INSTALLATION<br />

When mounting the valve on a vessel, care should be taken that the float can move freely and is shielded from<br />

incoming liquid by an internal baffle. Overall valve dimensions are shown in figure 2. The valve is typically mounted<br />

to the vessel by a flange on the end of a 3” pipe.<br />

Figure 2: Valve Dimensions<br />

0.8 [19]<br />

1.8 [44]<br />

3" SOCKET WELD<br />

CONNECTION<br />

3" FPT<br />

CONNECTION<br />

3/4" FPT LIQUID INLET<br />

EITHER SIDE OF BODY<br />

2.4 [60]<br />

12.3 [312] (301H)<br />

14.8 [375] (301A)<br />

BAFFLE SHIELDS FLOAT FROM<br />

FALLING LIQUID<br />

5.3 [135]<br />

MANUAL STEM<br />

3.0 [76]<br />

3.8 [95] (301H)<br />

4.0 [102] (301A)<br />

2.8 [71] (301H)<br />

3.3 [83] 301A<br />

7.5 [189] (301H)<br />

10.0 [254] (301A)<br />

13 [330] (301H)<br />

15.5 [394] (301A)<br />

KEEP AREA FREE OF OBSTRUCTIONS<br />

4.3 [108] MAX<br />

PIPE LENGTH<br />

45°<br />

3 4" FPT REMOTE<br />

FEED OUTLET<br />

Ø5.5 [Ø140]<br />

(6) 0.5 [13] HOLES ON<br />

Ø4.5 [114] B.C<br />

FOR 7/16-20 UNF<br />

A typical installation arrangement is shown in<br />

figure 3. Notice the optional shutoff solenoid in<br />

the liquid supply line. When the refrigeration<br />

load is greatly reduced on an individual air unit,<br />

or if fans are shut off, it is advisable to close<br />

the liquid line solenoid ahead of the float valve<br />

in order to stop liquid feed. Otherwise the body<br />

of liquid in the surge drum will flow down into<br />

the coil and the float valve will continue<br />

feeding, thus filling the coil with liquid<br />

refrigerant. Room thermostats can be used to<br />

stop liquid feed to the evaporators.<br />

Figure 3: Typical Installation<br />

GAS<br />

RETURN<br />

SURGE<br />

DRUM<br />

SUCTION<br />

3 4 " LIQUID SUPPLY<br />

SHUT-OFF<br />

SOLENOID<br />

VALVE<br />

<strong>HA</strong>ND<br />

EXPANSION<br />

VALVE<br />

LIQUID<br />

TO COIL<br />

301H SERIES<br />

FLOAT VALVE<br />

500 SERIES<br />

STRAINER<br />

OIL DRAIN<br />

301H-SB11-01 2