PDU Catalogue 2013 - Conteg
PDU Catalogue 2013 - Conteg
PDU Catalogue 2013 - Conteg
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
8. INTELLIGENT POWER DISTRIBUTION UNITS - MONITORED MODELS<br />
8.1 MONITORED <strong>PDU</strong> MODEL: IP-DMI-008C300016<br />
INLET C20<br />
Features<br />
Current Meter<br />
Power Monitor<br />
Protocols<br />
Alarm Thresholds<br />
Event Alert<br />
Digital True RMS Current Meter<br />
Total Power Monitoring by Meter, Web, SNMP, Free Bundle Software<br />
Http, Https, SNMP, DHCP, UDP<br />
User-Defined Alarm Thresholds for Warning and Overload<br />
Email, Trap, Audible Alarm<br />
Specification<br />
General<br />
Output<br />
Input<br />
Protection<br />
(8) IEC 320 C13<br />
(1) IEC 320 C20 inlet (without input power cord)<br />
(1) 16 AMP Circuit Breaker<br />
Communication<br />
IP Address<br />
<strong>PDU</strong> Status<br />
Network<br />
(1) Yellow LED<br />
(1) Green LED<br />
(1) RJ45 for Ethernet<br />
3 Digits Meter<br />
Range: 0A ~ 20 A<br />
Current<br />
Resolution: 0.1A<br />
Precision: +/-2%+/-0.1AMP<br />
Operation<br />
Nominal Voltage<br />
Voltage<br />
Frequency<br />
Max. Output Current<br />
Temperature<br />
230V<br />
200V~ 240V full range<br />
50/60Hz full range<br />
16A (total); Each Outlet 10A<br />
0 ~ 40 Celsius degree<br />
Humidity 0% ~ 90%<br />
Size<br />
Weight<br />
90 x 432 x 44 mm<br />
1.5 kg<br />
16