain annealed copper conductor to IEC60228, XLPE insulated to IEC60502/<strong>LSZH</strong> extruded bedded to<br />
IEC60502/ Steel wire armoured to IEC60502/<strong>LSZH</strong> sheathed t0 IEC60502 600/1000 volts grade to BS6724 Fire<br />
performance to IEC60754, flame propagation to IEC60332 & smoke emissions to BSEN61034-2<br />
Applications: Power cable suitable for power networks, where fire & emission of smoke and toxic fumes create a serious<br />
potential threat<br />
TWO CORE: REF 6942 XWL<br />
SIZE<br />
SQ.MM<br />
1.5<br />
2.5<br />
4<br />
6<br />
10<br />
16<br />
25<br />
35<br />
50<br />
70<br />
95<br />
120<br />
150<br />
185<br />
240<br />
300<br />
400<br />
CLASS<br />
OF<br />
CONDUCTOR<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2*<br />
2*<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
RT<br />
OF<br />
INSULATION<br />
0.6<br />
0.7<br />
0.7<br />
0.7<br />
0.7<br />
0.7<br />
0.9<br />
0.9<br />
1.0<br />
1.1<br />
1.1<br />
1.2<br />
1.4<br />
1.6<br />
1.7<br />
1.8<br />
2.0<br />
RT OF<br />
BEDDING<br />
MM<br />
DIAMETER<br />
OVER<br />
BEDDING<br />
MM<br />
Conductor stranding: Class 2 - stranded circular or circular compacted.<br />
6.0<br />
6.8<br />
7.9<br />
9.1<br />
10.9<br />
12.9<br />
16.8<br />
19.3<br />
17.0<br />
20.0<br />
22.7<br />
25.5<br />
28.5<br />
32.1<br />
36.2<br />
40.1<br />
45.2<br />
Operating temperature: Maximum 90°C, Minimum bending 0 °C.<br />
Conductor identification: Brown & Blue<br />
Minimum bending radius: 8 x overall diameter<br />
(Wherever possible, larger installation radi should be used)<br />
DIAMETER<br />
OF<br />
ARMOUR<br />
WIRE<br />
MM<br />
DIAMETER<br />
OVER<br />
ARMOUR<br />
MM<br />
Combustion Characteristics:<br />
Oxygen index: 35% (Temperature index 280°C).<br />
HCL emission 0.5% in accordance with BSEN50267-1Common test methods for cables under<br />
fire conditions. Tests on gases evolved during combustion of materials from cables. Apparatus<br />
BSEN50267-2-1:Common test methods for cables under fire conditions. Tests on gases<br />
evolved during combustion of materials from cables. Procedures. Determination of the amount<br />
of halogen acid gas<br />
Low smoke classification based on 3 metre cube test.<br />
Completed cables comply with the requirements of fire test BSEN50266-1:2001(previously BS4066)<br />
For approximate conductor, armour resistance and percentage of conductivity, refer to technial section<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
1.0<br />
1.2<br />
1.2<br />
1.2<br />
1.4<br />
1.4<br />
1.6<br />
1.6<br />
BATT PART NUMBER & GLAND PART NUMBER TABLE<br />
APPROX<br />
OVERALL<br />
DIAMETER<br />
MM<br />
WEIGHT<br />
KG/KM<br />
For current ratings, refer to Table 4E4A<br />
www.batt.co.uk battindustrial.sales@batt.co.uk<br />
7.7<br />
8.5<br />
9.7<br />
10.7<br />
