INSTALLATION<br />
When mounting the valve on a vessel, care should be taken that the float can move freely and is shielded from<br />
incoming liquid by an internal baffle. Overall valve dimensions are shown in figure 2. The valve is typically mounted<br />
to the vessel by a flange on the end of a 3” pipe.<br />
Figure 2: Valve Dimensions<br />
0.8 [19]<br />
1.8 [44]<br />
3" SOCKET WELD<br />
CONNECTION<br />
3" FPT<br />
CONNECTION<br />
3/4" FPT LIQUID INLET<br />
EITHER SIDE OF BODY<br />
2.4 [60]<br />
12.3 [312] (301H)<br />
14.8 [375] (301A)<br />
BAFFLE SHIELDS FLOAT FROM<br />
FALLING LIQUID<br />
5.3 [135]<br />
MANUAL STEM<br />
3.0 [76]<br />
3.8 [95] (301H)<br />
4.0 [102] (301A)<br />
2.8 [71] (301H)<br />
3.3 [83] 301A<br />
7.5 [189] (301H)<br />
10.0 [254] (301A)<br />
13 [330] (301H)<br />
15.5 [394] (301A)<br />
KEEP AREA FREE OF OBSTRUCTIONS<br />
4.3 [108] MAX<br />
PIPE LENGTH<br />
45°<br />
3 4" FPT REMOTE<br />
FEED OUTLET<br />
Ø5.5 [Ø140]<br />
(6) 0.5 [13] HOLES ON<br />
Ø4.5 [114] B.C<br />
FOR 7/16-20 UNF<br />
A typical installation arrangement is shown in<br />
figure 3. Notice the optional shutoff solenoid in<br />
the liquid supply line. When the refrigeration<br />
load is greatly reduced on an individual air unit,<br />
or if fans are shut off, it is advisable to close<br />
the liquid line solenoid ahead of the float valve<br />
in order to stop liquid feed. Otherwise the body<br />
of liquid in the surge drum will flow down into<br />
the coil and the float valve will continue<br />
feeding, thus filling the coil with liquid<br />
refrigerant. Room thermostats can be used to<br />
stop liquid feed to the evaporators.<br />
Figure 3: Typical Installation<br />
GAS<br />
RETURN<br />
SURGE<br />
DRUM<br />
SUCTION<br />
3 4 " LIQUID SUPPLY<br />
SHUT-OFF<br />
SOLENOID<br />
VALVE<br />
<strong>HA</strong>ND<br />
EXPANSION<br />
VALVE<br />
LIQUID<br />
TO COIL<br />
301H SERIES<br />
FLOAT VALVE<br />
500 SERIES<br />
STRAINER<br />
OIL DRAIN<br />
301H-SB11-01 2