DALI LS/PD BASIC LI â Combined sensor for ceiling ... - Osram
DALI LS/PD BASIC LI â Combined sensor for ceiling ... - Osram
DALI LS/PD BASIC LI â Combined sensor for ceiling ... - Osram
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Description<br />
Purpose and application<br />
<strong>DA<strong>LI</strong></strong> <strong>LS</strong>/<strong>PD</strong> <strong>BASIC</strong> <strong>LI</strong><br />
The <strong>DA<strong>LI</strong></strong> <strong>LS</strong>/<strong>PD</strong> <strong>BASIC</strong> <strong>LI</strong> <strong>sensor</strong> detects the presence of<br />
persons and measures the intensity of ambient light.<br />
The <strong>sensor</strong> is designed <strong>for</strong> connection to <strong>DA<strong>LI</strong></strong> RS <strong>BASIC</strong> SO<br />
control units and can be installed in luminaires or <strong>ceiling</strong>s.<br />
Function<br />
The <strong>sensor</strong> measures the brightness in the area requiring<br />
control and transmits the light value to the control unit <strong>for</strong> the<br />
purpose of keeping it to an adjustable set value by introducing<br />
artificial light according to the amount of daylight available. As<br />
the amount of daylight increases, artificial lighting is reduced.<br />
The <strong>sensor</strong> always transmits the detection of movements of<br />
persons to the control unit. After the <strong>sensor</strong> stops detecting<br />
motion, the control unit switches the luminaires off following an<br />
adjustable delay period.<br />
Design<br />
Light and motion <strong>sensor</strong><br />
Fitting instructions<br />
A<br />
B<br />
The <strong>sensor</strong> is made up of the following components:<br />
• Light <strong>sensor</strong> (A)<br />
• Motion <strong>sensor</strong> (B)<br />
• Connection cable (C):<br />
––<br />
Green: supply voltage (Vcc)<br />
––<br />
Brown: ground (0V)<br />
––<br />
Yellow: output <strong>for</strong> light measurement value (<strong>LS</strong>)<br />
––<br />
White: output <strong>for</strong> motion signal (<strong>PD</strong>)<br />
• Housing (D)<br />
D<br />
C<br />
Installation<br />
Safety instructions<br />
The <strong>sensor</strong> must only be installed and put into operation by a<br />
qualified electrician. The applicable safety regulations and accident<br />
prevention regulations must be observed.<br />
WARNING!<br />
Exposed, live cables or damaged housing.<br />
Danger of electric shock!<br />
• Only work on the <strong>sensor</strong> when it is de-energised.<br />
CAUTION!<br />
Destruction of the <strong>sensor</strong> and other devices through<br />
incorrect mounting!<br />
• Adhere to the connection diagram.<br />
• Do not route the <strong>sensor</strong> lines together with <strong>DA<strong>LI</strong></strong><br />
or power supply lines.<br />
• When mounting in luminaires, use a UV-resistant<br />
cable.<br />
• Only connect the <strong>sensor</strong> to control units of type<br />
<strong>DA<strong>LI</strong></strong> RC <strong>BASIC</strong> SO.<br />
• Do not exceed the maximum line length.<br />
Mounting the <strong>sensor</strong> in suspended <strong>ceiling</strong>s<br />
The supplied adapter ring can be used <strong>for</strong> mounting the <strong>sensor</strong><br />
in installation housings <strong>for</strong> 50 mm NV halogen light sources,<br />
making it easy to install them in suspended <strong>ceiling</strong>s.<br />
In installation housings with swivel inserts, the installation angle<br />
and thus the detection area can be varied.<br />
Note:<br />
Because the <strong>sensor</strong> cable exits from the side of the <strong>sensor</strong>, not<br />
all installation housings are suitable <strong>for</strong> holding the <strong>sensor</strong>. See<br />
the dimensions provided in the manufacturer in<strong>for</strong>mation.<br />
IV 2009<br />
<strong>DA<strong>LI</strong></strong>_<strong>LS</strong>-<strong>PD</strong>_<strong>BASIC</strong>_<strong>LI</strong>_ma0904en_we1.01.indd<br />
OSRAM GmbH<br />
Kunden Service Center<br />
Customer-Service-Center (CSC)<br />
Steinerne Furt 62<br />
86167 Augsburg<br />
Germany<br />
Tel : +49 (0) 1803 677 - 200<br />
(kostenpflichtig / charges apply)<br />
Fax.: +49 (0) 1803 677 - 202<br />
www.osram.com<br />
www.osram.de<br />
40503008501848<br />
4050300850184<br />
Page 1 of 2
Installation (cont.)<br />
Selecting the installation location<br />
3 m<br />
E Optimal mounting height: 2.5 – 3 m. As the mounting height<br />
increases, the detection area increases and sensitivity is<br />
reduced.<br />
F Monitoring cone: entire workplace; not on window surfaces<br />
E<br />
2,5 m<br />
3,5 m<br />
G Avoid exposure to direct light.<br />
H Place devices that radiate heat outside of the monitoring<br />
cone.<br />
I Avoid drafts (e.g. from ventilators)<br />
100° 100°<br />
F<br />
Connecting the <strong>sensor</strong><br />
G<br />
K Light measurement value<br />
L Motion signal<br />
(+)<br />
(-)<br />
Vcc<br />
0V<br />
<strong>LS</strong><br />
<strong>PD</strong><br />
H<br />
gr<br />
ye<br />
br<br />
wh<br />
I<br />
Appendix<br />
43<br />
13,5 10<br />
Technical data<br />
Operating voltage<br />
Current consumption<br />
Maximum total line<br />
length<br />
Line connection<br />
Nominal 10 V DC<br />
(8 – 20 V DC)<br />
Max. 3 mA DC<br />
100 m<br />
4 wires, stripped and tin-plated,<br />
4 x 0.14 mm²<br />
Operating temperature 0 °C … +50 °C<br />
Operating range Up to 400 lx measured at <strong>sensor</strong><br />
Detection area<br />
Conical, opening angle approx.<br />
100°<br />
Pollution severity 2 (dry, not conductive, as per<br />
IEC 664)<br />
Dimensions (Ø x H) 47 x 24 mm<br />
Weight<br />
Approx. 65 g<br />
Protection type IP 20<br />
Protection class II<br />
Ø 47<br />
Ø 30<br />
44<br />
39<br />
3,2<br />
Dimensioned drawing<br />
2 m<br />
10 1,7<br />
Ø 4<br />
Con<strong>for</strong>mity with the relevant EU directives is<br />
confirmed by the CE symbol.<br />
Page 2 of 2