12.7<br />
14.5<br />
18.4<br />
21.3<br />
19.0<br />
22.0<br />
25.1<br />
27.9<br />
30.9<br />
34.9<br />
39.0<br />
43.3<br />
48.4<br />
SIZE CABLE GLAND GLAND SIZE CABLE GLAND GLAND<br />
SQ.MM PART NO TYPE/SIZE PART NO SQ.MM PART NO TYPE/SIZE PART NO<br />
1.5<br />
2.5<br />
4<br />
6<br />
10<br />
16<br />
25<br />
35<br />
50<br />
55131<br />
55132<br />
55134<br />
55145<br />
55147<br />
55149<br />
56428<br />
56429<br />
56430<br />
BW20S<br />
BW20S<br />
BW20S<br />
BW20S<br />
BW20<br />
BW25<br />
BW25<br />
BW32<br />
BW25<br />
88344<br />
88344<br />
88344<br />
88344<br />
88345<br />
88346<br />
88346<br />
88283<br />
88346<br />
DIAMETER<br />
OVER<br />
LAID UP<br />
CORES<br />
MM<br />
70<br />
95<br />
120<br />
150<br />
185<br />
240<br />
300<br />
400<br />
56431<br />
56432<br />
56433<br />
56434<br />
56435<br />
56436<br />
56437<br />
56438<br />
BW32<br />
BW32<br />
BW40<br />
BW40<br />
BW50S<br />
BW50<br />
BW50<br />
BW63<br />
88283<br />
88283<br />
88284<br />
88284<br />
88349<br />
88350<br />
88350<br />
88352<br />
0.9<br />
0.9<br />
0.9<br />
0.9<br />
0.9<br />
1.25<br />
1.25<br />
1.6<br />
1.6<br />
1.6<br />
2.0<br />
2.0<br />
2.0<br />
2.5<br />
2.5<br />
2.5<br />
2.5<br />
9.6<br />
10.4<br />
11.6<br />
12.6<br />
14.6<br />
17.0<br />
20.9<br />
24.5<br />
22.2<br />
25.2<br />
29.1<br />
31.9<br />
34.9<br />
39.9<br />
44.0<br />
48.3<br />
53.4<br />
12.3<br />
13.6<br />
14.7<br />
15.9<br />
18.0<br />
20.0<br />
24.1<br />
27.9<br />
25.8<br />
29.0<br />
33.1<br />
36.1<br />
39.3<br />
44.7<br />
49.0<br />
53.5<br />
59.0<br />
300<br />
360<br />
420<br />
500<br />
650<br />
910<br />
1060<br />
1480<br />
1800<br />
2300<br />
3170<br />
3800<br />
4500<br />
5800<br />
7280<br />
8750<br />
10700
SIZE<br />
SQ.MM<br />
CLASS<br />
OF<br />
CONDUCTOR<br />
RT OF<br />
BEDDING<br />
MM<br />
<strong>Multicore</strong> <strong>Armoured</strong> <strong>LSZH</strong> (<strong>Copper</strong>)<br />
XLPE/<strong>LSZH</strong>/SWA/<strong>LSZH</strong> (COPPER) BS6724 & IEC60502<br />
<strong>Multicore</strong> plain annealed copper conductor to IEC60228, XLPE insulated to IEC60502/<strong>LSZH</strong> extruded<br />
bedded to IEC60502/ Steel wire armoured to IEC60502/<strong>LSZH</strong> sheathed to IEC60502 600/1000 volts<br />
grade to BS6724 Fire performance to IEC60754, flame propagation to IEC60332 & smoke emissions to<br />
BSEN61034-2<br />
Applications: Power cable suitable for power networks, where fire & emission of smoke and toxic fumes<br />
create a serious potential threat<br />
THREE CORE: REF 6943 XWL<br />
1.5<br />
2.5<br />
4<br />
6<br />
10<br />
16<br />
25<br />
35<br />
50<br />
70<br />
95<br />
120<br />
150<br />
185<br />
240<br />
300<br />
400<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2 2*<br />
