9.9 3-PHASE MANAGED <strong>PDU</strong> MODEL: IP-DMA-318C36C922<br />
INPUT<br />
Features<br />
Current Meter<br />
Power Monitor<br />
Protocols<br />
Outlet Control<br />
Alarm Thresholds<br />
Temp./Humidity<br />
Event Alert<br />
Specification<br />
General<br />
Output<br />
Input<br />
Protection<br />
Communication<br />
SSL Indication<br />
DHCP Indication<br />
Circuit Status<br />
Output Status<br />
Network<br />
Temp./Humidity<br />
<strong>PDU</strong> ID<br />
Current Meter<br />
Operation<br />
Nominal Voltage<br />
Voltage<br />
Frequency<br />
Load capacity<br />
Max. Input Current<br />
Max. Output Current<br />
(outlet)<br />
Digital True RMS Current Meter<br />
Remote Total Power Monitoring by Meter, Web, SNMP, Free Bundle Software<br />
Http, Https, SNMP, DHCP, UDP<br />
Individual Outlet Control<br />
User-Defined Alarm Thresholds for Warning and Overload<br />
Option Accessory<br />
Email, Trap, Audible Alarm<br />
(18) IEC 320 C13<br />
(6) IEC 320 C19<br />
(1) IEC 309 (3x32A); attached power cord 3 meters long<br />
(6) 16 Amp single-pole Circuit Breaker<br />
(1) Yellow LED<br />
(1) Green LED<br />
(6) Red LED<br />
(24) Green LED<br />
(1) RJ45 for Ethernet<br />
(1) RJ11 for ENV probe connection<br />
1 Digit Seven Segments for <strong>PDU</strong> Identification<br />
3 Digits Seven Segments for True RMS Meter<br />
Range: 0A ~ 20 A<br />
Resolution: 0.1A<br />
Precision: +/-2% +/-0.1AMP<br />
400V AC, 3-Phase 3P+N+PE<br />
230V<br />
50/60Hz full range<br />
22kVA<br />
32A per phase<br />
IEC 320 C13: 10A<br />
IEC 320 C19: 16A<br />
Max. Output Current<br />
(Bank)<br />
16A (2 Banks per phase)<br />
Temperature<br />
0 ~ 40 Celsius degree<br />
Humidity 0% ~ 90%<br />
Size<br />
Weight<br />
56 x 1778 x 44 mm<br />
7.3 kg<br />
32