<strong>24</strong>VDC systems using high density 3.1kW rectifiers<br />

> Front access DC connections<br />

> CXCM4 advanced modular controller<br />

> Includes 7ft seismic relay rack<br />

> Optional DC-DC converter upgrade kit<br />

> Integrated system shunt and LVD<br />

<strong>CXPS</strong> <strong>24</strong>-<strong>4T</strong><br />

Standard <strong>24</strong>VDC Power Systems<br />

<strong>CXPS</strong> <strong>24</strong>-<strong>4T</strong> Power<br />

System in 23" 7ft Rack<br />

Argus <strong>CXPS</strong> standard power systems bring proven Cordex technology into a standard integrated system package.<br />

The <strong>CXPS</strong> <strong>24</strong>-<strong>4T</strong> uses high density <strong>24</strong>V-3.1kW rectifiers, the front access two-tier distribution, and the advanced CXCM4<br />

digital controller.<br />

Perfect for wireless applications, the <strong>CXPS</strong> <strong>24</strong>-<strong>4T</strong> provides up to 1430 Amps of <strong>24</strong>VDC power. Power system expansion of<br />

up to 2000 Amps is possible with an optional rectifier shelf expansion kit. An optional DC-DC converter kit is available for<br />

quick integration of Cordex CXDF converters to provide dual <strong>24</strong>V/48V output operation.<br />

The <strong>CXPS</strong> <strong>24</strong>-<strong>4T</strong> is factory wired, tested, and installed in a 7ft seismic rack for quick system installation and turn-up.


<strong>CXPS</strong> <strong>24</strong>-<strong>4T</strong><br />

Part Number: 053-391-20<br />

Features<br />

Configurations:<br />

053-391-20-020 .............System mounted in 44RU Zone 4 seismic rack<br />

Rectifier: ............................Up to 11x <strong>24</strong>V-3.1kW rectifier positions<br />

Distribution: ....................... 58x AM plug-in breaker positions<br />

(expandable to 78x positions)<br />

10x GMT type fuse positions<br />

Shunt<br />

Low voltage disconnect<br />

Controller:..........................CXCM4 modular controller<br />

Electrical<br />

Input:<br />

Voltage: ..........................176 to 312VAC<br />

Current: ........................... 14.6A @ <strong>24</strong>0VAC nominal (per rectifier module)<br />

Frequency: .....................45 to 66Hz<br />

Power Factor: .................>.99<br />

Output:<br />

Voltage: ..........................21 to 29VDC<br />

Current: ........................... S y s t e m : 14 3 0 A<br />

(expandable to 2000A with additional CXRF shelf)<br />

Rectifier: 115A @ 27VDC<br />

Power: ............................. S y s t e m : 3 4 .1k W<br />

(expandable to 48.0kW with additional CXRF shelf)<br />

Rectifier: 3100W max<br />

Environmental<br />

Temperature ...................-40 to +65°C (-40 to 149°F)<br />

-40 to +75°C (-40 to 167°F) de-rated output<br />

Humidity .........................0 to 95% RH non-condensing<br />

Elevation .........................-500 to +2800m (-1640 to 9186ft)<br />

-500 to +4000m (-1640 to 131<strong>24</strong>ft) with de-rated<br />

output<br />

Mechanical<br />

Dimensions:<br />

mm: .................................2134H x 648W x 533D<br />

inches: ............................ 84H x 25.5W x 21D<br />

(-020 configuration - includes relay rack)<br />

Mounting: ..........................23" center mount<br />

Weight: ..............................172kg (379lb)<br />

(includes relay rack, no rectifiers or<br />

breakers included)<br />

Connnections:<br />

Load breaker: ................. H o t : ¼"-20 studs on ⅝" centers<br />

Return: ¼" holes on ⅝" centers<br />

GMT fuses: ..................... Screw terminal 1.31mm 2 to<br />

0.128mm 2 (#16 to #26 AWG)<br />

Battery terminations: ...... ⅜" holes on 1" centers<br />

5x sets per polarity<br />

Rectifier input: ................⅜" holes on 1" centers<br />

Alarm connections: ........Screw terminal 1.31mm 2 to<br />

0.128mm 2 (#16 to #26 AWG)<br />

Access: ...........................Cable: Top<br />

User: Front access after installation<br />

Related Components<br />

010-572-20: ....................Cordex <strong>24</strong>V-3.1kW rectifier<br />

058-736-20:....................Cordex rectifier CXRF <strong>24</strong>-3.1kW expansion<br />

shelf kit<br />

038-257-20: ....................Cordex converter CXDF <strong>24</strong>-48/2kW upgrade kit<br />

<strong>CXPS</strong> <strong>24</strong>-<strong>4T</strong> Internal Distribution<br />

Argus Technologies For more information visit www.argusdcpower.<strong>com</strong><br />

Canada: Burnaby, British Columbia Tel: 604 436 5900 Fax: 604 436 1233 #048-7<strong>24</strong>-10 (04/2008)<br />

United States: Bellingham, Washington Tel: 360 647 2360 Fax: 360 671 4936<br />

Argus Technologies reserves the right to make changes to the products and information contained in this document without notice.<br />

Copyright © 2008 Argus Technologies. All Rights Reserved. Argus ® is a registered trademark of Argus Technologies. member of The <strong>Alpha</strong> Group is a trademark of <strong>Alpha</strong> Technologies.<br />

Cordex is a trademark of Argus Technologies.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!