2*<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
1.0<br />
1.0<br />
1.2<br />
1.2<br />
1.4<br />
1.4<br />
1.4<br />
1.6<br />
1.6<br />
FOUR CORE: REF 6944 XWL<br />
SIZE<br />
SQ.MM<br />
1.5<br />
2.5<br />
4<br />
6<br />
10<br />
16<br />
25<br />
35<br />
50<br />
70<br />
95<br />
120<br />
150<br />
185<br />
240<br />
300<br />
400<br />
CLASS<br />
OF<br />
CONDUCTOR<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2*<br />
2*<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
2S<br />
RT OF<br />
BEDDING<br />
MM<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
1.0<br />
1.2<br />
1.2<br />
1.4<br />
1.4<br />
1.4<br />
1.6<br />
1.6<br />
1.8<br />
DIAMETER<br />
OVER<br />
BEDDING<br />
MM<br />
8.2<br />
9.1<br />
10.4<br />
11.5<br />
13.7<br />
15.5<br />
20.1<br />
22.8<br />
21.7<br />
25.2<br />
28.8<br />
32.0<br />
35.9<br />
40.0<br />
44.9<br />
49.8<br />
55.4<br />
DIAMETER<br />
OVER<br />
BEDDING<br />
MM<br />
9.0<br />
10.0<br />
11.5<br />
12.7<br />
15.1<br />
17.2<br />
22.3<br />
25.3<br />
25.0<br />
29.5<br />
33.3<br />
37.5<br />
41.6<br />
46.4<br />
52.6<br />
58.0<br />
64.8<br />
DIAMETER<br />
OF<br />
ARMOUR<br />
WIRE<br />
MM<br />
0.9<br />
0.9<br />
0.9<br />
0.9<br />
1.25<br />
1.25<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
2.0<br />
2.0<br />
2.5<br />
2.5<br />
2.5<br />
2.5<br />
2.5<br />
DIAMETER<br />
OF<br />
ARMOUR<br />
WIRE<br />
MM<br />
0.9<br />
0.9<br />
0.9<br />
1.25<br />
1.25<br />
1.25<br />
1.6<br />
1.6<br />
1.6<br />
2.0<br />
2.0<br />
2.5<br />
2.5<br />
2.5<br />
2.5<br />
2.5<br />
3.15<br />
DIAMETER<br />
OVER<br />
ARMOUR<br />
MM<br />
APPROX<br />
OVERALL<br />
DIAMETER<br />
MM<br />
WEIGHT<br />
KG/KM<br />
55151<br />
55154<br />
55155<br />
55159<br />
55160<br />
55161<br />
56474<br />
56475<br />
56476<br />
56477<br />
56478<br />
56479<br />
56480<br />
56481<br />
56482<br />
56483<br />
56484<br />
BW<br />
INDOOR<br />
GLAND<br />
SIZE<br />
GLAND<br />
KIT<br />
PART<br />
NUMBER<br />
www.batt.co.uk battindustrial.sales@batt.co.uk<br />
10.1<br />
11.0<br />
12.3<br />
13.4<br />
16.4<br />
18.0<br />
23.3<br />
26.0<br />
24.9<br />
28.4<br />
32.8<br />
36.0<br />
40.9<br />
45.0<br />
49.9<br />
54.8<br />
60.6<br />
DIAMETER<br />
OVER<br />
ARMOUR<br />
MM<br />
10.9<br />
11.9<br />
13.4<br />
15.3<br />
17.6<br />
19.7<br />
25.5<br />
28.5<br />
28.2<br />
33.5<br />
37.3<br />
42.5<br />
46.6<br />
51.4<br />
57.6<br />
63.0<br />
71.3<br />
12.8<br />
14.1<br />
15.3<br />
16.6<br />
19.5<br />
21.2<br />
26.7<br />
29.6<br />
28.5<br />
32.2<br />
37.0<br />
40.4<br />
45.5<br />
49.8<br />
55.1<br />
60.2<br />
66.6<br />
APPROX<br />
OVERALL<br />
DIAMETER<br />
MM<br />
13.5<br />
15.0<br />
16.4<br />
18.7<br />
21.1<br />
22.9<br />
28.9<br />
32.1<br />
32.0<br />
37.7<br />
41.7<br />
47.1<br />
