16.01.2014 Views

CONSOLE (CCE) SERIES - HVAC Tech Support

CONSOLE (CCE) SERIES - HVAC Tech Support

CONSOLE (CCE) SERIES - HVAC Tech Support

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CLIMATEMASTER WATER-SOURCE HEAT PUMPS<br />

Console (<strong>CCE</strong>) Series<br />

Rev.: 05/23/07D<br />

Performance Data<br />

<strong>CCE</strong>09B<br />

*WPD Adder for<br />

Motorized Valve,<br />

<strong>CCE</strong>09<br />

(Cv = 4.9,<br />

MOPD = 125 psi)<br />

GPM<br />

WPD Adder<br />

PSI<br />

FT<br />

1.3 0.34 0.80<br />

1.9 0.80 1.85<br />

2.5 1.50 3.46<br />

300 CFM Nominal (Rated) Airfl ow<br />

EWT<br />

°F<br />

GPM<br />

WPD* Cooling - EAT 80/67°F Heating - EAT 70°F<br />

PSI FT TC SC Sens/Tot<br />

Ratio<br />

kW HR EER HC kW HE LAT COP<br />

20 2.5 6.2 14.3 Operation Not Recommended 7.2 0.63 5.1 92.3 3.35<br />

30<br />

40<br />

Performance capacities shown in thousands of Btuh<br />

1.3 1.8 4.2 11.3 7.6 0.67 0.48 13.0 23.8 7.5 0.66 5.2 93.0 3.34<br />

1.9 3.2 7.4 11.7 7.7 0.66 0.44 13.2 26.5 7.6 0.67 5.4 93.5 3.36<br />

2.5 5.0 11.6 11.9 7.8 0.66 0.42 13.3 28.1 7.7 0.67 5.4 93.8 3.38<br />

1.3 1.5 3.5 10.9 7.4 0.68 0.54 12.8 20.4 8.1 0.69 5.8 95.1 3.46<br />

1.9 2.6 6.0 11.2 7.5 0.67 0.49 12.9 22.6 8.4 0.70 6.0 95.9 3.52<br />

2.5 4.0 9.2 11.3 7.6 0.67 0.47 13.0 23.9 8.6 0.71 6.2 96.4 3.56<br />

1.3 1.3 3.0 10.6 7.2 0.68 0.60 12.6 17.6 9.1 0.72 6.6 97.9 3.67<br />

50<br />

1.9 2.5 5.8 10.8 7.3 0.68 0.56 12.7 19.4 9.4 0.73 6.9 99.1 3.77<br />

2.5 3.9 9.0 10.9 7.4 0.67 0.53 12.8 20.5 9.7 0.74 7.1 99.7 3.82<br />

1.3 1.2 2.8 10.2 7.1 0.69 0.67 12.5 15.2 10.1 0.75 7.6 101.2 3.94<br />

60<br />

1.9 2.4 5.5 10.4 7.2 0.69 0.62 12.6 16.8 10.6 0.77 8.0 102.7 4.05<br />

2.5 3.7 8.5 10.6 7.2 0.68 0.60 12.6 17.6 10.9 0.77 8.2 103.5 4.12<br />

1.3 1.2 2.8 9.8 6.9 0.71 0.75 12.4 13.1 11.3 0.79 8.6 104.8 4.21<br />

70<br />

1.9 2.2 5.1 10.1 7.0 0.70 0.70 12.5 14.4 11.9 0.80 9.1 106.6 4.34<br />

2.5 3.5 8.1 10.2 7.1 0.69 0.67 12.5 15.2 12.2 0.81 9.4 107.5 4.42<br />

1.3 1.1 2.5 9.3 6.8 0.73 0.83 12.1 11.2 12.5 0.82 9.7 108.4 4.48<br />

80<br />

1.9 2.1 4.9 9.6 6.9 0.71 0.78 12.3 12.4 13.1 0.83 10.3 110.4 4.61<br />

2.5 3.2 7.5 9.8 6.9 0.71 0.75 12.4 13.1 13.5 0.84 10.6 111.5 4.68<br />

1.3 1.1 2.5 9.0 6.7 0.74 0.87 12.0 10.3 13.1 0.83 10.2 110.3 4.60<br />

85<br />

1.9 2.0 4.6 9.4 6.8 0.72 0.82 12.2 11.5 13.7 0.85 10.8 112.3 4.73<br />

2.5 3.1 7.2 9.6 6.9 0.72 0.79 12.3 12.1 14.1 0.86 11.2 113.4 4.79<br />

1.3 1.0 2.3 8.7 6.5 0.75 0.92 11.8 9.4 13.7 0.85 10.8 112.1 4.71<br />

90<br />

1.9 2.0 4.6 9.1 6.7 0.74 0.86 12.0 10.5 14.3 0.87 11.4 114.1 4.83<br />

2.5 3.0 6.9 9.3 6.8 0.73 0.83 12.1 11.1 14.7 0.88 11.7 115.2 4.89<br />

1.3 1.0 2.3 7.9 6.2 0.79 1.01 11.3 7.8<br />

100<br />

1.9 1.9 4.4 8.4 6.4 0.77 0.95 11.6 8.8<br />

2.5 3.0 6.9 8.6 6.5 0.76 0.92 11.8 9.4<br />

1.3 1.0 2.3 6.9 5.7 0.83 1.10 10.7 6.3<br />

Operation Not Recommended<br />

110<br />

1.9 1.9 4.4 7.5 6.0 0.80 1.04 11.1 7.2<br />

2.5 3.0 6.9 7.8 6.2 0.79 1.02 11.3 7.7<br />

Interpolation is permissible; extrapolation is not.<br />

All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.<br />

ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.<br />

Table does not refl ect fan or pump power corrections for ARI/ISO conditions.<br />

All performance is based upon the lower voltage of dual voltage rated units.<br />

Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.<br />

Operation below 40°F EWT is based upon a 15% antifreeze solution.<br />

Operation below 60°F EWT requires optional insulated water/refrigerant circuit.<br />

See performance correction tables for operating conditions other than those listed above.<br />

See Performance Data Selection Notes for operation in shaded areas.<br />

<strong>CCE</strong><br />

10<br />

ClimateMaster Water-Source Heating and Cooling Systems

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!