Contactors 2,2...132 kW<br />

3.1 Version for switching of capacitor bank<br />

8<br />

[kVAr]<br />

Switchable capacitive load of capacitor banks<br />

(Electric durability max. 105 c)<br />

3.2 Auxiliary contacts<br />

Characteristics<br />

Rated insulation<br />

voltage [V]<br />

Conditional thermal<br />

current (free air) [A]<br />

Rated operational<br />

current (free air)<br />

AC-15 [A]<br />

Mechanical<br />

durability<br />

Electrical<br />

durability [c]<br />

Cross-section<br />

of connecting<br />

wires [mm 2]<br />

230 V<br />

400 V<br />

500 V<br />

230 V<br />

400 V<br />

500 V<br />

Size and tightening<br />

torque of terminal<br />

screws<br />

Degree of protection<br />

230 V<br />

400 V<br />

[c]<br />

230 V<br />

400 V<br />

rigid<br />

flexible<br />

with ferrule<br />

4. Thermal relays<br />

DL-K7/c-10<br />

20<br />

6<br />

4<br />

107<br />

106<br />

10<br />

12,5<br />

15<br />

DL-K30/c-11<br />

30<br />

50<br />

60<br />

KS-..<br />

0,75...2,5<br />

M 3<br />

/1,2<br />

IP 00<br />

Hi- , Li-<br />

S..<br />

690<br />

M 3,5 / 1,2 Nm<br />

IP 20<br />

The compensating bimetallic unit ensures the operation<br />

irrespecitively the actual ambient temperature (within<br />

10<br />

6<br />

4<br />

3 × 107<br />

106<br />

2×(1...6)<br />

DL-K15/c-11<br />

PK22E PKB11<br />

12<br />

0,6...2,5 2×(1...6) 0,75...1,5 0,75...1,5<br />

- 1×(0,5...6) - -<br />

4<br />

2<br />

107<br />

0,8×106<br />

106<br />

15<br />

25<br />

30<br />

DL-K37/c-11<br />

35<br />

60<br />

70<br />

12<br />

4<br />

2<br />

5×106<br />

0,8×106<br />

106<br />

1...2,5 1...2,5<br />

Technical data of builit-in auxiliary contacts see in the table 3.<br />

the given wide ambient temperature-range).<br />

The resetting mode (manual or automatic) can be<br />

chosen. The termal relays have a double side-system<br />

which operates the switch-off mechanism, in case of<br />

phase failure. It releases faster: within 2 hours at 15 %<br />

overload. The contacting mechanism contains two<br />

electrically independent NO and NC contacts.<br />

Time-values of release<br />

Contacts<br />

Multiples of<br />

current setting<br />

Trip<br />

class: 10A<br />

10<br />

20<br />

1,05 × I e<br />

1,2 × I e<br />

1,5 × I e<br />

7,2 x I e<br />

4.1 MH type mini thermal relay<br />

The mini thermal relays are produced in the current-range<br />

of 0,11 A...14 A. They can be plugged directly to the lower<br />

terminals of the MK 2- and MK 4- type minicontactors, they<br />

cannot mounted independently to a plate or rail.<br />

4.2 H0-2K type thermal relays<br />

Time of<br />

release [T ]<br />

p<br />

after 2 hours<br />

within 2 hours<br />

within 2 min<br />

2 < Tp < 10 s<br />

4 < Tp < 10 s<br />

6 < Tp < 20 s<br />

95 98<br />

TEST H<br />

RESET<br />

A<br />

96 97<br />

The current-range are avaible from 0,2 A to 32 A covered<br />

by 13 differently set devices. Mounting is possible to 35<br />

mm rail (snap-on) or fixed with three M4 screws to a<br />

mounting plate. The device can be plugged directly to<br />

lower terminals (2T1, 4T2, 6 T3) of DL-K4, DL-K5, DL-K7,<br />

DL-K11, DL-K15, and DL-K18 contactors after removing<br />

the fixing and connecting elements.<br />

The right-side terminal (L3) of the relay should be put to the<br />

correct position before connecting to the contactor.<br />

4.3 H6 type thermal relay with reeveable<br />

current-transformer<br />

Working<br />

condition<br />

cold<br />

warm<br />

warm<br />

cold<br />

The reeveable current-transformer is available between<br />

25 and 250 A, covered by 6 ranges.<br />

It can be used for motorstarter, reversing and star-delta<br />

starter combinations with DL-K15, DL-K18, DL-K22...DL-<br />

K132 contactors.<br />

Cross-section of the reeveable wires accross the current<br />

transformer: 25...51 A 25 mm 2 ( 11,5<br />

mm)<br />

51...250 A 120 mm 2 ( 21,5<br />

mm)<br />

Note: Detailed description of thermal relays can be found<br />

in the catalogue ,,OVERLOAD (THERMAL) RELAYS”<br />