51.4<br />
56.6<br />
63.0<br />
68.8<br />
78.1<br />
341<br />
405<br />
495<br />
600<br />
900<br />
1080<br />
1750<br />
2100<br />
2350<br />
3150<br />
4300<br />
5250<br />
6720<br />
8040<br />
10150<br />
12320<br />
15090<br />
WEIGHT<br />
KG/KM<br />
390<br />
465<br />
579<br />
820<br />
1090<br />
1400<br />
2100<br />
2580<br />
3000<br />
4300<br />
5510<br />
7150<br />
8500<br />
10300<br />
13000<br />
15750<br />
20450<br />
BATT<br />
CABLES<br />
PART<br />
NUMBER<br />
BATT<br />
CABLES<br />
PART<br />
NUMBER<br />
55162<br />
55175<br />
55193<br />
55194<br />
55195<br />
55196<br />
56496<br />
56497<br />
56498<br />
56499<br />
56500<br />
56501<br />
56502<br />
56503<br />
56504<br />
56505<br />
56506<br />
20S<br />
20S<br />
20S<br />
20<br />
20<br />
25<br />
25<br />
32<br />
32<br />
32<br />
40<br />
40<br />
50S<br />
50<br />
63<br />
63<br />
75S<br />
BW<br />
INDOOR<br />
GLAND<br />
SIZE<br />
20S<br />
20S<br />
20<br />
20<br />
25<br />
25<br />
32<br />
32<br />
32<br />
40<br />
50S<br />
50<br />
50<br />
63<br />
63<br />
75S<br />
75<br />
88344<br />
88344<br />
88344<br />
88345<br />
88345<br />
88346<br />
88346<br />
88283<br />
88283<br />
88283<br />
88284<br />
88284<br />
88349<br />
88350<br />
88352<br />
88352<br />
88354<br />
GLAND<br />
KIT<br />
PART<br />
NUMBER<br />
88344<br />
88344<br />
88345<br />
88345<br />
88346<br />
88346<br />
88283<br />
88283<br />
88283<br />
88284<br />
88349<br />
88350<br />
88350<br />
88352<br />
88352<br />
88353<br />
88354<br />
L<br />
107
108<br />
L <strong>Multicore</strong> <strong>Armoured</strong> <strong>LSZH</strong> (<strong>Copper</strong>)<br />
XLPE/<strong>LSZH</strong>/SWA/<strong>LSZH</strong> (COPPER) BS6724 & IEC60502<br />
<strong>Multicore</strong> plain annealed copper conductor to IEC60228, XLPE insulated to IEC60502/<strong>LSZH</strong> extruded bedded to<br />
IEC60502/ Steel wire armoured to IEC60502/<strong>LSZH</strong> sheathed to IEC60502 600/1000 volts grade to BS6724 Fire<br />
performance to IEC60754, flame propagation to IEC60332 & smoke emissions to BSEN61034-2<br />
Applications: Power cable suitable for power networks, where fire & emission of smoke and toxic fumes create a<br />
serious potential threat<br />
FIVE CORE: REF 6945 XWL<br />
SIZE<br />
SQ.MM<br />
1.5<br />
2.5<br />
4<br />
6<br />
10<br />
16<br />
25<br />
CLASS<br />
OF<br />
CONDUCTOR<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2<br />
RT OF<br />
BEDDING<br />
MM<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
1.0<br />
SIX CORE: REF 6946 XWL<br />
1.5<br />
2.5<br />
4<br />
6<br />
10<br />
16<br />
25<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
1.0<br />
SEVEN CORE: REF 6947 XWL<br />
1.5<br />
2.5<br />
4<br />
6<br />
10<br />
16<br />
2<br />
2<br />
2<br />
2<br />
2<br />
