2 TECHNICAL DATA<br />

<strong>GFC</strong> <strong>300</strong><br />

2.1 General technical data<br />

Interface<br />

RS485, galvanically isolated<br />

Baud rate 1200, 2400, 3600, 4800, 9600, 19200, 38400, 57600 or 115200<br />

Protocol<br />

Maximum participants on bus<br />

Coding<br />

Modbus RTU (available as a separate document on request)<br />

32 per line, master included (may be extended by repeaters)<br />

NRZ bit coding<br />

Address range Modbus: 1...247<br />

Transmission procedure<br />

Bus access<br />

Cable<br />

Distances<br />

Half duplex, asynchronous<br />

Master / slave<br />

Shielded twisted pair for RS 485 applications<br />

Maximum 1.2 km / 3937 ft without repeater (dependant on<br />

baud rate and cable specifications)<br />

2.2 Technical data of the Modbus interface (acc. to EIA standards)<br />

Kind of signal transmission<br />

Maximum number of<br />

transmitter/receivers<br />

Voltage range on converter input<br />

Maximum voltage on converter output<br />

Minimum voltage on driver output, max.<br />

load<br />

Maximum input current (off state)<br />

Receiver input voltage<br />

Sensitivity of the receiver<br />

Receiver input resistance<br />

Short circuit current<br />

Termination / polarization resistors<br />

(if activated by the jumpers X5/X6)<br />

Differential, 2-wire topology<br />

32<br />

-7...+12 V<br />

5V<br />

U diff >1.5V<br />

-20...+20 μA<br />

-7...+12 V<br />

-200...+200 mV<br />

>12kΩ<br />

< 250 mA<br />

120 Ω / 560 Ω<br />

4<br />

www.krohne.com<br />

03/2012 - 7312402100 - AD Modbus <strong>GFC</strong> <strong>300</strong> R01 en