HMW-<strong>2230</strong> T6<br />
Powered by:<br />
<strong>MTU</strong> 16V 4000 G83<br />
2,228 <strong>kW</strong> at 60 Hz<br />
Generating Set Performance<br />
60 Hz<br />
SERVICE<br />
Rated output<br />
Active power output *<br />
Rated speed<br />
Standard Voltage<br />
Voltage available<br />
kVA<br />
<strong>kW</strong><br />
r.p.m.<br />
V<br />
V<br />
P.R.P<br />
(1)<br />
2.600<br />
2,080<br />
1,800<br />
480<br />
480/277 - 440/254<br />
Performance data refers to Standard Reference Conditions of ISO 8528 : + 25 °C , 100 m ALT, relative humidity 30 %<br />
During running-in period the output increases by approx. 5 % which is taken into consideration at delivery.<br />
Power reduction acc. to DIN ISO 3046. Standard values: Above 100 m ALT approx. 1 % per 100 m. Above 25 °C (77 °F) approx. 4 % per 10 °C (50 °F).<br />
* Considering cos phi= 0,8<br />
Standby<br />
(2)<br />
2.785<br />
2,228<br />
Prime Mover Performance<br />
1.800 r.p.m.<br />
SERVICE<br />
Rated output<br />
Manufacturer<br />
Engine model<br />
4 stroke <strong>Diesel</strong> Engine - Injection type<br />
Aspiration type<br />
Cylinders, number and arrangement<br />
Bore x stroke<br />
Total displacement<br />
Cooling system<br />
Lube oil <strong>spec</strong>ifications<br />
Compression ratio<br />
Specific fuel consumption (P.R.P)<br />
Specific oil consumption (at full load)<br />
Lube oil maximum capacity<br />
Total coolant capacity<br />
Speed governor<br />
Air filter<br />
<strong>kW</strong><br />
2,280<br />
<strong>MTU</strong><br />
16V 4000 G83<br />
DIRECT<br />
2,508<br />
TURBOCHARGED AND AFTERCOOLED<br />
16 - V<br />
mm 170 x 210<br />
L<br />
76.3<br />
WATER<br />
SAE 15 W 40<br />
16.5 : 1<br />
g / <strong>kW</strong>h<br />
208<br />
%<br />
1.0<br />
L<br />
240<br />
L<br />
Type<br />
Type<br />
P.R.P<br />
(1)<br />
175<br />
Electronic, system MDEC<br />
DRY<br />
Standby<br />
(2)<br />
(1) Prime Power (P.R.P.) - ISO 8528: prime power is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year,<br />
between stated maintenance intervals. The permissible average power output during a 24 hours period shall not exceed 80% of the prime power. 10% overload available for governing<br />
purposes only.<br />
(2) Max Stand-by power (ISO 3046 Fuel Stop power): power available for use at variable loads for limited annual time (500h), within the following limits of maximum operating time: 100%<br />
loads 25 h per year - 90% loads 200 h per year No overload available. Applicable in case of failure of the main in areas of reliable electrical network.<br />
Synchronous Generator *<br />
Poles<br />
Winding connections (standard)<br />
Frame mounting<br />
Insulation<br />
Enclosure (according to IEC-34-5)<br />
Exciter system<br />
Voltage regulator<br />
Steady voltage precision<br />
*Alternator used by Gensets meet the requirements of following Standard: BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359.<br />
Nº<br />
class<br />
4<br />
Star - serie<br />
SAE 0 - 21”<br />
H<br />
IP 23<br />
Self-regulating Brushless<br />
A.V.R (Electronic)<br />
within ± 1.5% from no load to full loading with cosφ=0.8÷1
HMW <strong>2230</strong> T6 - 2,228 <strong>kW</strong> at 60 Hz<br />
Generating Set Installation Data<br />
EXHAUST SYSTEM<br />
Max. exhaust temperature at full load<br />
Exhaust gas flow<br />
Maximum allowed back pressure<br />
Recommended exhaust pipe size for L= 5 m<br />
AIR REQUIREMENT<br />
Air requirement for combustion<br />
at 100% load / rated speed<br />
ELECTRIC STARTING SYSTEM<br />
Starting motor output<br />
Minimum recommended battery capacity<br />
Auxiliary voltage<br />
LIQUID CAPACITY<br />
Lube oil system including sump, filters, etc.<br />
FUEL TANK CAPACITY<br />
Open Skid Genset<br />
Soundproofed<br />
º C<br />
º F<br />
m 3 /s<br />
mbar<br />
mm<br />
m 3 /min<br />
ft 3 /min<br />
<strong>kW</strong><br />
CV<br />
Ah<br />
Vcc.<br />
L<br />
1,800 r.p.m.<br />
480<br />
896<br />
7.6<br />
85<br />
-<br />
180<br />
6,356.7<br />
-<br />
-<br />
-<br />
24V<br />
300<br />
L<br />
999<br />
L<br />
999<br />
Generating Set transport data<br />
WEIGHT AND DIMENSIONS OPEN SKID GENSET<br />
Length<br />
Width<br />
Height<br />
Shipping volume seaworthy (Standard supplier)<br />
Dry weight (with standard accessories)<br />
m - ft<br />
m - ft<br />
m - ft<br />
m 3 - ft 3<br />
kg - lb<br />
5.85<br />
1.8<br />
2.40<br />
-<br />
-<br />
-<br />
19.18<br />
5.9<br />
7.87<br />
25.27 - 890.58<br />
-<br />
WEIGHT AND DIMENSIONS SOUNDPROOFED CONTAINER 40''<br />
Length<br />
Width<br />
Height<br />
Shipping volume seaworthy (Standard supplier)<br />
Dry weight (with standard accessories)<br />
Sound level at 7m<br />
* Weights and dimmensions approximate. To consult in factory.<br />
m - ft<br />
m - ft<br />
m - ft<br />
m 3 - ft 3<br />
kg - lb<br />
dB(A)<br />
12.19<br />
2.44<br />
2.59<br />
67.4<br />
17,700<br />
-<br />
-<br />
-<br />
-<br />
-<br />
39.99<br />
7.97<br />
8.49<br />
39,021<br />