2<br />
0.8<br />
0.8<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
TEN CORE: REF 694/10 XWL<br />
1.5<br />
2.5<br />
4<br />
6<br />
2<br />
2<br />
2<br />
2<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
DIAMETER<br />
OVER<br />
BEDDING<br />
MM<br />
9.9<br />
11.0<br />
12.7<br />
14.0<br />
17.1<br />
19.8<br />
24.5<br />
10.9<br />
12.1<br />
13.9<br />
15.4<br />
18.8<br />
21.8<br />
26.9<br />
10.9<br />
12.1<br />
13.9<br />
15.4<br />
18.8<br />
21.8<br />
13.9<br />
15.5<br />
18.3<br />
20.3<br />
TWELVE CORE: REF 694/12 XWL<br />
1.5<br />
2.5<br />
4<br />
6<br />
2<br />
2<br />
2<br />
2<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
14.3<br />
16.0<br />
18.9<br />
21.0<br />
SIXTEEN CORE: REF 694/16 XWL<br />
1.5<br />
2.5<br />
4<br />
6<br />
2<br />
2<br />
2<br />
2<br />
0.8<br />
0.8<br />
1.0<br />
1.0<br />
16.0<br />
18.2<br />
22.1<br />
23.4<br />
DIAMETER<br />
OF<br />
ARMOUR<br />
WIRE<br />
MM<br />
0.9<br />
0.9<br />
1.25<br />
1.25<br />
1.25<br />
1.6<br />
1.6<br />
0.9<br />
0.9<br />
0.9<br />
1.25<br />
1.6<br />
1.6<br />
1.6<br />
0.9<br />
0.9<br />
1.25<br />
1.25<br />
1.25<br />
1.6<br />
1.25<br />
1.25<br />
1.6<br />
1.6<br />
1.25<br />
1.25<br />
1.6<br />
1.6<br />
1.25<br />
1.6<br />
1.6<br />
1.6<br />
DIAMETER<br />
OVER<br />
ARMOUR<br />
MM<br />
11.8<br />
12.9<br />
15.3<br />
16.6<br />
19.7<br />
23.1<br />
27.8<br />
12.8<br />
14.0<br />
16.5<br />
18.0<br />
22.1<br />
25.1<br />
30.2<br />
12.8<br />
14.0<br />
16.5<br />
18.0<br />
22.1<br />
25.1<br />
16.5<br />
18.1<br />
21.6<br />
23.6<br />
16.9<br />
18.6<br />
22.2<br />
24.3<br />
18.6<br />
21.5<br />
25.4<br />
26.7<br />
APPROX<br />
OVERALL<br />
DIAMETER<br />
MM<br />
WEIGHT<br />
KG/KM<br />
55158<br />
55507<br />
55509<br />
55512<br />
55478<br />
55203<br />
56214<br />
BW<br />
INDOOR<br />
GLAND<br />
SIZE<br />
GLAND<br />
KIT<br />
PART<br />
NUMBER<br />
www.batt.co.uk battindustrial.sales@batt.co.uk<br />
14.2<br />
16.0<br />
18.4<br />
19.7<br />
23.2<br />
26.6<br />
31.7<br />
15.2<br />
17.1<br />
19.7<br />
21.3<br />
25.6<br />
28.8<br />
34.1<br />
15.2<br />
17.1<br />
19.7<br />
21.3<br />
25.6<br />
28.8<br />
19.8<br />
21.4<br />
25.1<br />
27.3<br />
19.4<br />
22.4<br />
25.7<br />
28.0<br />
21.9<br />
25.0<br />
29.1<br />
30.4<br />
433<br />
530<br />
775<br />
929<br />
1300<br />
1880<br />
2670<br />
497<br />
609<br />
886<br />
1070<br />
1650<br />
2190<br />
3090<br />
506<br />
618<br />
907<br />
1110<br />
1720<br />
2300<br />
812<br />
989<br />
1410<br />
1680<br />
854<br />
1080<br />
1550<br />
1920<br />
1020<br />
1430<br />
1950<br />
2300<br />
BATT<br />
CABLES<br />
PART<br />
NUMBER<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
55157<br />
55364<br />
55510<br />
55052<br />
55137<br />
55167<br />
55208<br />
