<strong>LOW</strong> <strong>VOLTAGE</strong> <strong>POOL</strong> <strong>AND</strong> <strong>SPA</strong> <strong>LIGHT</strong> <strong>TRANSFORMER</strong><br />

INSTALLATION <strong>AND</strong> USER’S GUIDE<br />

umps)<br />

ool Products ® )<br />

FAILURE TO FOL<strong>LOW</strong> ALL INSTRUCTIONS <strong>AND</strong> WARNINGS CAN RESULT IN SERIOUS BODILY<br />

INJURY OR DEATH. THIS PRODUCT SHOULD BE INSTALLED <strong>AND</strong> SERVICED ONLY BY A QUALIFIED<br />

<strong>POOL</strong> SERVICE PROFESSIONAL. INSTALLERS, <strong>POOL</strong> OPERATORS <strong>AND</strong> OWNERS MUST READ<br />

THESE WARNINGS <strong>AND</strong> ALL INSTRUCTIONS IN THE OWNER'S MANUAL BEFORE USING THIS<br />

PRODUCT. THESE INSTRUCTIONS MUST BE LEFT WITH THE <strong>POOL</strong> OWNER.<br />

Warnings and safety instructions for <strong>Pentair</strong> Aquatic Systems pumps and other related products are available<br />

at: http://www.pentairpool.com/safety-warnings Call (800) 831-7133 for additional free copies of these<br />

instructions.<br />

SAFETY INSTRUCTIONS<br />

When installing and operating this product and other associated equipment, basic safety precautions should always be followed,<br />

including the following:<br />

1. Read and follow all instructions.<br />

2. This transformer must be installed by a qualified electrician, according to the National Electrical Code (Including article<br />

680) or Canadian Electrical Code (including section 68) and, local code requirements. For Canadian installations, supply<br />

circuit must be protected by a ground fault circuit interrupter.<br />

3. If used for direct connection of underwater lights, refer to NEC 680-21(b) or CEC 68-060, 062 and 066 for further details.<br />

4. Do not install this equipment within 5 feet (3 meters) of any body of water. USE COPPER CONDUCTORS ONLY.<br />

5. Do not exceed the maximum ratings of individual components wiring devices, and current carrying capacity of conductors.<br />

General Information<br />

The safety transformer is specifically designed to supply 12 volts to pool/spa lights and submersible fixtures. A grounded shield<br />

between the primary and secondary windings assures safe operation. This transformer is suitable for direct connections to underwater<br />

pool and spa lights.<br />

MODEL: PS100/ PS300 – 100 Watt and 300 Watt Transformers<br />

INPUT: 120 VOLT 60 Hz<br />

OUTPUT: 12 VAC, 13 VAC or 14 VAC<br />

Specifications:<br />

Enclosure Size: 8.5" H x 4.2" W x 5.05" D.<br />

Mounting brackets top and bottom.<br />

Enclosure Type: Corrosion resistant steel<br />

with special coating.<br />

Knockouts: Four ½” at bottom of enclosure.<br />

* Any combination of bulbs<br />

Technical Support: Call (800) 831-7133<br />

1


Installation<br />

Pool/Spa Underwater Lighting Application<br />

For transformer field wiring information, please refer to the instructions attached to inside of<br />

enclosure front cover.<br />

• The enclosure of the transformer must be provided with a fail-proof ground as required by NEC,<br />

article 680 and any applicable local codes. For Canadian Installations, the supply circuit must be<br />

protected by a ground fault circuit interrupter.<br />

• For direct wiring of underwater lights, the installation must comply with article 680-21(b) of the<br />

National Electrical Code, or articles 68-060, 062 and 066 of the Canadian Electric Code.<br />

• The transformer should be mounted at least one (1) foot above the pool/spa deck level with the field<br />

wiring compartment down.<br />

• Make sure that all unused taps (leads) are separately insulated.<br />

• Use the following tables as a guide to determine the correct wire size.<br />

• Check voltage at bulb terminals after installation. It should be 12 ±0.3 volts.<br />

120 V Primary Inputs (12, 13, 14 VAC) – 100 W Output<br />

Distance<br />

* Feet<br />

2 #6AWG 2 #8AWG 2 #10AWG 2 #12AWG 2 #14AWG<br />

5FT. 12V 12V 12V 12V 12V<br />

30FT 12V 12V 12V 13V 13V<br />

60FT. 12V 12V 13V 13V 14V<br />

90FT 12V 13V 13V 14V<br />

120FT 13V 13V 14V<br />

150FT 13V 13V 14V<br />

180FT 13V 14V<br />

210FT 13V 14V<br />

240FT 13V<br />

* Length of run to light from transformer.<br />

120 VAC Primary Inputs (12, 13, 14 VAC) – 300 W Output<br />

Distance<br />

* Feet<br />

2 #6 AWG 2 #8AWG 2 #10AWG 2 #12AWG<br />

5FT. 12V 12V 12V 12V<br />

10FT 12V 12V 12V 13V<br />

20FT. 12V 12V 13V 13V<br />

30FT 12V 13V 13V 14V<br />

40FT 13V 13V 14V<br />

50FT 13V 13V 14V<br />

60FT 13V 14V<br />

70FT 13V 14V<br />

80FT 13V 14V<br />

90FT 14V<br />

100FT 14V<br />

110FT 14V<br />

* Length of run to light from transformer.<br />

Pool and Spa Lighting Application<br />

For transformer wiring diagram, see instructions on the inside of the front cover.<br />

To ensure proper lighting performance, it’s important to use the correct gauge cable for the total bulb wattage being used.<br />

The following chart shows the minimum gauge cable to use depending on the total bulb wattage for the lighting system. To<br />

determine the total bulb wattage, add the sum of all the individual bulb wattage for the rating for the transformer being<br />

used. Be sure not to exceed the transformer rating.<br />

Series<br />

Total Bulb<br />

Wattage<br />

Recommended<br />

gauge cable<br />

for up to<br />

100 Ft. run*<br />

Series<br />

Total Bulb<br />

Wattage<br />

Recommended<br />

gauge cable for<br />

up to<br />

100 Ft. run*<br />

12<br />

14 - 12<br />

16 - 14 - 12<br />

18 - 16 - 14 - 12<br />

PS100 0 - 100 18 - 16 - 14 - 12<br />

PS300<br />

201 - 300<br />

157 - 200<br />

121 - 156<br />

0 - 120<br />

* For runs between 100 ft. to 150 ft. long,<br />

increase cable size by one gauge.<br />

* For runs between 100 ft. to 150 ft. long,<br />

increase cable size by one gauge.<br />

READ <strong>AND</strong> KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE<br />