• Fieldbus power supply for<br />
<strong>PROFIBUS</strong> PA and protocol<br />
converter to <strong>PROFIBUS</strong> DP<br />
• Transparent coupling between DP-<br />
Master and PA field devices<br />
• Redundancy for Gateway and/or<br />
<strong>Power</strong> Supply/Conditioner Modules<br />
• Motherboard design for simplified<br />
installation/wiring/maintenance<br />
• Installation in Zone 2/Class I, Div. 2<br />
• Advanced Diagnosis for physical<br />
layer including fieldbus oscilloscope<br />
Function<br />
The <strong>Power</strong> <strong>Hub</strong> for <strong>PROFIBUS</strong><br />
provides protocol conversion and<br />
power supply to up to four <strong>PROFIBUS</strong><br />
PA segments.<br />
The Gateway Module transparently<br />
„displays“ PA field devices as DP<br />
slaves on the DP network with up to 12<br />
Mbps. DCS engineering and device<br />
communication is simplified since all<br />
field devices are treated as DP slaves.<br />
Gateways in redundant configuration<br />
can be connected to all simplex DCS<br />
systems. Redundant gateways also<br />
conform to <strong>PROFIBUS</strong> standards for<br />
Flying Redundancy.<br />
A choice of Fieldbus <strong>Power</strong> Supply and<br />
<strong>Power</strong> Conditioner Modules provide up<br />
to 500 mA to each PA segment (Trunk).<br />
Following the High <strong>Power</strong> Trunk<br />
Concept, field-mounted Field Barriers<br />
provide intrinsically safe Spurs for<br />
connection of field devices.<br />
Motherboards for redundancy of power<br />
modules are available for applications<br />
with demand for high availability.<br />
The <strong>Power</strong> <strong>Hub</strong>’s Basic Diagnostic<br />
Module continously monitors conditions<br />
of all modules. A potential-free contact<br />
annunciates summary alarms.<br />
DTM software accesses gateway status<br />
and advanced diagnostic functions from<br />
remote via dedicated bus system or<br />
<strong>PROFIBUS</strong> DP.<br />
Advanced diagnostics monitor PA<br />
physical layer and communication<br />
status and thus expedite start-up and<br />
troubleshooting. Alarming of long-term<br />
degradation enables pro-active action<br />
for increased plant availability.<br />
G<br />
to DCS<br />
G: Gateway Module<br />
P: <strong>Power</strong> Module<br />
D: Diagnostic Module<br />
P P P P D<br />
4 segments <strong>PROFIBUS</strong> PA<br />
"High <strong>Power</strong> Trunk"<br />
<strong>Power</strong> <strong>Hub</strong> <strong>System</strong> for <strong>PROFIBUS</strong>, redundant<br />
Composition<br />
G G P P P P D P P P P<br />
4 segments <strong>PROFIBUS</strong> PA<br />
"High <strong>Power</strong> Trunk"<br />
Connection to Bulk <strong>Power</strong> Supply<br />
(redundant)<br />
Subject to reasonable modifications due to technical advances.<br />
Copyright Pepperl+Fuchs, Printed in Germany<br />
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 1
Technical data<br />
<strong>PROFIBUS</strong> <strong>Power</strong> <strong>Hub</strong>-<strong>System</strong><br />
Technical data please see individual module data sheet.<br />
Supplementary information<br />
Statement of Conformity, Declaration of Conformity and instructions have to be observed. For information see<br />
www.pepperl-fuchs.com.<br />
Release date 2006-03-01 13:58 Date of issue 2006-03-10 T31128_ENG.xml<br />
Subject to reasonable modifications due to technical advances.<br />
Copyright Pepperl+Fuchs, Printed in Germany<br />
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com<br />
2
Technical data<br />
<strong>PROFIBUS</strong> <strong>Power</strong> <strong>Hub</strong>-<strong>System</strong><br />
B<br />
Overview of <strong>System</strong> Components:<br />
The <strong>PROFIBUS</strong> DP/PA <strong>Power</strong> <strong>Hub</strong> Gateway <strong>System</strong> is comprised of the following components:<br />
Type Code<br />
Motherboards:<br />
MB-FB-GT<br />
MB-FB-GTR<br />
MB-FB-4.GEN<br />
MB-FB-4R.GEN<br />
Modules:<br />
HD2-GTR-4.PA<br />
HD2-FBPS-1.500<br />
HD2-FBPS-1.17.500<br />
HD2-FBPS-1.23.500<br />
HD2-FBCL-1.500<br />
Diagnostic Modules:<br />
HD2-DM-B<br />
HD2-DM-A<br />
Accessories:<br />
ACC-MB-HSK<br />
ACC-MB-HDC<br />
ACC-MB-HGC<br />
For detailed information concerning Motherboards, Gateway, <strong>Power</strong> and Diagnostic Modules please refer to the respective<br />
component data sheets.<br />
Pepperl+Fuchs recommends the following 3 system combinations:<br />
1. Fully redundant system: Redundant coupling and redundant supply<br />
Use the following components: MB-FB-GTR, MB-FB-4R.GEN, 2x HD2-GTR-4PA, 8 <strong>Power</strong> Modules, 1 Diagnostic Module, 1<br />
Sub D cable.<br />
2. Redundant coupling<br />
Use the following components: MB-FB-GTR, MB-FB-4.GEN, 2x HD2-GTR-4PA, 4 <strong>Power</strong> Modules, 1 Diagnostic Module, 1 Sub<br />
D cable.<br />
3. Simplex system<br />
Use the following components: MB-FB-GT, MB-FB-4.GEN, 1x HD2-GTR-4PA, 4 <strong>Power</strong> Modules, 1 Diagnostic Module, 1 Sub<br />
D cable.<br />
Installation instructions<br />
see <strong>System</strong> manual<br />
Description<br />
Gateway Motherboard<br />
Gateway Motherboard, redundant<br />
<strong>Power</strong> <strong>Hub</strong> Motherboard for 4 segments<br />
<strong>Power</strong> <strong>Hub</strong> Motherboard for 4 segments, redundant<br />
<strong>PROFIBUS</strong> DP/PA Gateway Module<br />
<strong>Power</strong> Supply Modul, isolated, Output 500 mA, max. 30 V<br />
<strong>Power</strong> Supply Modul, isolated, Output 500 mA, max. 17 V<br />
<strong>Power</strong> Supply Module, isolated, Output 500 mA, max. 23 V<br />
<strong>Power</strong> Conditioner Modul, non isolated, Output 500 mA<br />
Diagnostic Module, Basic Version<br />
Diagnostic Module, Advanced Version<br />
Screening/Earthing Kit<br />
Diagnostic Link Cable, Length 6 cm<br />
Sub-D-Cable, 9 PIN, to connect the Gateway Motherboards to the <strong>Power</strong> <strong>Hub</strong> Motherboard.<br />
This cable comes with the MB-FB-GT and MB-FB-GTR motherboards.<br />