55166<br />
55352<br />
55511<br />
-<br />
-<br />
-<br />
-<br />
20S<br />
20<br />
20<br />
25<br />
25<br />
32<br />
32<br />
20S<br />
20<br />
25<br />
25<br />
25<br />
32<br />
40<br />
20S<br />
20<br />
25<br />
25<br />
25<br />
32<br />
20<br />
25<br />
25<br />
32<br />
25<br />
25<br />
25<br />
32<br />
25<br />
25<br />
32<br />
32<br />
88344<br />
88345<br />
88345<br />
88346<br />
88346<br />
88283<br />
88283<br />
88344<br />
88345<br />
88346<br />
88346<br />
88346<br />
88283<br />
88284<br />
88344<br />
88345<br />
88346<br />
88346<br />
88346<br />
88283<br />
88345<br />
88346<br />
88346<br />
88283<br />
88346<br />
88346<br />
88346<br />
88283<br />
88346<br />
88346<br />
88283<br />
88283
SIZE<br />
SQ.MM<br />
CLASS<br />
OF<br />
CONDUCTOR<br />
RT OF<br />
BEDDING<br />
MM<br />
<strong>Multicore</strong> <strong>Armoured</strong> <strong>LSZH</strong> (<strong>Copper</strong>)<br />
XLPE/<strong>LSZH</strong>/SWA/<strong>LSZH</strong> (COPPER) BS6724 & IEC60502<br />
<strong>Multicore</strong> plain annealed copper conductor to IEC60228, XLPE insulated to IEC60502/<strong>LSZH</strong> extruded bedded to<br />
IEC60502/ Steel wire armoured to IEC60502/<strong>LSZH</strong> sheathed to IEC60502 600/1000 volts grade to BS6724 Fire<br />
performance to IEC60754, flame propagation to IEC60332 & smoke emissions to BSEN61034-2<br />
Applications: Power cable suitable for power networks, where fire & emission of smoke and toxic fumes create a<br />
serious potential threat<br />
NINETEEN CORE: REF 694/16 XWL<br />
1.5<br />
2.5<br />
4<br />
2<br />
2<br />
2<br />
1.0<br />
1.0<br />
1.0<br />
DIAMETER<br />
OVER<br />
BEDDING<br />
MM<br />
17.3<br />
19.3<br />
22.3<br />
TWENTY TWO CORE : REF 694/22 XWL<br />
1.5<br />
2.5<br />
4<br />
2<br />
2<br />
2<br />
1.0<br />
1.0<br />
1.0<br />
20.3<br />
22.7<br />
26.3<br />
DIAMETER<br />
OF<br />
ARMOUR<br />
WIRE<br />
MM<br />
TWENTY SEVEN CORE : REF 694/27 XWL<br />
1.5<br />
2.5<br />
4<br />
2<br />
2<br />
2<br />
1.0<br />
1.0<br />
1.0<br />
20.7<br />
23.2<br />
26.9<br />
THIRTY CORE : REF 694/30 XWL<br />
1.5<br />
2.5<br />
2<br />
2<br />
1.0<br />
1.0<br />
21.5<br />
24.1<br />
THIRTY SEVEN : REF 694/37 XWL<br />
1.5<br />
2.5<br />
2<br />
2<br />
1.0<br />
1.0<br />
FORTY CORE: REF 694/40 XWL<br />
1.5<br />
2.5<br />
2<br />
2<br />
1.0<br />
1.0<br />
23.3<br />
26.1<br />
24.3<br />
27.7<br />
FORTY EIGHT : REF 694/48 XWL<br />
1.5<br />
2.5<br />
2<br />
2<br />
1.0<br />
1.0<br />
26.7<br />
30.4<br />
Operating temperature: Maximum 90°C.<br />
Minimum bending -20°C<br />
Minimum bending radius:<br />
1.5 sq.mm - 16 sq.mm - 8 x overall diameter<br />
25 sq.mm and above - 8 x overall diameter<br />
Conductor identification:<br />
Two Core - Brown & Blue<br />
Three Core - Brown, Black & Grey<br />
