GB.<strong>TBLZ</strong><strong>24</strong>25.101120<br />

<strong>Instructions</strong> <strong>for</strong> <strong>Installation</strong><br />

<strong>Room</strong> <strong>sensor</strong>, <strong>TBLZ</strong>-1-<strong>24</strong>/GOLD<br />

Outdoor <strong>sensor</strong>, <strong>TBLZ</strong>-1-25/GOLD<br />

Temperature <strong>sensor</strong>, <strong>TBLZ</strong>-1-25-2/MIRUVENT<br />

1. General<br />

The <strong>sensor</strong> is intended <strong>for</strong> wall mounting and is equipped<br />

with a screw terminal connection <strong>for</strong> a cable.<br />

2. Range of Application<br />

<strong>Room</strong> <strong>sensor</strong>, <strong>TBLZ</strong>-1-<strong>24</strong>/GOLD<br />

The room temperature <strong>sensor</strong> is designed <strong>for</strong> supplementing<br />

the extract air temperature <strong>sensor</strong> located inside the air<br />

handling unit. The room <strong>sensor</strong> is used when the temperature<br />

in a room shall be given priority. It can also be used if<br />

there are temperature losses in the extract air duct up to<br />

the air handling unit’s point of measurement.<br />

Outdoor <strong>sensor</strong>, <strong>TBLZ</strong>-1-25/GOLD<br />

The outdoor <strong>sensor</strong> is designed <strong>for</strong> supplementing the<br />

outdoor air temperature <strong>sensor</strong> located inside the air<br />

handling unit. The outdoor <strong>sensor</strong> is used when measurement<br />

of the outdoor temperature is required while the air<br />

handling unit is idle or the outdoor air duct is closed off.<br />

The <strong>sensor</strong> can also be used as a room <strong>sensor</strong> a <strong>sensor</strong> of a<br />

higher enclosure class is required.<br />

Temperature <strong>sensor</strong>, <strong>TBLZ</strong>-1-25-2/MIRUVENT<br />

The outdoor <strong>sensor</strong> is designed <strong>for</strong> measuring the outdoor<br />

air temperature or the room temperature.. It is used <strong>for</strong><br />

offsetting the pressure or airflow setpoint.<br />

3. <strong>Installation</strong><br />

3.1 <strong>Room</strong> <strong>sensor</strong>, <strong>TBLZ</strong>-1-<strong>24</strong><br />

Carefully remove the upper, smaller cover. Then unscrew<br />

the screw to remove the lower, larger cover. Secure the<br />

<strong>sensor</strong> to an interior wall by means of two screws. The<br />

<strong>sensor</strong>’s air flow-through slots must be positioned vertically.<br />

Position the <strong>sensor</strong> at a representative point of measurement<br />

about 1.5 metres above the floor. Avoid sources<br />

of interference such as radiators, direct solar radiation and<br />

the like.<br />

3.2 Outdoor <strong>sensor</strong>, <strong>TBLZ</strong>-1-25/<br />

Temperature <strong>sensor</strong>, <strong>TBLZ</strong>-1-25-2<br />

Secure the <strong>sensor</strong> to an exterior wall by means of two<br />

screws. Note that the <strong>sensor</strong> should be mounted with<br />

the cable gland facing downward. Position the <strong>sensor</strong> at<br />

a representative point of measurement. Avoid sources<br />

of interference such as direct solar radiation, exhaust air<br />

discharge and the like.<br />

If the <strong>sensor</strong> is used as a room <strong>sensor</strong>, locate and install<br />

the <strong>sensor</strong> as described in the paragraph above.<br />

<strong>TBLZ</strong>-1-<strong>24</strong><br />

4. Technical data<br />

4.1 <strong>Room</strong> <strong>sensor</strong>, <strong>TBLZ</strong>-1-<strong>24</strong><br />

<strong>TBLZ</strong>-1-25/<br />

<strong>TBLZ</strong>-1-25-2<br />

Dimensions (W x H x D) 80x80x16 mm<br />

Enclosure class IP 20<br />

Range of measurement -50 °C – +70 °C<br />

4.2 Outdoor <strong>sensor</strong>, <strong>TBLZ</strong>-1-25/<br />

Temperature <strong>sensor</strong>, <strong>TBLZ</strong>-1-25-2<br />

Dimensions (W x H x D) 52x55x27 mm<br />

Enclosure class IP 43<br />

Range of measurement -50 °C – +70 °C<br />

<strong>Swegon</strong> reserves the right to alter specifications. www.swegon.com 1


GB.<strong>TBLZ</strong><strong>24</strong>25.101120<br />

5. Electrical connections<br />

The electrical connections should be wired by a qualified<br />

electrician in accordance with local electrical safety regulations.<br />

5.1 <strong>Room</strong> <strong>sensor</strong>, <strong>TBLZ</strong>-1-<strong>24</strong>/<br />

Outdoor <strong>sensor</strong>, <strong>TBLZ</strong>-1-25 <strong>for</strong> the GOLD<br />

The temperature <strong>sensor</strong> is digital and depending on the<br />

nature of the installation may be sensitive to external<br />

interference. The cable to the temperature <strong>sensor</strong> must<br />

not be run parallel with and near a power cable. If the<br />

<strong>sensor</strong> cable crosses a power cable, it should cross it at a<br />

90° angle.<br />

Outdoor <strong>sensor</strong><br />

<strong>TBLZ</strong>-1-25<br />

<strong>Room</strong> <strong>sensor</strong>,<br />

<strong>TBLZ</strong>-1-<strong>24</strong><br />

GND Data<br />

GOLD<br />

Control unit<br />

Data<br />

GND<br />

Max. permissible length of cable: 100 m<br />

Min. permissible cross-sectional cable area: 0.5 mm²<br />

Digital temperature <strong>sensor</strong>s require correct polarity. Be careful when you wire the conductors.<br />

5.2 Temperature <strong>sensor</strong>, <strong>TBLZ</strong>-1-25-2 <strong>for</strong> the MIRUVENT<br />

Temperature <strong>sensor</strong><br />

<strong>TBLZ</strong>-1-25-2<br />

20 21<br />

MIRU Control<br />

Max. permissible length of cable: 100 m<br />

Min. permissible cross-sectional cable area: 0.5 mm²<br />

2 www.swegon.com<br />

<strong>Swegon</strong> reserves the right to alter specifications.