7) Accuracy & routine tests:<br />
The metering panels shall be tested for following tests as per IS:3427 by the representative of<br />
purchaser before accepting the supplies<br />
i) power frequency voltage dry test<br />
ii)<br />
iii)<br />
voltage test on auxiliary circuits<br />
Verification of wiring.<br />
The 28 kV pf withstand voltage for one minute as per relevant ISS will be carried on 10% of units<br />
and remaining 90% units shall be tested at 75% of 28 kV i.e. 21 kV pf with stand tests on the<br />
offered lot.<br />
7.2) Following CTs & PTs of same specification are to be supplied free of cost along with cubicles :-<br />
i) Single phase PT- 70 nos.<br />
ii) Single phase CT- 140 nos.<br />
Electrical Superintending Engineer<br />
(Purchase) JSEB, Ranchi.<br />