02.06.2014 Views

comparison of practical fault ride-through capability for mv - PSCC

comparison of practical fault ride-through capability for mv - PSCC

comparison of practical fault ride-through capability for mv - PSCC

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Reduction in <strong>fault</strong> clearing time can be reached by reducing<br />

time grading <strong>of</strong> two successive relays or applying<br />

differential protection.<br />

The nowadays undervoltage protection settings in the<br />

Netherlands are such that at voltage levels below 0.8<br />

p.u. all DG-units are disconnected. Comparing the current<br />

settings with the CCT-curves displayed in Figure<br />

13, it can be concluded that the settings <strong>of</strong> the undervoltage<br />

protection can be altered without instability <strong>of</strong><br />

the DG-units.<br />

Based on the data in Figure 12 with the current settings,<br />

the frequency <strong>of</strong> disconnection is 0.37 times per<br />

annum or 9.3 % <strong>of</strong> all the voltage dips (calculated by<br />

summing up all the frequencies <strong>of</strong> the voltage dips below<br />

0.8 p.u.). By applying the developed CCT-curves in<br />

the undervoltage protection the frequency <strong>of</strong> disconnection<br />

can be reduced to 0.02 times per annum or 0.5 % <strong>of</strong><br />

all the voltage dips. This figure holds <strong>for</strong> the wind turbine,<br />

while <strong>for</strong> the CHP-plant there are no disconnections<br />

at all. Thus, the availability <strong>of</strong> the DG-units can be<br />

increased significantly by adjusting the under-voltage<br />

protection in accordance with the CCT-curves.<br />

The <strong>fault</strong> <strong>ride</strong>-<strong>through</strong> capabilities <strong>of</strong> the wind turbine<br />

can be improved by adding a crowbar to the DFIG. The<br />

crowbar separates the rotor side converter from the rotor<br />

circuit. In [10] the operation <strong>of</strong> the crowbar is simulated<br />

and it is demonstrated that <strong>fault</strong> <strong>ride</strong> <strong>through</strong> during and<br />

after a deep voltage dip (0 V remains, 150 ms) is possible.<br />

6 CONCLUSION<br />

In this paper the <strong>ride</strong>-<strong>through</strong> behavior <strong>of</strong> a CHPplant<br />

and a DFIG-based wind turbine is studied. Based<br />

on the data <strong>of</strong> an existing power system including reliability<br />

data a voltage dip pr<strong>of</strong>ile at the generator terminals<br />

is established. This pr<strong>of</strong>ile is combined with the<br />

<strong>fault</strong> clearing times <strong>of</strong> the test system which have led to<br />

a plot where the depth and duration <strong>of</strong> the voltage dips<br />

are indicated. Using the single machine infinite network<br />

scheme the CCT-curves <strong>of</strong> the DG-units are derived.<br />

From stability point <strong>of</strong> view these curves show that it is<br />

not necessary to disconnect the DG-units at a voltage<br />

level <strong>of</strong> 0.8 p.u. (the present setting <strong>of</strong> DG undervoltage<br />

protection in the Netherlands), but at lower levels, which<br />

are dependent on the critical clearing times. These CCTcurves<br />

can be implemented in the undervoltage relay<br />

and prevent switching <strong>of</strong>f during a voltage dip caused by<br />

a <strong>fault</strong> in a HV- or neighboring MV-grid. In some cases<br />

disturbances in the 20 kV grid lead to unstable operation.<br />

This can be prevented by adjusting the <strong>fault</strong> clearing<br />

time or applying differential protection. For DFIG<br />

wind turbines transient stability can be significantly<br />

improved by introduction <strong>of</strong> crowbar protection and<br />

switching between different control strategies <strong>for</strong> normal<br />

operation and <strong>fault</strong> conditions.<br />

The method presented in this paper can be followed<br />

in all locations <strong>of</strong> the grid and prevent ambitious disconnection<br />

<strong>of</strong> DG.<br />

REFERENCES<br />

[1] B.M. Buchholz, “Dynamic Simulation <strong>of</strong> Renewable<br />

Energy Sources and Requirements on Fault Ride<br />

Through Behaviour”, Power Engineering Society<br />

General Meeting, Montreal, Canada, June, 2006<br />

[2] F.M. Gatta, F. Ilicento, S. Lauria and P. Masato,<br />

“Behaviour <strong>of</strong> Dispersed Generation in Distribution<br />

Networks During System Disturbances. Measures to<br />

prevent disconnection”, CIRED 17th International<br />

Conference on Electricity Distribution, Barcelona,<br />

May 2003<br />

[3] I. Erlich and U. Bachmann, “Grid Code Requirements<br />

Concerning Connection and Operation <strong>of</strong><br />

Wind Turbines in Germany”, IEEE Power Engineering<br />

Society General Meeting, San Francisco, Cali<strong>for</strong>nie,<br />

USA, 2005<br />

[4] G. Daniëls, “Betrieb von Mittelspannungsnetzen mit<br />

hoher Blockheizkraftwerkeinspeisung”, Band 39,<br />

dissertation Rheinisch-Westfälischen Technische<br />

Hochschule Aachen, 1996 (in German)<br />

[5] “SimPowerSystems User's Guide”, The Mathworks,<br />

2007<br />

[6] A.D. Hansen and G. Michalke, “Voltage grid support<br />

<strong>of</strong> DFIG wind turbines during grid <strong>fault</strong>s”,<br />

European Wind Energy Conference & Exhibition,<br />

Milan, Italy, May 2007<br />

[7] J.F.G. Cobben, “Power Quality: Implications at the<br />

Point <strong>of</strong> Connection”, PhD Thesis, ISBN: 978-90-<br />

386-1030-6, Eindhoven University <strong>of</strong> Technology,<br />

June 2007<br />

[8] R. Luiten et al, “Reliability <strong>of</strong> Electricity Networks<br />

in the Netherlands <strong>for</strong> 2006”, KEMA, May 2007 (in<br />

Dutch)<br />

[9] M.H.J. Bollen, “Understanding Power Quality Problems,<br />

Voltage Sags and Interruptions”, Piscataway,<br />

NJ: IEEE press, 1999<br />

[10]I. Erlich, H. Wrede and C. Feltes, “Dynamic Behavior<br />

<strong>of</strong> DFIG-Based Wind Turbines during Grid<br />

Faults”, PCC Power Conversion Conference, Nagoya,<br />

Japan, April, 2007<br />

16th <strong>PSCC</strong>, Glasgow, Scotland, July 14-18, 2008 Page 6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!