2.5.2 <strong>DALI</strong> topology<br />

The <strong>DALI</strong> ECGs are wired in parallel to each other and groups are not<br />

taken into consideration. Star configurations are also possible. Ring<br />

wiring is not permitted (indicated by X in the diagram). There is also no<br />

need for terminating resistors on the communication cable.<br />

Figure 8: <strong>DALI</strong> topology<br />

2.5.3 <strong>DALI</strong> parameters in the ECG<br />

The following data can be stored in the <strong>DALI</strong> ECGs when a <strong>DALI</strong><br />

system is started up:<br />

• Group assignment of the <strong>DALI</strong> ECG (max. 16 groups, multiple<br />

assignment is possible)<br />

• Individual address for accessing each ECG directly (max. 64)<br />

• Lighting values for the individual scenes (max. 16)<br />

• ECG parameters that determine the behavior of the ECG:<br />

• Dimming rate<br />

• Behavior if the voltage fails on the interface (System Failure Level)<br />

• Behavior when the mains voltage is restored (Power On Level)<br />

In addition to the above-mentioned options, it is always possible to<br />

address all the devices together, even without programming the devices<br />

beforehand (construction site function).<br />