1 TECHNICAL BACKGROUND ........................................................................ 3<br />
2 SETTING THE FAIL SAFE POSITION........................................................ 3<br />
3 USING THE <strong>PS</strong>EP ...................................................................................... 3<br />
4 WIRING DIAGRAM OF <strong>PS</strong>EP..................................................................... 4<br />
<strong>PS</strong> Automation GmbH BA_<strong>AMS</strong>_<strong>PS</strong>EP_0002.DOC 2
1 TECHNICAL BACKGROUND<br />
The <strong>PS</strong>-<strong>Energy</strong> <strong>Pack</strong> secures the continous power supply of 24VDC in case of mains<br />
breakdown. The <strong>Energy</strong> <strong>Pack</strong> is connected to a mains supplied DC-Power supply (contained<br />
in <strong>PS</strong>-<strong>AMS</strong>) and the actuator (<strong>PS</strong>-<strong>AMS</strong>).<br />
By using a relay implemented in the <strong>Energy</strong> <strong>Pack</strong>, a status information is generated and<br />
given to the <strong>PS</strong>-<strong>AMS</strong>.<br />
This signal is connected to the Power Fault input of <strong>PS</strong>-<strong>AMS</strong>.<br />
As long as the signal of Power fault is active a red LED is blinking on the actuator and reacts<br />
as programmed.<br />
A reset of the Power fault signal will be done automatically when the mains are up.<br />
2 SETTING THE FAIL SAFE POSITION<br />
If Power Fault is detected, the actuator reacts as programmed in the „Safety & Control“<br />
section of the Communication Software.<br />
(Refer to the special Handbook for details about the Communication Software)<br />
The parameter Power fault can be changed to set up different actions:<br />
• Stop Actuator - When failure is detected, the actuator stops immediate, and will not<br />
move until failure is reset.<br />
• Close Valve - Actuator closes the valve immediate.<br />
• Open Valve - Actuator opens the valve immediate.<br />
• <strong>PS</strong>1 - Actuator moves to the given position 1 (as set up in section basics)<br />
• <strong>PS</strong>2 - Actuator moves to the given position 2 (as set up in section basics)<br />
• <strong>PS</strong>3 - Actuator moves to the given position 3 (as set up in section basics)<br />
• <strong>PS</strong>4 - Actuator moves to the given position 4 (as set up in section basics)<br />
• <strong>PS</strong>5 - Actuator moves to the given position 5 (as set up in section basics)<br />
3 USING THE <strong>PS</strong>EP<br />
• The charging-process is indicated by the yellow LED on the <strong>PS</strong>EP, while the green LED<br />
indicates the fully charged status. To avoid a damaging total discharge of the Ni-cad cells,<br />
the <strong>PS</strong>EP switches of its critical charging level, and indicates this by the red LED.<br />
• The complete charging process of <strong>PS</strong>EP needs 20 hours approximately.<br />
<strong>PS</strong> Automation GmbH BA_<strong>AMS</strong>_<strong>PS</strong>EP_0002.DOC 3
4 WIRING DIAGRAM OF <strong>PS</strong>EP<br />
<strong>PS</strong> Automation GmbH<br />
Gesellschaft für Antriebstechnik<br />
Philipp-Krämer-Ring 13<br />
Tel.: (0) 6322/6003-0<br />
Fax: (0) 6322/6003-20<br />
D-67098 Bad Dürkheim<br />
e-mail:<br />
Internet:<br />
info@ps-automation.com<br />
www.ps-automation.com<br />
<strong>PS</strong> Automation GmbH BA_<strong>AMS</strong>_<strong>PS</strong>EP_0002.DOC 4