12 Device Description WAGO-I/O-SYSTEM 750<br />

750-495 3-Phase Power Measurement Module<br />

Pos : 20 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Gerätebesc hreibung/Gerätebeschreibung - Übersc hrift 1 @ 3\mod_1233756084656_21.docx @ 27096 @ 1 @ 1<br />

3 Device Description<br />

Pos : 21 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ei nlei tung/Analogei ngangs klemmen/Gerätebeschr eibung - Ei nleitung 750- 0495 @ 16\mod_1376321299425_21.docx @ 128508 @ @ 1<br />

The 3-Phase Power Measurement Module (also called I/O Module) measures the<br />

electrical data in a 3-phase supply network.<br />

The 3 phase voltages are measured via connection to L1, L2, L3 and N. The<br />

currents are fed to I1+ and I1−, I2+ and I2−, I3+ and I3−, IN+ and IN− via current<br />

transformers resp. via ‘Rogowski’ coils to RC1+ and RC1−, RC2+ and RC2−,<br />

RC3+ and RC3−, RCN+ and RCN−. Based on these input signals the I/O module<br />

calculates numerous AC values like voltages, currents, powers (active, reactive<br />

and apparent), energies, power factors, phase shift angles and frequencies.<br />

Furthermore, an analysis of harmonic waves is carried out up to the 41 st harmonic.<br />

The measured values are available in the process image. Therefore, no high<br />

computing power is required from the higher-level controller.<br />

The calculated values indicate whether the load is inductive or capacitive and<br />

whether it consumes or generates energy. For this purpose a 4-quadrant display is<br />

incorporated in WAGO-I/O-CHECK.<br />

The I/O module provides a great number of measured values for a comprehensive<br />

supply network analysis via the fieldbus. By means of the measured values the<br />

operator can regulate the supply to a drive or machine in the best possible way<br />

and protect the installation from damage/failure.<br />

The I/O module 750-495 measures currents up to 1 A, 750-495/000-001 measures<br />

currents up to 5 A and 750-495/000-002 measures currents via ‘Rogowski’ coils<br />

RT500 up to 500 A or via RT2000 up to 2000 A.<br />