5.0 Roof<br />

5.1 Roof shall be sloped for positive drainage at a minimum pitch of ¼ “per<br />

foot. Storm water shall be collected by roof drains and internal leaders<br />

connected into an underground storm collection system.<br />

5.2 Roof shall be insulated with rigid insulation board installed over metal roof<br />

deck. Minimum thermal resistance value (R- value) shall be as required<br />

by applicable building code.<br />

5.3 Roof covering shall be EPDM membrane installed in strict accordance<br />

with manufacturer’s recommendations and shall be furnished with a<br />

minimum 15 year warranty.<br />

6.0 Heating, Ventilating and Air Conditioning Equipment<br />

6.1 Individual HVAC rooftop equipment and distribution systems sized to<br />

provide not less than 1 ton of cooling per 350 square feet of area the<br />

Premises, including all thermostatic controls, fire alarm and smoke<br />

detection devices as required by applicable building and life safety codes<br />

installed by Tenant at Tenant’s expense.<br />

7.0 Electrical and other Utility Services<br />

7.1 Electrical service available to the demised Premises shall be 480/277V, 3<br />

phase, 4 wire service in conduit provided from the nearest primary power<br />

source (electrical distribution room or buss duct) with a capacity based<br />

upon 20 watts per square foot. Landlord shall furnish and install conduit<br />

with pull string from the primary power source to the rear of the Premises<br />

with a main disconnect switch. The balance of the electrical<br />

distribution system shall be designed, installed and maintained by<br />

Tenant at Tenant’s expense.<br />

or<br />

7.2 Electrical service available to the demised Premises shall be 208/120V, 3<br />

phase service in conduit provided from the nearest primary power source<br />

(electrical distribution room or buss duct) with a capacity based upon 20<br />

watts per square foot. Landlord shall furnish and install conduit with pull<br />

string from the primary power source to the rear of the Premises with a<br />

main disconnect switch. The balance of the electrical distribution<br />

system shall be designed, installed and maintained by Tenant at<br />

Tenant’s expense.<br />

7.3 Telephone service shall be provided via an empty 1 ¼” conduit with pull<br />

string from the Landlord’s telephone distribution backboard to the rear of<br />

the Premises. The balance of the telephone distribution system shall<br />

be designed, installed and maintained by Tenant at Tenant’s<br />

expense.<br />

7.4 A fire protection sprinkler main trunk line with a supervised fire control<br />

system and a single point of connection within the Premises. The<br />

balance of the fire protection and fire alarm system shall be<br />

designed, installed and maintained by Tenant at Tenant’s expense.<br />