Four Core - Brown, Grey, Blue & Black<br />
Five Core & above - Numbered cores.<br />
1.25<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
1.6<br />
2.0<br />
DIAMETER<br />
OVER<br />
ARMOUR<br />
MM<br />
19.9<br />
22.6<br />
25.6<br />
23.6<br />
26.0<br />
29.6<br />
24.0<br />
26.5<br />
30.2<br />
24.8<br />
27.4<br />
26.6<br />
29.4<br />
27.6<br />
31.8<br />
30.0<br />
34.5<br />
APPROX<br />
OVERALL<br />
DIAMETER<br />
MM<br />
22.2<br />
26.1<br />
29.3<br />
26.1<br />
29.7<br />
33.5<br />
26.7<br />
30.2<br />
34.4<br />
28.5<br />
31.3<br />
29.2<br />
33.8<br />
31.5<br />
35.9<br />
33.9<br />
38.8<br />
WEIGHT<br />
KG/KM<br />
1120<br />
1570<br />
2050<br />
1560<br />
1930<br />
2530<br />
1630<br />
2050<br />
2740<br />
1730<br />
2200<br />
1970<br />
2540<br />
2080<br />
2970<br />
2390<br />
3430<br />
BATT<br />
CABLES<br />
PART<br />
NUMBER<br />
55451<br />
55363<br />
55051<br />
-<br />
-<br />
-<br />
55504<br />
55353<br />
55231<br />
-<br />
-<br />
55505<br />
55355<br />
-<br />
-<br />
55506<br />
55508<br />
BW<br />
INDOOR<br />
GLAND<br />
SIZE<br />
25<br />
25<br />
32<br />
32<br />
32<br />
40<br />
32<br />
32<br />
40<br />
32<br />
32<br />
32<br />
40<br />
32<br />
40<br />
40<br />
40<br />
Insulation thickness: Refer to Two core (6942XWL)<br />
GLAND<br />
KIT<br />
PART<br />
NUMBER<br />
88346<br />
88346<br />
88283<br />
88283<br />
88283<br />
88284<br />
88283<br />
88283<br />
88284<br />
88283<br />
88283<br />
88283<br />
88284<br />
88283<br />
88284<br />
88284<br />
88284<br />
Conductor Stranding: Class 2 stranded copper:<br />
2 circular or circular compacted conductors.<br />
2* shaped or circular conductors or circular compacted<br />
conductors.<br />
2S shaped conductors.<br />
(Dimensions and weights based on circular.)<br />
For approximate conductor and armour resistance, and<br />
percentage conductivity, refer to technical section D<br />
Combustion characteristics: HCL emission 0.5% in accordance<br />
with BSEN50267-1Common test methods for cables under fire condi-<br />
For current ratings, refer to Table 4E4A<br />
tions. Tests on gases evolved during combustion of materials from<br />
cables. Apparatus<br />
BW Brass indoor glands.<br />
BSEN50267-2-1:Common test methods for cables under fire condi-<br />
For a full specification of type BW glands, refer to Section C Page194<br />
tions. Tests on gases evolved during combustion of materials from<br />
Other gland types suitable, BW SOLO (LSF), CW (Indoor/Outdoor),<br />
cables. Procedures. Determination of the amount of halogen acid gas<br />
CW SOLO (LSF)E1W (outdoor) & E1FW ( Flameproof) types.<br />
Complete cables comply with the requirements of fire test<br />
For further details on these other gland types, refer to Section C .<br />
www.batt.co.uk BSEN50266-1:2001 (previously BS4066 Part 3)<br />